Parameter 03 (Pon) – Power regulator ON time
This parameter defines floor heating time in minutes when Power Regulator (P, PA or PF) is selected as the
source sensor.
Factory default value is 15 minutes.
Parameter 04 (Pof) – Power regulator OFF time
Floor idle time in minutes when Power Regulator (P, PA or PF) is selected as the source sensor.
Factory default value is 15 minutes.
Parameter 05 (AIL) – Air Temperature Minimum
Room temperature low limit. Reading of internal temperature sensor. It has effect only if FA or PA is selected
as the source sensor.
Factory default value is 21°C or 70°F.
*Note: AIL value cannot be higher than AIH value - 1°C
Parameter 06 (AIH) – Air Temperature Maximum
Room temperature high limit. Reading of the internal temperature sensor. It has effect only if FA or PA is
selected as the source sensor.
Factory default value is 27°C or 81°F.
*Note: AIH value cannot be lower than AIL value + 1°C
Parameter 07 (FLL) – Floor Temperature Minimum
Floor temperature low limit. Reading of external floor temperature sensor. It has effect only if AF or PF are
selected as the source sensor.
Factory default value is 18°C or 64°F.
*Note: FLL value cannot be higher than FLH value - 1°C
Parameter 08 (FLH) – Floor Temperature Maximum
Floor temperature high limit. Reading of the external floor temperature sensor. It has effect only if AF or PF
are selected as the source sensor.
Factory default value is 32°C or 90°F.
*Note: FLH value cannot be lower than FLL value + 1°C
Parameter 09 (dry) – Dry Time
This parameter specifies how long in minutes the thermostat will be in heating mode when the DRY mode is
selected. After this time the thermostat will go to the GEN mode. The time range is 5-90 minutes.
Factory default time is 30 minutes.
Parameter 10 (FSr) – Floor sensor resistance
If the external floor NTC temperature sensor is used it is necessary to select the correct ohm value (resistance)
of the sensor. 9 – 100 kΩ is available to select.
In the box is included one floor NTC 10kΩ temperature sensor with three metre connection wire.
The factory default value is 10kΩ.
Note:
If the floor sensor is disconnected or damaged “- -” will indicate on the display FLOOR TEMP field and
regulation modes F, FA, AF, PF will be not able to be selected.
Parameter 11 (FCA) – Floor Temperature Calibration
This parameter defines the offset value for floor temperature. Should the external floor temperature sensor
not be correctly calibrated then temperature changes are able to be adjusted by up to +/- 9.5°C or +/- 19°F.
This value will be added or subtracted from the floor temperature sensor reading.
Default value is 0.