Page 5
HERZ - Pump group Simple 3 F532
Product description
1. Operating button for pump adjustment
2. Run signal/fault signal LED
3. Display of selected control mode
4. Display of selected characteristic curve (I, II, III)
5. Mains connection: 3-pin plug connection
Indicator lights - LEDs
- Signal display
• LED is lit up in green in normal opertaion
• LED lights up/flashes in case of a fault
- Display of selected control mode Δp-v, Δp-c and constant speed
- Display of selected pump curve (I, II, III) within the control mode
- LED indicator combinations during the pump venting function, manual restart
and key lock
Commissioning
Commissioning only by qualified technicians.
The pump attempts an automatic restart upon detecting a blockage. If the pump
does not restart automatically:
- Activate manual restart via the operating button: press and hold for 5 seconds,
then release.
• The restart function is initiated, and lasts max. 10 minutes.
• The LEDs flash in succession clockwise.
- To cancel, press and hold the operating button for 5 seconds.
NOTICE
After the restart, the LED displays shows the previously set values of the
pump.
Page 5
HERZ - Mixing set
Pump data
Type:
WILO PARA 15-130/6-43/SC
Thread:
G 1"
Overall length:
130 mm
Energy Efficiency Index (EEI):
≤ 0,20
Max. delivery head:
6,7 m
Max. volume flow:
3,2 m3/h
Max. operating temperature:
100 °C
Maxi. operating pressure:
10 bar
Mains connection:
1~230 V +10%/-15%, 50/60 Hz (tensiune standard /IEC 8 standard voltage)
Protection class:
IPx4D
Insulation class:
F
Minimum suction head at suction port to avoid cavitation at water pumping temperature
Minimum suction head at 50/95 °C:
0.5 / 4.5 m
Pump hydraulic operation area
Product description
1 Operating button for pump adjustment
2 Run signal/fault signal LED
3 Display of selected control mode
4 Display of selected characteristic curve (I, II, III)
5 Mains connection: 3-pin plug connection
Indicator lights - LEDs
-
Signal display
•
LED is lit up in green in normal opertaion
•
LED lights up/flashes in case of a fault
-
Display of selected control mode Δp-v, Δp-c and constant speed
-
Display of selected pump curve (I, II, III) within the control mode
-
LED indicator combinations during the pump venting function, manual restart
and key lock
Commissioning
Commissioning only by qualified technicians.
Manual restart
The pump attempts an automatic restart upon detecting a blockage. If the pump
does not restart automatically:
-
Activate manual restart via the operating button: press and hold for 5 seconds,
then release.
•
The restart function is initiated, and lasts max. 10 minutes.
•
The LEDs flash in succession clockwise.
-
To cancel, press and hold the operating button for 5 seconds.
i
NOTICE
After the restart, the LED displays shows the previously set values of the pump.
Page 5
HERZ - Mixing set
Pump data
Type:
WILO PARA 15-130/6-43/SC
Thread:
G 1"
Overall length:
130 mm
Energy Efficiency Index (EEI):
≤ 0,20
Max. delivery head:
6,7 m
Max. volume flow:
3,2 m3/h
Max. operating temperature:
100 °C
Maxi. operating pressure:
10 bar
Mains connection:
1~230 V +10%/-15%, 50/60 Hz (tensiune standard /IEC 8 standard voltage)
Protection class:
IPx4D
Insulation class:
F
Minimum suction head at suction port to avoid cavitation at water pumping temperature
Minimum suction head at 50/95 °C:
0.5 / 4.5 m
Pump hydraulic operation area
Product description
1 Operating button for pump adjustment
2 Run signal/fault signal LED
3 Display of selected control mode
4 Display of selected characteristic curve (I, II, III)
5 Mains connection: 3-pin plug connection
Indicator lights - LEDs
-
Signal display
•
LED is lit up in green in normal opertaion
•
LED lights up/flashes in case of a fault
-
Display of selected control mode Δp-v, Δp-c and constant speed
-
Display of selected pump curve (I, II, III) within the control mode
-
LED indicator combinations during the pump venting function, manual restart
and key lock
Commissioning
Commissioning only by qualified technicians.
