background image

Pag.10 

 

 

 

Ensure that the fuel supplied to the unit is clean and free from particles and moisture. 

Before a gas supply pipe (new or existing) is connected to the main gas pipe at the gas meter and to  
the gas control block of the unit, clean and dry compressed air should been blown through it. 
Cut copper pipes as well as aluminium pilot pipes must be deburred and blown clean before they  

are connected. The dust filter at the connection to the gas control block will only filter out the  
coarsest dirt from the system. Fine particles are still able to reach the inside and may damage and/or  
adversely affect regulation in the gas control block . 

 

Heat, moisture and dust are a threat to all electronic components 

Protect the electronic gas control 

until all construction, plastering and paintwork has been completed.  

If such work cannot be avoided, then protect the control against dirt and moisture penetration by using,  
for example, plastic film . 

 

 
 

Only place the batteries 

after wiring to the receiver, gas control block and pilot set is connected. 

Premature connection to the energy source may damage the control’s CPU (central processor). 

 

Ensure that the ignition cable is not near the antenna wire and that they do not cross each other. 

The high voltage released at ignition may damage the sensitive receiver circuit. 

This may mean that the unit becomes less responsive or not responsive at all to handset commands. 

 

 

Extend the supplied thermocouple with just the original extension. (available from your supplier) 

Unauthorized extension of the thermocouple has the effect of stress reduction, thereby 
the magnetic coil can not be activated. 

 

Prevent leakage of the ignition spark to other parts of the installation than the Ignition by the pilot 

Keep the ignition free of hull or other metal parts. If cable extension is used, see to it that connections are  
additionally insulated with silicone grommet. 

 

For automatic start via the transmitter, the receiver and the control the gas control valve to  
be switched 

The oval disk on the gas control block should be turned to the ON position. The 

I/0 

switch should 

to be set to "

I

". The ignition must be connected to the receiver box at the terminal 

SPARK

 

The transmitter's contains the thermostat sensor system 

The transmitter operates best at 2 to 3 m from the unit. Although the communication via short wave radio  

signals takes place, it is recommended that the transmitter in the 'visibility' of to lay the gas apparatus in  
a place where the user wants to experience a pleasant temperature. Place the hand transmitter in direct  

sunlight or other hot places. The thermostat measures the temperature and regulates the flame size of the  
gas in accordance. 

 

Remove batteries only with the red ribbon which is under the battery, not with metal tool 

Removing batteries with a metal object, the electronic control can permanently damage.

 

 

 

5. INSTRUCTIONS FOR MERTIK MAXITROL GV60 GASCONTROL 

Electronic components will become permanently faulty when exposed to temperatures higher than 60°C. 
Standard AA batteries will crack open at temperatures >54°C and the battery contents will damage the  

electronic switches located underneath. Batteries last longest at <25°C. At >50°C the life span is around  
23 weeks, this makes the use of the gas fire unnecessarily expensive. 

Only install the gas control block and receiver as pre-installed at the factory

 

 

Remember that components may have to be replaced or that repairs may have to be performed at a later date. 
This may be more difficult if the control is installed using a method that is different from the instructions  

provided here. 

 

WARNING

 

 

IN THE EVENT OF REPLACEMENT

 

Do not tighten the contact breaker and the thermocouple connection too tightly on the gas control  

block or to each other. 

It is sufficient to tighten by hand and add a half a turn with an open-end spanner.  

Tightening too much will break the connection to the magnetic coil below and/or the insulation around  

the aluminium contact pin in the contact breaker. This may lead to the magnetic coil not opening the gas  
supply to the pilot and the unit not working. 

NOTICE 

 WARNING

 

It is forbidden to start up the unit if window (s) are not present or broken! 

 

NOTICE 

Waiting time of 5 minutes between each starting attempt 

Содержание Harmony 25

Страница 1: ...Pag 1 OPERATING AND INSTALLATION INSTRUCTION STANFORD HARMONY 25 STANFORD HARMONY 35 UNITED KINGDOM UK IRELAND IE...

Страница 2: ...as lines 3 2 Preparation and installation 3 3 Fitting the ceramic logs 4 TECHNICAL DETAILS GV60 Page 9 5 INSTRUCTIONS FOR MERTIK MAXITROL GV60 GASCONTROL Page 10 6 GAS TECHNICAL DATA Page 11 7 CONCENT...

