HERZ - Pump group Simple 3 F532

 

   Stroke [%]

kvs [%]

0

10

20

30

40

50

60

70

80

90

100

0

10

20

30

40

50

60

70

80

90

100

B... AB

Joint flow

A... AB

kvs [m

3

/h]

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

Maintaince

According to EN 806-5 (point 6. Operation) valves should always be in their fully opened or closed position and 

actuated at regular intervals to ensure they remain operational. Therefore HERZ Ball valves should be closed and 

opened periodically at least twice a year. This prevents the ball valve from blocking, reduces sediment deposition and 

reduces the possibility of corrosion inside the valve.

Disposal instructions

The disposal of 

HERZ - Pump group Simple

 must not endanger the health or the environment. National legal 

regulations for proper disposal of the 

HERZ - Pump group Simple

 have to been followed.

Operating data

Nominal pressure:                                                       6 bar

Max. operating temperature:                                      110 °C (suggested max. 50 °C)

Min. operating temperature:                                        2 °C

kvs −AB−A:                                                                  5,0

kvs −AB−B:                                                                  3,8

Stroke of the mixing valve:                                          3,7 mm

Pressure difference between circuits: Δp

primary c

 > p

secondary c

Medium:

Heating water according to ÖNORM H5195 or VDI- Standard 2035. The use of ethylene, or propylene glycol in a 

mixing ratio 25- 50% is allowed. EPDM gaskets can be affected by Mineral oils lubricants and thus lead to failure of 

the EPDM seals. Please refer to manufacturers documentation when using ethylene glycol products for frost and 

corrosion protection.

Components and labels of HERZ Pump group Simple

1. Mixing valve

2. Non-return valve

3. Thermostatic head 1 

9420

 88

4. Termometer of inlet flow

5. Circulation pump Wilo PARA 15-130/6-43/SC

    (3 

F532 

36 - space for pump)

6. Spacer

7. Immersion sleeve

8. Connectors with free moving nut

9. Ball valves

10. Contact control thermostat

11. Eccentric connector

 

*each set contains 4 additional pcs

of EPDM gaskets for flat sealing, 

2 connectors with free moving nut.

Mixing valve characteristic

Page 3

HERZ - Mixing set

Maintaince

According to EN 806-5 (point 6. Operation) valves should always be in their fully opened or closed position and actuated 

at regular intervals to ensure they remain operational. Therefore HERZ Ball valves should be closed and opened 

periodically at least twice a year. This prevents the ball valve from blocking, reduces sediment deposition and reduces 

the possibility of corrosion inside the valve.

Disposal instructions

The disposal of HERZ Mixing set must not endanger the health or the environment. National legal regulations for proper 

disposal of the HERZ Mixing set have to been followed.

Operating data

Nominal pressure: 

  

 

6 bar  

Max. operating temperature: 

  

 

110 °C (suggested max. 50 °C) 

Min. operating temperature: 

  

 

2 °C  

kv

s

 

 −AB−A: 

  

 

5,0

kv

s

  −AB−B: 

  

 

3,8  

Stroke of the mixing valve: 

  

 

3,7 mm

Pressure difference between circuits: 

  

 

∆p

primary c

>

p

secondary c

 

Medium:

Heating water according to ÖNORM H5195 or VDI- Standard 2035. The use of ethylene, or propylene glycol in a 

mixing ratio 25- 50% is allowed. EPDM gaskets can be affected by Mineral oils lubricants and thus lead to failure of the 

EPDM seals. Please refer to manufacturers documentation when using ethylene glycol products for frost and corrosion 

protection.

 

Components and labels of HERZ mixing set

1. Mixing valve

2. Non-return valve

3. Thermostatic head 1 

9420

 88

4. Thermometer of inlet flow

5. Circulation pump Wilo PARA 15-130/6-43/SC 

    (1732007 space for pump)

6. Spacer

7. Immersion sleeve

8. Connectors with free moving nut

9. Ball valves

10. Contact control thermostat

11. Eccentric connector

 

*each set contains 4 additional pcs

of EPDM gaskets for flat sealing, 

2 connectors with free moving nut.

