PRINCIPLE OF CONTROLS
CONTROL OPERATION :
The controls on the Heatstar are intended to ensure that the pool room environment is constantly maintained at
the correct conditions in terms of temperature and humidity.
The controls monitor the actual conditions within the pool room at all times and automatically switch
‘ON or ‘OFF’
heating or dehumidification accordingly.
All the controls operate on a simple
‘ON’ or ‘OFF’ principle.
Air heating, for example, will either be
‘ON’, if the pool room air temperature is colder than the control setting, or
‘OFF, if the pool room air temperature is warm enough.
The control setting simply tells the Heatstar what temperature you consider to be
‘warm enough’.
The heat output available from the Heatstar is a fixed quantity and increasing the control setting will not serve to
increase the amount of heat coming from the Heatstar at all.
The controls are intended to be completely automatic and, once correctly set up, they should not require any
further adjustment at all.
CONTROL OF CONDITIONS :
All conditions within the pool room are controlled at the same level at all times, for example :
Pool water temperature
-
Always heated up to 28°C
Pool room air temperature
-
Always heated up to 30°C (*)
Upper limit air temperature - Always cooled down to 32°C
Pool room humidity level
-
Always dehumidified down to 65% R.H.
(*)
The pool room air temperature normally requires to be maintained slightly warmer than the pool water
temperature.
If a pool surface cover is used, then the pool room air temperature can be
‘set back’ to the lesser
temperature of 22°C during the periods when the pool cover is in place.