Страница 3: ...fter the batteries have been inserted press the OFF button and small at the same time to toggle between F and 12 hour clock and C and 24 hour clock Wait a moment or press OFF to return to MAN mode 1 4...

Страница 4: ...ited the flame will adjust to its maximum height automatically 1 7 Possible error messages Long sound signals during ignition Receiver batteries are almost empty After this signal is heard the unit ma...

Страница 5: ...ly 1 10 Inserting and replacing the batteries The manual transmitter and receiver batteries have a life span of approximately one year The use of alkaline batteries is recommended The batteries need t...

Страница 6: ...able to see whether the pilot flame is burning through the glass window If the pilot flame is alight keep the metal circle pressed down for another 10 seconds and then let go Turn the operating butto...

Страница 7: ...d check whether the burner flame is uniform After the unit has been used for the first time you should remove any deposits resulting from Running burning in the paint using a glass cleaner for heaters...

Страница 8: ...over the burner and the burner decoration plate so that they are just covered Glowing embers can be placed here and there as decoration Place the ceramic wood blocks in the correct order as shown on A...

Страница 9: ...gory C11 C31 C91 Combustion gas discharge and Combustion air supply Concentric 100 150 mm 4 TECHNICAL DETAILS GV60 Main valve knob Thermocouple connection Pressure regulator Ignition connection Pilot...

Страница 10: ...control block should be turned to the ON position The I 0 switch should to be set to I The ignition must be connected to the receiver box at the terminal SPARK The transmitter s contains the thermosta...

Страница 11: ...MBAR 20 Mbar 20 25Mbar 30 30 37 30 Mbar BURNERPRESSURE HIGH MBAR 18 5 18 28 9 BURNERPRESSURE LOW MBAR 3 6 3 11 INJECTOR SIZE MM 1 9 2 1 1 15 INJ PILOTBURNER CODE 51 51 30 LOWSETTING SIZE MM 1 7 1 7 1...

Страница 12: ...striction Baffle plate 0 3 meter no yes 3 7 meter 30 mm yes 7 12 meter 50 mm yes Vertical path with bends 45 X total Y 3 6 meter 30 mm yes 45 X total Y 6 12 meter 50 mm yes 90 X total Y 4 6 meter 30 m...

Страница 13: ...ue should be cased if necessary Sufficient fireproof measures must also be taken when the flue is being mounted along flammable materials Determine the position of the unit and outlet and begin constr...

Страница 14: ...is in place using 2 parkers Level the bottom side of the adjustable pipe 5 with the ceiling of existing chimney Shorten the flexible hose to approximately 100 mm above the existing chimney top Attach...

Страница 15: ...ow Floor ceiling support Fire stop plate flat Concentric element Wall bracket Floor support Fire stop plate flat Locking band 9 Roof terminal 8 Locking band 7 Chimney connection set Renovation kit 6 F...

Страница 16: ...receiver range limited 1 Move antenna cable see instructions 2 Replace receiver Optional wall switch cabling not operating properly Replace wall switch cabling Receiver fuse blown in older versions on...

Страница 17: ...es not react Press RESET button see instructions Add ground wire between pilot burner and gas valve Do not coil the IGN cable Shorten IGN cable if possible NO IGN sequence stops no pilot flame Transmi...

Страница 18: ...ver does not react Press RESET button see instructions Add ground wire between pilot burner and gas valve OK Do not coil the IGN cable Shorten IGN cable if possible 7 Main burner is lit NO Gas valve m...

Страница 19: ...instructions The main burner goes out when the unit is warm 1 This can be a normal effect of the thermostat Check whether the pilot flame is able to heat the thermocouple adequately If the pilot flam...

Страница 20: ...Pag 20 APPENDIX 1 DIMENSIONAL DRAWINGS Stanford Harmony 25 TOP CONNECTION Stanford Harmony 35 TOP CONNECTION...

Страница 21: ...s A combustible shelf may be fitted over the appliance if in the case of a 150mm or less deep shelf there is at least 280mm clearance above the top of the stove The shelf depth may increase at the sam...

Страница 22: ...Pag 22 APPENDIX 3 FITTING LOG SET Stanford Harmony 25 NG LPG...

Страница 23: ...Pag 23 Stanford Harmony 35 NG...

Страница 24: ...24 Industrias Herg m S A Soto de la Marina Cantabria Espa a Stanford Harmony 35 LPG Place behind the horizontal log embers to break the high pointed flame Place embers under the open space Horizontal...

Отзывы: