31
P/N 240010943, Rev. C [09/07/2016]
8.1
General
Electrically bond boiler to ground in accordance with
requirements of authority having jurisdiction. Refer to:
• USA- National Electrical Code, ANSI/NFPA 70.
• Canada - Canadian Electrical Code, Part I, CSA C22.1:
Safety Standard for Electrical Installations.
8.2
Line Voltage Connections
(figure 8-3)
• Boiler
A. Provide individual 120V, 30 amp circuit
(recommended) with fused disconnect or service
switch as required by authority having jurisdiction.
B. Open High Voltage Junction Box (see Figure 8-1
and 8-3) to access line voltage terminal strip.
C. Connect 120 VAC circuit to line voltage terminal
strip 120 VAC L,N,G.
• Central Heating Pump
A. Isolate pump from control module if pump FLA (Full
Load Amps) exceeds 10 amp maximum allowable
current draw. See Figure 8-3.
B. Connect pump to line voltage terminal strip CH
PUMP L,N,G.
• Domestic Hot Water Pump
A. Isolate pump from control module if pump FLA
exceeds 10 amp maximum allowable current draw.
See Figure 8-3.
B. Connect pump to line voltage terminal strip DHW
PUMP L,N,G.
• General Pump (Boiler Loop)
A. Isolate pump from control module if pump FLA
exceeds 10 amp maximum allowable current draw.
See Figure 8-3.
B. Connect pump to line voltage terminal strip primary
pump, L, N, G.
8.3
External Connections
(figure 8-4)
• User Interface Terminals
A. Factory wired to USER INTERFACE terminals
• Argus Link (Multiple boiler applications only)
• Outdoor Sensor, if used.
A. Provided with boiler.
B. Locate outdoor sensor to protect against wind and
direct sunlight. Mounting instructions provided with
sensor.
C. Maximum wire length is 100 ft (30m) for 22 ga.
wire, or 150 ft (45m) for 18 ga. wire.
D. Connect wires to OUTDOOR SENSOR terminals.
Wires are interchangeable.
• System Sensor (Multiple boiler applications only)
• Domestic Hot Water (DHW) Thermostat, if used.
A. Use temperature control with dry contacts rated
at 0.5 amps @ 120 VAC. Boiler control does not
provide power to DHW temperature control.
WARNING
Electrical shock hazard. Turn OFF electrical power
supply at service panel before making electrical
connections. Failure to do so could result in death
or serious injury.
!
NOTICE
Wiring diagrams can be found in Section 14 of this
Manual.
FIGURE
8-1
Electric Knockouts
8 - ELECTRICAL CONNECTIONS
FIGURE
8-2
Low Voltage Connections
Low Voltage Knockouts
(Use supplied
grommets when using
these knockouts)
position)
High Voltage
Knockouts (5)
High Voltage
Terminal Box
Low Voltage
Terminals
Содержание VX-399
Страница 50: ...50 P N 240010943 Rev C 09 07 2016 13 TROUBLE SHOOTING ...
Страница 62: ...62 P N 240010943 Rev C 09 07 2016 14 3 Connection Diagram 399 MBH 14 WIRING DIAGRAM ...
Страница 63: ...63 P N 240010943 Rev C 09 07 2016 14 4 Schematic Diagram of Ladder Form 399 MBH 14 WIRING DIAGRAM ...
Страница 81: ...81 P N 240010943 Rev C 09 07 2016 Company Address Phone Company Name Tech Initials Service Performed Date ...
Страница 82: ...DUNKIRK BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...