![Helmholz CAN 300 PRO Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/helmholz/can-300-pro/can-300-pro_startup-manual_2122264030.webp)
7.4
Operating conditions for CANopen
®
slave devices
To be able to use a CANopen
®
Slave on the CAN 300 PRO in
CANopen
®
master operation, the slave must meet the following
conditions:
1.
It must be possible to read out the SDO 0x1000.
2.
The slave should perform a restart after the NMT reset
command.
3.
After the slave has been reset, it should transmit a boot-up
message (0x700 + node ID; data: 0x00)
4.
For monitoring by the master, the slave should support either
nodeguarding or producer heartbeat.
Please use the device manual to check whether the conditions
stated above have been met or speak to your device manufacturer.
If a device to be used does not meet these conditions, some
functional restrictions may result, or the device cannot be used
with the CAN 300 PRO via CANopen
®
.
Alternatively, such a device can be used in Layer 2 mode of the
CAN 300 PRO. Please contact us about this …
30
Start-up Guide CAN 300 PRO