Manual restart
The pump attempts an automatic restart upon detecting a blockage. If the pump
does not restart automatically:
-
Activate manual restart via the operating button: press and hold for 5 seconds,
then release.
•
The restart function is initiated, and lasts max. 10 minutes.
•
The LEDs flash in succession clockwise.
-
To cancel, press and hold the operating button for 5 seconds.
i
NOTICE
After the restart, the LED displays shows the previously set values of the pump.
Page 5
HERZ - Mixing set
Pump data
Type:
WILO PARA 15-130/6-43/SC
Thread:
G 1"
Overall length:
130 mm
Energy Efficiency Index (EEI):
≤ 0,20
Max. delivery head:
6,7 m
Max. volume flow:
3,2 m3/h
Max. operating temperature:
100 °C
Maxi. operating pressure:
10 bar
Mains connection:
1~230 V +10%/-15%, 50/60 Hz (tensiune standard /IEC 8 standard voltage)
Protection class:
IPx4D
Insulation class:
F
Minimum suction head at suction port to avoid cavitation at water pumping temperature
Minimum suction head at 50/95 °C:
0.5 / 4.5 m
Pump hydraulic operation area
Product description
1 Operating button for pump adjustment
2 Run signal/fault signal LED
3 Display of selected control mode
4 Display of selected characteristic curve (I, II, III)
5 Mains connection: 3-pin plug connection
Indicator lights - LEDs
-
Signal display
•
LED is lit up in green in normal opertaion
•
LED lights up/flashes in case of a fault
-
Display of selected control mode Δp-v, Δp-c and constant speed
-
Display of selected pump curve (I, II, III) within the control mode
-
LED indicator combinations during the pump venting function, manual restart
and key lock
Commissioning
Commissioning only by qualified technicians.
Manual restart
The pump attempts an automatic restart upon detecting a blockage. If the pump
does not restart automatically:
-
Activate manual restart via the operating button: press and hold for 5 seconds,
then release.
•
The restart function is initiated, and lasts max. 10 minutes.
•
The LEDs flash in succession clockwise.
-
To cancel, press and hold the operating button for 5 seconds.
i
NOTICE
After the restart, the LED displays shows the previously set values of the pump.
Page 5
HERZ - Mixing set
Pump data
Type:
WILO PARA 15-130/6-43/SC
Thread:
G 1"
Overall length:
130 mm
Energy Efficiency Index (EEI):
≤ 0,20
Max. delivery head:
6,7 m
Max. volume flow:
3,2 m3/h
Max. operating temperature:
100 °C
Maxi. operating pressure:
10 bar
Mains connection:
1~230 V +10%/-15%, 50/60 Hz (tensiune standard /IEC 8 standard voltage)
Protection class:
IPx4D
Insulation class:
F
Minimum suction head at suction port to avoid cavitation at water pumping temperature
Minimum suction head at 50/95 °C:
0.5 / 4.5 m
Pump hydraulic operation area
Product description
1 Operating button for pump adjustment
2 Run signal/fault signal LED
3 Display of selected control mode
4 Display of selected characteristic curve (I, II, III)
5 Mains connection: 3-pin plug connection
Indicator lights - LEDs
-
Signal display
•
LED is lit up in green in normal opertaion
•
LED lights up/flashes in case of a fault
-
Display of selected control mode Δp-v, Δp-c and constant speed
-
Display of selected pump curve (I, II, III) within the control mode
-
LED indicator combinations during the pump venting function, manual restart
and key lock
Commissioning
Commissioning only by qualified technicians.
