36
EN
8.
Malfunction diagnosis
Fault
Cause
Remedy
1. Oil firing unit
Fault signal lamp is not lighting
No voltage is present
Check wiring
Boiler temperature control has not
been set correctly
Adjust properly
Fault signal lamp is lighting
Oil firing unit set to malfunction
Correct the fault
Oil firing unit is defective
Exchange
Terminal socket wring is not correct
Check wiring
Check oil pre-heater
Decode cause of malfunction through LED flashing diode Remedy of decoded malfunction
according to Chapter. 2.6 (only for Siemens LMO 14)
according to error diagnosis, point 2 ... 10
2. Motor
Motor will not start
Defective release thermostat in oil pre-heater
Exchange oil pre-heater
Capacitor is defective
Exchange capacitor
Tight bearing
Exchange motor
Tight oil pump
Exchange oil pump
Motor is running with heavy noise
Defective motor
Exchange motor
Defective bearing
Exchange motor
Defective oil pump
Exchange oil pump
3. Ignition
No build up of ignition spark
Defective ignition unit
Exchange ignition unit
Defective ignition wire
Exchange ignition wire
Defective oil firing unit
Exchange oil firing unit
Defective insulator
Exchange ignition electrode
Slight ignition spark existing
Improper position of ignition electrodes
Position ignition electrodes
Very dirty ignition electrodes
Clean ignition electrodes carefully
4. Oil pump
Fluctuating oil pressure, oil pump runs with Leaking suction line (air entry)
Check oil supply (see Chapter 3.5)
heavynoise, oil pressure does not build up Oil supply is not in accordance with standard settings
Check oil supply (see Chapter 3.5)
Suction line is not de-aerated
De-aerate suction line
Oil stop valve is locked
Open oil stop valve
Defective coupling
Exchange coupling
Dirty oil pump filter
Carefully clean oil pump filter
Dirty preliminary filter
Clean / exchange preliminary filter
Defective oil pump gear
Exchange oil pump
Discharge of paraffin (+4°C)
Install cold insulation
Heating oil no longer free-flowing (-1°C)
Install cold insulation
5. Solenoid valve
Solenoid valve does not open
Defective solenoid valve coil
Exchange solenoid valve coil
Defective oil firing unit
Exchange oil firing unit
6. Flame monitoring (optically)
Fault shutdown without flame formation
Secondary light
Remove secondary light
Defective flame detector
Exchange flame detector
Fault shutdown with flame formation
Dirty glass insert of flame detector /
Clean carefully glass insert of flame detector /
light tube
light tube
Sensitivity setting of the flame detector
Adjust sensitivity of flame detector according
is not correct (only for Honeywell IRD)
to specifications (see Chapter 2.4)
7. Flame monitoring (Ionisation)
Fault shutdown with/without
Earth contact on the combination electrode
Remove moisture in the vicinity of the com-
formation of flame
for ignition and ionisation
bination electrode for ignition and ionisation
Exchange combination electrode for ignition
and ionisation, remove deposits as well as
coating from the electrodes
8. Nozzle
Irregular spraying, high emissions
Defective nozzle
Exchange nozzle
of CO
²
and soot
Oil pressure not in accordance with requirements
Adjust oil pressure
Defective diaphragm valve
Exchange diaphragm valve
9. Mixing device
Air nozzle / re-circulation tube
Setting of burner is not correct
Adjust burner in accordance with
has heavy contamination
basic setting table (see Chapter 5)
Nozzle sprays irregular
Exchange nozzle, or replace diaphragm valve
Nozzle is after-dripping
Exchange diaphragm valve
Improper type of nozzle
Use nozzle in accordance with the
(spray angle, spraying characteristic curve, size)
requirements (see Chapter 4)
10. Gebläse
Blower provides too little air
Contaminated blower wheel
Clean blower wheel carefully
Damaged blower wheel
Exchange blower wheel
Blower runs with heavy noise
Blower wheel not properly positioned
Position blower wheel properly