21
Meduim-Pressure Axial Smoke Extraction Fans –
B AMD F300/F400
Installation and Operating Instructions
Interval
Test and maintenance work
Fan
To be carried out by:
Standard
incl . LZD Basic
incl . LZD Comfort
1/2 annual
Test run up to maximum nominal speed
and then deactivate again
x
x
x
Instructed personnel
1/2 annual
Check fan and drive motor for running noises.
x
x
x
Instructed personnel
Annual
Test run for at least 20 minutes and then deactivate
again.
For fans with bearing condition diagnostics, operate fan
until steady-state is reached (around 60-75 minutes) be-
fore reading out values
(see Installation and Operating Instructions for LZD).
x
x
x
Instructed personnel
Annual
General visual inspection and check of fan condition for
external soiling, correct fastening, corrosion and dama-
ge.
Clean components for functional integrity if needed.
x
x
x
Instructed personnel
Annual
Check fan suspension and on-site substructure/foun-
dation for damage and corrosion as well as correct
fastening.
x
x
x
Instructed personnel
Annual
Check flexible connectors and connections for tensi-
on-free installation, tightness, correct fastening, soiling
and damage.
Clean components for functional integrity if needed.
x
x
x
Instructed personnel
Annual
Check vibration dampers for functionality, correct fas-
tening, corrosion and damage.
x
x
x
Instructed personnel
Annual
Check air gap between wingtip and fan casing.
x
x
x
Instructed personnel
Annual
Check drive motor for soiling, corrosion, damage and
correct fastening. Clean components for functional inte-
grity if needed.
x
x
x
Instructed personnel
Annual
Check impeller for soiling, corrosion, damage and cor-
rect fastening.
Clean components for functional integrity if needed.
x
x
x
Instructed personnel
Annual
Check inspection opening for tight fit, corrosion and
damage.
x
x
x
Instructed personnel
Annual
Check protection devices (protection grilles, etc.) for so-
iling, corrosion, damage and correct fastening.
Clean components for functional integrity if needed.
x
x
x
Instructed personnel
Annual
Check accessory components (mounting brackets,
backdraught shutters, extension ducts, etc.) for soiling,
corrosion, damage and correct fastening.
Clean components for functional integrity if needed.
x
x
x
Instructed personnel
Annual
Check terminax box (motor and casing terminal box)
and connection cable for correct fit, damage and cor-
rosion.
x
x
x
Instructed personnel
Annual
Check power consumption of drive motor
x
x
x
Instructed personnel
Annual
Check motor protection device, for ventilation mode
(motor protection device, not in case of fire).
x
x
x
Instructed personnel
Annual
Check on-site bridging of frequency converter and mo-
tor protection devices in case of fire.
x
x
x
Instructed personnel
Annual
Measurement and evaluation of bearing conditions with
bearing condition diagnostics.
x
x
Instructed personnel
Annual
Check fan vibration state
x
x
x
Specialist personnel
Annual
Check impeller for imbalance
x
x
x
Specialist personnel
TEST AND MAINTENANCE PLAN
Folgendes ist zu prüfen:
EN
Содержание B AMD 1000 Series
Страница 25: ...23 Brandgas Axial Mitteldruckventilatoren B AMD F300 F400 Montage und Betriebsvorschrift DE LEISTUNGSERKLÄRUNG ...
Страница 74: ...24 Ventilateurs de désenfumage axiaux moyenne pression B AMD F300 F400 Notice de montage et d utilisation ...
Страница 75: ...25 Ventilateurs de désenfumage axiaux moyenne pression B AMD F300 F400 Notice de montage et d utilisation ...