1.4
Sequence of Operation
Operational State
User Interface Display
Explanation
Boiler operates in standby mode
until demand for Central Heat (CH)
or Domestic Hot Water (DHW) is
detected.
CH or DHW pump is turned on based
on type of heating demand.
(CH call is illustrated)
General boiler pump is activated for
any heat call.
Control Module compares supply
Temperature to set point. Boiler
proceeds to ignition if supply
temperature is less than set point.
Combustion Air Blower speed
modulates to pre-purge setting for 15
seconds.
Sparking initiated sequence.
Heat
Demand?
DHW CH
Pump on
Supply
Temperature
<Setpoint?
15 Second
Prepurge
Ignition
Sparking
No
Yes
No
Yes
After 2 seconds