Control panel function: 

 
The steam generator is turned on by pressing the ON-OFF button on the control panel. After this, 
the temperature display will begin to flash. The temperature can be set to the degree (ranging 
between 25 °C – 50 °C) by pressing the + or – buttons. If the temperature value on the display is 
correct, press the OK button and move on to the time display. While the display is flashing, you can 
set the time to the minute (up to 90 minutes) using the + or – buttons, after which the display will 
change to hours (max. 4 hours). 
When the time remaining reaches 90 minutes, the display will change back to minutes. Any time 
beyond 90 minutes is only displayed in full hours. 
 

Light control: 

 
Lights can be controlled by a control panel button, which, when pressed, will activate an LED next 
to the button. 
Connectors LC1 and LC2 on the circuit board are for light control. The circuit board draws external 
voltage (24V DC max. 50mA), which is switched to connector LC1. When the light button is 
pressed, the circuit board transistor will transfer power to connector LC2, which controls the actual 
lighting unit. 
 
 
 

BUTTON HSX M 
 

 

 

Button function: 
 

Turning on the steam generator with the button will take 30 minutes, at which time the LED above 
the button will come on. The steam generator time cannot be set – it will shut itself off. The steam 
generator can also be shut off before time runs out by pressing the button, at which time the LED 
will turn off. If desired, the steam generator can be turned on again. 

When using 

the push button

 it is recommended to install the limiting thermostat to prevent the rise 

of the temperature above +50 °C when the steam room is used for longer than 30 minutes, which is 
the fixed operating time of a steamer equipped with a push button. See the separate installation and 
connection picture. 
The 2-phase control works with the button control version by switching off two thermal resistors 
with a contactor when the thermostat measures a temperature of +50 °C. When the temperature 
drops 1 °C, all three resistors are switched back on. If the temperature rises above +50 °C, all three 
resistors will be switched off. 
 
 

ON - OFF button

Led indicator light

Содержание HSX M 120

Страница 1: ...M New HELO HSX M steam generator for home and professional use Operating instructions Installation instructions Operating and installation instructions for models HELO HSX M 34 47 60 77 95 120 140 701...

Страница 2: ...ill and water level control Floor or wall mounting Digital control panel Temperature control Time setting Light control Control panel can be installed inside the steamroom Magnetic valve equipped with...

Страница 3: ...enerator is 30 cm When placing the steam generator also take into consideration the space required for its maintenance Ensure that there is a drain in close proximity to the steam generator for discha...

Страница 4: ...room NO drainage traps water pockets may be installed on the line any water condensation forming in the steam line must be able to run freely into the steamroom or back into the steam generator If an...

Страница 5: ...ilation must also be given extra power The required power output can be estimated using the fomula below Volume m3 x K1 x K2 Required output kW Ventilation K1 0 75 No ventilation K1 0 52 Acrylic walls...

Страница 6: ...N 3 N N N N N V2 V1 H1 H2 N L PE OLEA 72 S1 S2 Lower limit Upper limit Water valve discharge 230 V AC Water valve fill 230 V AC Resistors Contactor LC1 LC2 B1 B2 T1 T2 A K S1 S2 TX RX 5 0 Serieal traf...

Страница 7: ...0 354 SHS 31 A 1 5 2 6 Levelprobe in Tank Main switch Top cover Lower limit Upper limit Water valve discharge 230 V AC Water valve fill 230 V AC Thermo fuse Resistors Contactor Serieal traffic MIDI co...

Страница 8: ...N 1 2 3 6 4 5 3 4 7 7 kW 230 V 1N 2 L1 N L2 1 2 3 6 4 5 3 4 14 kW 400 V 3N L1 L2 L3 Level probe N N N N V2 V1 H1 H2 N L PE OLEA 72 S1 S2 Low level High level Water valve drain 230 V AC Water valve fil...

Страница 9: ...ng time of a steamer equipped with a push button See the separate installation and connection picture The steam nozzle s are installed approx 20 40 cm above floor level under the bench or seat or on t...

Страница 10: ...selector button time display flashes button increases both time setting and temperature value button decreases both time setting and temperature value Light control button opto switch max 24 V DC 50...

Страница 11: ...n is pressed the circuit board transistor will transfer power to connector LC2 which controls the actual lighting unit BUTTON HSX M Button function Turning on the steam generator with the button will...

Страница 12: ...remove the frame use the included tool The frame has small holes around its edges 4 Using the tool lightly press the locking pin in each hole and then pull the frame out The button is filled with mas...

Страница 13: ...hing on or with the steam generator already running the water faucet is shut or water is for some other reason being prevented from flowing into the steam generator Turn on the water faucet If the fau...

Страница 14: ...hake off the excess water After one minute compare the colour of the strip with the colour code on the package Test result 3 dH Very soft water Lime removal once every 500 operating hours 4 dH Soft wa...

Страница 15: ...turn on again and refill the tank with water The generator shuts down again and discharges and flushes again after 15 minutes This can be repeated about 3 5 times Manual discharge valve After boiling...

Отзывы: