Room Temperature Calibration (ACA) – Parameter 12 
This parameter defines the offset value for room air temperature. If the internal air temperature sensor  is not 
correctly  calibrated  changes  of  temperature  can  be  made  by  adjusting  the  values  by  up  to  +/-  9.5°C  or  +/- 
19°F.  This value will be added or subtracted from the internal air temperature sensor reading. 
Default value is 0. 
 
HYSTERESIS (HYS) – Parameter 13 
This  parameter  defines  the  hysteresis  value  for  temperature  control.  The  thermostat  will  stabilize  the 
temperature with selected hysteresis. For example, if the SET POINT is set for 25°C and HYSTERESIS is set for 
0.5°C then the thermostat will change the state to HEATING if the temperature will  be lower than 24.5°C and 
it will change the state to idle if temperature reaches 25.5°C. 
You can change the hysteresis from 0.5°C up to a maximum of 9.5°C in Celsius mode and from 1°F to 19°F in 
Fahrenheit mode.  
Default values are 0.5°C or 1°F. 
 
DISPLAY BRIGHTNESS 
The thermostat has two states of  brightness.  
Active state – when you press any key and commence adjustments.  
Inactive state – after five seconds of inactivity it will revert to inactive state.  
The display brightness in either state can be adjusted.  
 
Parameter 14 (brH) – Display brightness high level 
You can select the brightness level in the active state from values 1 to 4. 
Default value is 3. 
 
Parameter 15 (brL) – Display brightness low level 
This parameter defines the brightness level of the display in the inactive state. You can select the level from 
values 1 to 4 but the level cannot be higher than the level of brightness for the active state. 
Default value is 2. 
 
Parameter 16 (nEt) – INCLUSION / EXCLUSION MODE 
If the thermostat is included in the  z-wave network  the antenna will indicated in the main display and Inc will 
be  indicated  in  the  Param  16  value.  If  the  thermostat  is  not  included  in  the  network,  no  antenna  will  be 
indicated in the main display and the Param 16 value will be ECL. 
To  include  or  exclude  the  thermostat  into/from  your  home  automation  gateway,  activate  inclusion  or 
exclusion  mode  on  your  gateway  then  press  “+”  key  on  the  thermostat  for  inclusion  and  the  “-”  key  for 
exclusion. 
For more details go to point “Z-Wave Functions” – “Network “of this manual on page 9. 
 
Parameter 17 (Prr) – Power Meter Reset 
The Heltun thermostat monitors the load and power consumption. The data of total consumption  in kWh is 
indicated in the Param 17 value. If the device is included in the Z-Wave network it will also send the data of 
the current load and total consumption to the main controller. 
The  thermostat,  even when the electricity  is  disconnected,  maintains  the  electric  consumption  record  in  its 
memory. To reset the consumption memory  press and hold “+” key until the parameter value will be changed 
to 0 (about 3 seconds). 
 
CHILD LOCK – LOC 
To activate the child lock mode, press and hold the “HEATING” key for 5 seconds. The LOC text will appear in 
the bottom left hand corner. To deactivate the child lock press the FLOOR key for 5 seconds and the “UnL” will 
appear in the display.  
 
 
 

Содержание HE-ZW-THERM-FL1

Страница 1: ...FLOOR HEATING THERMOSTAT HE ZW THERM FL1 USER MANUAL...

Страница 2: ...in room air temperature sensor The thermostat is also equipped with built in humidity and energy consumption sensors The thermostat has a built in 5th generation Z Wave module which allows to integrat...

Страница 3: ...ork 4 operation modes ECO GEN DRY MANUAL Choosing a temperature sensor for operation Floor temperature only Air temperature only Floor Air temperature Power regulator Automatic ON OFF timer Time cycle...

Страница 4: ...o the wall mounting box using the screws provided Install the thermostat body by carefully aligning the top snap connectors and then pushing on the front cover with gentle pressure ensuring it snaps f...

Страница 5: ...table MODE This mode is recommended for normal comfort Factory default set point is 25 0 C 77 F Minimum set point is 4 0 C 39 F Maximum set point is 37 0 C 99 F ECO energy saving MODE You can use this...

Страница 6: ...02 SEn Source Sensor F F FA A AF P PF PA 03 Pon Power Regulation ON time min 15 10 90 04 PoF Power Regulation OFF time min 15 10 90 05 AIL Air Temperature Minimum C F 21 70 4 36 in Celsius mode 39 99...

Страница 7: ...aram 03 Pon and then OFF during the time in Param 04 Pof 6 PF Power regulator Floor sensor parameters Parameter is heating time set by Params 03 and 04 but also controlled by the floor temperature sen...

Страница 8: ...r 08 FLH Floor Temperature Maximum Floor temperature high limit Reading of the external floor temperature sensor It has effect only if AF or PF are selected as the source sensor Factory default value...

Страница 9: ...ines the brightness level of the display in the inactive state You can select the level from values 1 to 4 but the level cannot be higher than the level of brightness for the active state Default valu...

Страница 10: ...r appear in the value position then the inclusion was not completed Note In case the device has been part of a system before and not excluded since inclusion is not possible In this case exclusion mus...

Страница 11: ...3 Power Regulation ON time Value Description How to Read and Write Dec Hex Available settings 10 90 0x0A 0x5A Minutes Read Command CONFIGURATION_GET Parameter Number 3 0x03 Report is returned Write Co...

Страница 12: ...How to Read and Write Dec Hex Available settings 50 370 0x32 0x0172 Value 10 Temperature in Celsius Read Command CONFIGURATION_GET Parameter Number 8 0x08 Report is returned Write Command CONFIGURATIO...

Страница 13: ...Available settings 5 95 0x5 0x5F Value 10 in Celsius 0 5 C to 9 5 C Read Command CONFIGURATION_GET Parameter Number 13 0x0D Report is returned Write Command CONFIGURATION_SET Parameter Number 13 0x0D...

Страница 14: ...ure setpoint used in DRY mode Value 10 in Celsius 4 0 C to 37 0 C Read Command Class COMMAND_CLASS_THERMOSTAT_SETPOINT Command THERMOSTAT_SETPOINT_GET Type Dry air 0x08 Report is returned Write Comman...

Страница 15: ...0x01 0x08 0x0B OFF GEN DRY ECO Read Command Class COMMAND_CLASS_THERMOSTAT_MODE Command THERMOSTAT_MODE_GET Report is returned Write Command Class COMMAND_CLASS_THERMOSTAT_MODE Command THERMOSTAT_MODE...

Отзывы: