
38
INITIAL CONTROL SETTINGS
The controls should initially be set as follows :
CONTROL
SETTING
DEHUMIDIFICATION -
L1
65 :
Full Ventilation Rate switch on point.
AIR TEMPERATURE -
L1
30 :
‘In use’ period heating switch off point.
L2
22 :
‘Set back’ period heating switch off point.
POOL TEMPERATURE -
LH
29 :
Heating switch off point. (Super Plus Only).
UPPER LIMIT LH 32 Cooling switch off point
EXHAUST FAN :
Slow :
20%
Fast :
80%
SUPPLY FAN :
Slow :
40%
Fast :
90%
Содержание XF EC
Страница 9: ...8...
Страница 28: ...27 Exhaust Fan Slow Fast Supply Fan Slow Fast Auxiliary Electrical Contacts...
Страница 34: ...33...