Page 7
HERZ - Pump group Simple 3 F532
HERZ - Pump group Simple
Contact thermostat used in HERZ - Pump group Simple
General information
Contact thermostat dimensions
Contact thermostat data
Type: Afriso GAT / 7HC
Application: contact thermostat for use in heating, air conditioning, ventilation,
with clamping tape for mounting on pipes
from 16 mm to max. 100 mm diameter
Setting range: 20/90 ° C - temperature adjustable from inside the housing
Switching differential: Δt 8 K ± 2 K
Sensor element: bimetal
Switching contact: changeover contact, NC16 (2,5) A 250V AC, NO 2,5A 250 V AC V
Housing: base plate galvanized steel, upper part gray plastic
Max. Temperature: 85 ° C on the housing
Protection class: IP 20
Cable entry: screw connection M20x1.5
Conformity: CE marking, EU directives 2014/35 / EU (LVD), 2014/30 / EU
(EMC), 2011/65 / EU (RoHS)
Safety instructions:
There is a risk of electric shock, injury or death. Installation, commissioning, repair and decommissioning are carried
out by qualified persons in accordance with the statutory provisions. Work on electrical parts may be carried out only
by a qualified electrician. From the power supply disconnect device before removing the cover of the unit or if the
cover is damaged. Never touch live parts! Check the heat resistance of the pipes. Dispose of the appliance in the
household waste. Device disposal according to local regulations (electrical equipment).
Page 7
HERZ - Mixing set
Contact thermostat data
Type:
Afriso GAT / 7HC
Application:
contact thermostat for use in heating, air conditioning, ventilation,
with clamping tape for mounting on pipes
from 16 mm to max. 100 mm diameter
Setting range:
20/90 ° C - temperature adjustable from inside the housing
Switching differential:
Δt 8 K + 2 K
Sensor element:
bimetal
Switching contact:
changeover contact, NC16 (2,5) A 250V AC, NO 2,5A 250 V AC V
Housing:
base plate galvanized steel, upper part gray plastic
Max. Temperature:
85 ° C on the housing
Protection class:
IP 20
Cable entry:
screw connection M20x1.5
Conformity:
CE marking, EU directives 2014/35 / EU (LVD), 2014/30 / EU
(EMC), 2011/65 / EU (RoHS)
Safety instructions:
There is a risk of electric shock, injury or death. Installation, commissioning, repair and decommissioning are carried
out by qualified persons in accordance with the statutory provisions. Work on electrical parts may be carried out only
by a qualified electrician. From the power supply disconnect device before removing the cover of the unit or if the cover
is damaged. Never touch live parts! Check the heat resistance of the pipes. Dispose of the appliance in the household
waste. Device disposal according to local regulations (electrical equipment).