Manual restart
The pump attempts an automatic restart upon detecting a blockage. If the pump
does not restart automatically:
-
Activate manual restart via the operating button: press and hold for 5 seconds,
then release.
•
The restart function is initiated, and lasts max. 10 minutes.
•
The LEDs flash in succession clockwise.
-
To cancel, press and hold the operating button for 5 seconds.
i
NOTICE
After the restart, the LED displays shows the previously set values of the pump.
Page 5
HERZ - Mixing set
Pump data
Type:
WILO PARA 15-130/6-43/SC
Thread:
G 1"
Overall length:
130 mm
Energy Efficiency Index (EEI):
≤ 0,20
Max. delivery head:
6,7 m
Max. volume flow:
3,2 m3/h
Max. operating temperature:
100 °C
Maxi. operating pressure:
10 bar
Mains connection:
1~230 V +10%/-15%, 50/60 Hz (tensiune standard /IEC 8 standard voltage)
Protection class:
IPx4D
Insulation class:
F
Minimum suction head at suction port to avoid cavitation at water pumping temperature
Minimum suction head at 50/95 °C:
0.5 / 4.5 m
Pump hydraulic operation area
Product description
1 Operating button for pump adjustment
2 Run signal/fault signal LED
3 Display of selected control mode
4 Display of selected characteristic curve (I, II, III)
5 Mains connection: 3-pin plug connection
Indicator lights - LEDs
-
Signal display
•
LED is lit up in green in normal opertaion
•
LED lights up/flashes in case of a fault
-
Display of selected control mode Δp-v, Δp-c and constant speed
-
Display of selected pump curve (I, II, III) within the control mode
-
LED indicator combinations during the pump venting function, manual restart
and key lock
Commissioning
Commissioning only by qualified technicians.
Manual restart
The pump attempts an automatic restart upon detecting a blockage. If the pump
does not restart automatically:
-
Activate manual restart via the operating button: press and hold for 5 seconds,
then release.
•
The restart function is initiated, and lasts max. 10 minutes.
•
The LEDs flash in succession clockwise.
-
To cancel, press and hold the operating button for 5 seconds.
i
NOTICE
After the restart, the LED displays shows the previously set values of the pump.
Page 5
HERZ - Mixing set
Pump data
Type:
WILO PARA 15-130/6-43/SC
Thread:
G 1"
Overall length:
130 mm
Energy Efficiency Index (EEI):
≤ 0,20
Max. delivery head:
6,7 m
Max. volume flow:
3,2 m3/h
Max. operating temperature:
100 °C
Maxi. operating pressure:
10 bar
Mains connection:
1~230 V +10%/-15%, 50/60 Hz (tensiune standard /IEC 8 standard voltage)
Protection class:
IPx4D
Insulation class:
F
Minimum suction head at suction port to avoid cavitation at water pumping temperature
Minimum suction head at 50/95 °C:
0.5 / 4.5 m
Pump hydraulic operation area
Product description
1 Operating button for pump adjustment
2 Run signal/fault signal LED
3 Display of selected control mode
4 Display of selected characteristic curve (I, II, III)
5 Mains connection: 3-pin plug connection
Indicator lights - LEDs
-
Signal display
•
LED is lit up in green in normal opertaion
•
LED lights up/flashes in case of a fault
-
Display of selected control mode Δp-v, Δp-c and constant speed
-
Display of selected pump curve (I, II, III) within the control mode
-
LED indicator combinations during the pump venting function, manual restart
and key lock
Commissioning
Commissioning only by qualified technicians.
Manual restart
The pump attempts an automatic restart upon detecting a blockage. If the pump
does not restart automatically:
-
Activate manual restart via the operating button: press and hold for 5 seconds,
then release.
•
The restart function is initiated, and lasts max. 10 minutes.
•
The LEDs flash in succession clockwise.
-
To cancel, press and hold the operating button for 5 seconds.
i
NOTICE
After the restart, the LED displays shows the previously set values of the pump.