Mixing valve characteristic

B

B

AB

AB

A

A

   Stroke [%]

kvs [%]

0

10

20

30

40

50

60

70

80

90

100

0

10

20

30

40

50

60

70

80

90

100

B... AB

Joint flow

A... AB

kvs [m

3

/h]

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

Содержание 3 F532 34

Страница 1: ...s document are reflecting the information available at the time of going to print and meant for informational purpose only Herz Armaturen reserves the right to modify and change products as well as its technical specifications and or it function according to technological progress and require ments All diagrams are indicative in nature and do not to be complete It is understood that all images of ...

Страница 2: ...re obliged to point out that the material lead is listed on the SVHC list and that all brass components manufactured in our products exceed 0 1 w w lead CAS 7439 92 1 EINECS 231 100 4 Since lead is a component part of an alloy actual exposure is not possible and therefore no additional information on safe use is necessary HERZ Mixing set Dimensions Art Nr M mm G in G1 in H mm H1 mm H2 mm H3 mm H4 ...

Страница 3: ... 4 additional pcs of EPDM gaskets for flat sealing 2 connectors with free moving nut Mixing valve characteristic Page 3 HERZ Mixing set Maintaince According to EN 806 5 point 6 Operation valves should always be in their fully opened or closed position and actuated at regular intervals to ensure they remain operational Therefore HERZ Ball valves should be closed and opened periodically at least twi...

Страница 4: ... 30 40 Q m3 h 0 0 5 1 0 2 0 1 5 2 5 3 0 III max II I 0 0 2 0 4 0 6 0 8 Q l s 02 468 10 Q lgpm 0 0 2 0 4 0 6 0 8 Q l s 02 468 10 Q lgpm 6 H m 4 5 3 2 1 0 60 p kPa 40 50 30 20 10 0 Q m3 h 0 0 5 1 0 2 0 1 5 2 5 3 0 II I Wilo Para 15 6 25 6 30 6 1 230 V Rp Rp 1 Rp 1 III m ax 6 H m 4 5 3 2 1 0 60 p kPa 40 50 30 20 10 0 Q m3 h 0 0 5 1 0 2 0 1 5 2 5 3 0 III m a x II I Wilo Para 15 6 25 6 30 6 1 230 V Rp ...

Страница 5: ...D lights up flashes in case of a fault Display of selected control mode Δp v Δp c and constant speed Display of selected pump curve I II III within the control mode LED indicator combinations during the pump venting function manual restart and key lock Commissioning Commissioning only by qualified technicians Manual restart The pump attempts an automatic restart upon detecting a blockage If the pu...

Страница 6: ...xclusively intended for circulating fluids in hot water heating systems and similar systems with constantly changing volume flows Permitted fluids Heating water according to VDI 2035 CH SWKI BT 102 01 Water glycol mixtures with a maximum of 50 glycol Glycol has a higher viscosity than water If admixtures of glycol are used the pumping data of the pump must be corrected to match the mixing ratio In...

Страница 7: ...ispose of the appliance in the household waste Device disposal according to local regulations electrical equipment Page 7 HERZ Mixing set Contact thermostat data Type Afriso GAT 7HC Application contact thermostat for use in heating air conditioning ventilation with clamping tape for mounting on pipes from 16 mm to max 100 mm diameter Setting range 20 90 C temperature adjustable from inside the hou...

Страница 8: ... can occur depending on the type of installation and the system design Skala 1 2 3 4 5 6 7 C 20 25 30 35 40 45 50 Page 8 HERZ Mixing set HERZ mixing set Thermostats with Contact Sensor used in HERZ mixing set General information Contact thermostat dimensions Thermostat data Type 1 9420 88 Setting range 20 50 C Max differential pressure 0 75 bar for low noise operation should not exceed 0 2 bar Cap...

Страница 9: ...unit G 1 SW 36 M 30x1 5 1900979R 1 Ball valve with free moving nut G 3 4 G1 G1 L 80 1832024R 1 Page 9 HERZ Mixing set Spare parts Sketch Description Article Nr Pcs Thermometer 0 80 C 2220654H 1 Adapter G1 G1 1 4 It is used for connecting the mixing set with the floor heating distributor G 1 G1 1 1 4 SW 41 2250801R 2 Connector with free moving nut G1 R1 It is used for connecting the mixing set with...

Страница 10: ...quirements All diagrams are indicative in nature and do not to be complete It is understood that all images of Herz products are symbolic representations and therefore may visually differ from the actual product Colours may differ due to printing technology used In case of any further questions don t hesitate to contact your closest HERZ Branch Office Example of system with HERZ products Mixing Se...

Отзывы: