
23
P/N 240010943, Rev. C [09/07/2016]
1"(2.54cm)
Maximum
Combustion
Air
Vent
FIGURE 6-4 Side Wall Concentric Terminal
FIGURE 6-5 Side Wall Concentric Terminal Multiple
Appliances
1" (25.4mm)
Max.
Maintain 12"
clearance above
highest anticipated
snow level or grade
* See Note
Below
Vent
Combustion
Air
1" (25mm)
Max.
Roof
Overhang
36" (457mm) Min.
Maintain 12"(30cm) US
(18"(46cm) Canada)
Clearance Above Highest
Anticipated Snow Level
Or Grade
12" (305mm) Min.
FIGURE 6-6 Concentric Terminal Connection
Note: Securing strap must
be field installed to prevent
movement of termination
kit in side wall
Vent
Combustion Air
1"(25.4mm)
Maximum
**See
Note
4" (102mm) Diameter PVC
intake/combustion air
Combustion Air
4" (102mm) Diameter = 36" Length (0.9m)
** Note Overall length may be modified by cutting or extending
both combustion air and vent pipes. 12" (305mm) is minimum
allowable length and 60" (1.2m) is maximum allowable length for
this dimension.
SDR-26 PVC (D2241) only may be used for extending pipes.
Do not use Schedule 40 PVC or use couplings to extend pipes.
Dimension will change if intake/vent pipes are lengthened or
shortened.
4"
(102mm)
Kit
6 - COMBUSTION AIR AND VENT PIPING
24" (610mm) minimum Horizontal distance between
end bells of each concentric terminal to prevent flue gas
recirculation.
Содержание VX-399
Страница 50: ...50 P N 240010943 Rev C 09 07 2016 13 TROUBLE SHOOTING ...
Страница 62: ...62 P N 240010943 Rev C 09 07 2016 14 3 Connection Diagram 399 MBH 14 WIRING DIAGRAM ...
Страница 63: ...63 P N 240010943 Rev C 09 07 2016 14 4 Schematic Diagram of Ladder Form 399 MBH 14 WIRING DIAGRAM ...
Страница 81: ...81 P N 240010943 Rev C 09 07 2016 Company Address Phone Company Name Tech Initials Service Performed Date ...
Страница 82: ...DUNKIRK BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...