Input AC / Output AC / Input DC / Signal cables shall be separated
Cable crossings shall be done in 90 deg angles.
It is recommended to install appropriate breaker at AC input and place a warning label near the breaker
stating message as “
ISOLATE UNINTERRUPTIBLE POWER SUPPLY (UPS) BEFORE WORKING ON THIS CIRCUIT
”.
8.3.2 Terminations
Rear Side of Bravo ST 230 VAC terminations are clearly marked in the following figure
8.3.3 Grounding
“PE CHASSIS GROUND”
PE Chassis ground shall be wired to MET or distributed earth bar connected to MET
Main protective conductor(PE) connection is made to the X2(AC IN) terminal block marked with symbol for identification.
PE must be terminated even if commercial Mains is not available and shall be connected to building or main panel ground.
Recommended Cable cross section is the size equal(min) to Neutral cable cross section. Adhere to local regulations.
Ground has to be connected in accordance with local code.
20
– Bravo ST 230 VAC– User manual – v7.3