T-CONTROL
38
Term
Description
Unit
Must temperature
Setting the must temperature (47-85) of the boiler
°C
Min. Temperature
Activate/setting the min. temperature (20-58) (ON/OFF)
▪
With activated min. Outside of the hot water tank loading time, the hot
water tank temperature is set to the set min. temperature loaded.
If the hot water tank temperature is below the value of the set min.
temperature, the hot water tank loading starts.
°C
Min. loading
Indicates/activates the min. loading (20-58) (ON/OFF)
▪
With activated min. Outside of the hot water tank loading time, the hot
water tank temperature is set to the set min.
If hot water tank temperature is lower than the min. loading / temperature
value, the hot water tank loading will start.
°C
Circulation
temperature*
Setting the circulation temperature of hot water tank
°C
Menu "Aggregate-Test"
Agg-Test
1
Hot water tank pump*
If the indicator light lights, the output for controlling of the hot water tank
pump is switched.
Loading valve
If the indicator light lights, the output for controlling of the loading valve is
switched.
Circulation pump
Indicates the state of the hot water tank pump:
If the indicator lamp lights up, the hot water tank pump is activated and
the hot water tank gets charged.
Menu "time program / barrier times / circulation times“
Time program
1 2 3
Time 1
1 - 3 times can be set. The second and third time can be added by the
+. Example:
▪
time 1:
08:00
– 10:00
▪
time 2:
15:00
– 21:00
▪
time 3:
00:00
– 00:00
-
08:00
– 11:00
Setting up individual hot water tank loading times of every weekday
-
By pressing the symbol Monday preset gets assigned to remaining
weekdays
-
Barrier times
4 5
Time 1
1 - 2 times can be set. The second time can be added by the +.
Example: see time program
-
08:00
– 11:00
Setting up individual hot water tank loading times of every weekday,
when it will be not heated
-
By pressing the symbol Monday preset gets assigned to remaining
weekdays.
-
Circulation time
6 7 8
Time 1
1 - 3 times can be set. The second time can be added by the +.
Example: see time program
-
08:00
– 11:00
Setting up individual hot water tank loading times of every weekday,
when the hot water tank circulates.
-
By pressing the symbol Monday preset gets assigned to remaining
weekdays.
-
Содержание firematic CONDENSATION 30
Страница 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic CONDENSATION 30 40 ...
Страница 17: ...Temperature manager 8 17 Fig 8 6 Example temperature manager when time mode without difference ...
Страница 83: ...Annex 15 83 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Страница 84: ...15 Annex 84 Hydraulic recommendation 2 ...
Страница 85: ...Annex 15 85 15 2 Solar module Program 1 ...
Страница 86: ...15 Annex 86 Program 2 ...
Страница 87: ...Annex 15 87 Program 3 ...
Страница 88: ...15 Annex 88 Program 4 ...
Страница 89: ...Annex 15 89 Program 5 ...
Страница 90: ...15 Annex 90 Program 6 ...
Страница 91: ...Notes 16 91 16 NOTES ...