5. Before installation

5.1 Installation regulations

5.2 Installation requirements

Water supply

In  an  unvented  system  the  pressure  and  flowrate  is 

directly related to the incoming water supply. For this 

reason it is recommended that the maximum water 

demand is assessed and the water supply checked to 

ensure this demand can be satisfactorily met.

 

`

We suggest the minimum supply requirements 

should be 0.08MPa (0.8 bar) pressure and  20 litres 

per  minute  flow  rate.  However,  at  these  values 

outlet flow rates may be poor if several outlets are 

used simultaneously.

 

`

A 22mm cold water supply is recommended, 

however, if a 15mm (1/2”) supply exists, which 

provides sufficient flow, this may be used (although 

more flow noise may be experienced). 

 

`

The higher the available pressure and flow rate the 

better the system performance.

 

`

The appliance has a maximum operating pressure 

of 0.35MPa (3.5 bar) which is controlled by the 

Pressure Reducing Valve (PRV). 

 

`

The Pressure Reducing Valve can be connected 

to a maximum mains pressure of 1.6MPa (16 bar).

Outlet/terminal fittings (taps, etc.)

 

`

The water heater can be used with most types of 

terminal fittings. 

 

`

Outlets situated higher than the appliance will give 

outlet pressures lower than that at the heater, a 

10m height difference will result in a 1 bar pressure 

reduction at the outlet. 

 

`

All fittings, pipework and connections must have a 

rated pressure of at least 0.6 Mpa (0.6 Mpa (6 bar)) 

at 80°C.

Limitations

The appliance should not be used in association with 

any of the following:

 

`

Ascending spray type bidets or any other class 1 

back syphonage risk requiring that a type A air gap 

be employed.

 

`

Situations where maintenance is likely to be 

neglected or safety devices tampered with.

 

`

Water supplies that have either inadequate 

pressure or where the supply may be intermittent.

 

`

Situations where it is not possible to safely pipe 

away any discharge from the safety valves.

 

`

In areas where the water consistently contains a 

high proportion of solids, e.g. suspended matter 

that could block the strainer,  unless adequate 

filtration can be ensured.

 

`

In areas where the water supply contains chloride 
levels that exceed 250mg/l.

5.3 Choice of location

The appliance must be vertically wall mounted. 

Although location is not critical, the following points 

should be considered:

 

`

The appliance should be sited to ensure minimum 

dead leg distances, particularly to the point of most 

frequent use.

 

`

Avoid siting where extreme cold temperatures will 

be experienced. All exposed pipe work should be 

insulated.

 

`

The discharge pipework from the safety valves 

must have minimum fall of 1:200 from the appliance 

and terminate in a safe and visible position as per 

G3 requirements.

 

`

Access to associated controls and immersion 

heaters must be available for the servicing and 

maintenance of the system. 

 

`

Clearance under the water heater should be at 

least 300 mm to allow removal of the cover and 

immersion heater.

 

`

Ensure that the wall the appliance is to be mounted 

on is capable of permanently supporting the weight 

when full of water (see table 1, page 5 for weights).

 

`

The tundish should be installed away from any 
electrical components.

5.4 Transport

Prior to installation the appliance should be transported 

and stored in an upright position in its orignal packaging 

in a dry area free from excessive damp, humidity or 

frost.

Please take care when handling a packaged appliance. 

The units are heavy and must only be moved manually 

using safe working practices. The package weights 

are displayed on the carton label. Once the packaging 

has been removed decide on a safe lifting method for 

the appliance again taking note of the weights noted in 

table 1, page 5. DO NOT use the Temperature/Pressure 

Relief Valve to lift or manoeuvre the appliance.

WARNING

Installation of the appliance must be done 

by a qualified engineer in accordance with 

prevailing and national regulations as listed 

below.

 

`

Building Regulations G3

 

`

The Building Standards (Scotland)

 

`

The Building Regulations (Northern 

Ireland)

 

`

I.E.E Electrical Regulations

 

`

UK Water Regulations

Содержание 7037042

Страница 1: ...Multipoint Vertical 30 100 Litres Installation operation and maintenance manual...

Страница 2: ...manufacturers and installers The purpose is to ensure that customers are provided with the correct equipment for their needs that it is installed commissioned and serviced in accordance with the manuf...

Страница 3: ...ficient maintenance of the appliance Failure to abide by the instructions for installing the product Installer s liability The installer is responsible for the installation and the commissioning of th...

Страница 4: ...ended minimum water pressure 0 08 MPa 0 8 bar Max water pressure1 6 MPa 16 bar see table 1 page 5 If the supply cord is damaged it must be replaced by the manufacturer its service agent or simularly q...

Страница 5: ...duct Name Multipoint 30L V 3kW Multipoint 50L V 3kW Multipoint 80L V 3kW Multipoint 100L V 3kW Suppliers name or trade mark Multipoint Supplier s model identifier 30L V 3kW 50L V 3kW 80L V 3kW 100L V...

Страница 6: ...43 1028 1084 1253 D 626 903 956 1134 E 100 100 100 100 F 371 371 451 451 G 95 95 105 105 H OUTLET 22mm 3 4 BSP M I INLET 22mm 3 4 BSP M J TEMPERATURE PRESSURE RELIEF VALVE DISCHARGE PIPE CONNECTION 15...

Страница 7: ...TY BLACK WIRE A TERMINAL BLOCK ELEMENT EARTH IMMERSION STUD L N E OUTER CLADDING L N THERMOSTAT ADJUSTMENT SPINDLE FACTORY SET AT 54 C 2 1 B A RESET CUT OUT TO ELEMENT CUT OUT SENSOR THERMOSTAT SENSOR...

Страница 8: ...pressure to the tap or shower an unvented water heater uses the incoming mains water pressure To do this the water heater is sealed and not vented However when the volume of water is heated it expands...

Страница 9: ...r consistently contains a high proportion of solids e g suspended matter that could block the strainer unless adequate filtration can be ensured In areas where the water supply contains chloride level...

Страница 10: ...fitted Temperature Pressure Relief valve be removed other than by a competent person To do so would invalidate any warranty claim The cold water controls supplied MUST be fitted on the mains water sup...

Страница 11: ...ical installation table supplied and should be fitted A suitable draining tap should be installed in the cold water supply to the appliance between the Expansion Valve and the appliance at as low a le...

Страница 12: ...ve with no more than 600mm of pipe between the valve outlet and the tundish see Fig 7 Note To comply with the Water Supply Water Fittings Regulations the tundish should incorporate a suitable air gap...

Страница 13: ...able providing that a wire cage or similar guard is positioned to prevent contact whilst maintaining visibility and c discharges at high level e g into a metal hopper and metal downpipe with the end o...

Страница 14: ...p to 27m 1 4m 1 7m 2 3m Table 6 Sizing of copper discharge pipe D2 for common temperature relief valve outlet sizes Safety device e g Temperature relief valve Metal discharge pipe D1 from Temperature...

Страница 15: ...g heating When the set temperature is reached the indicator light will go out The set temperature can be adjusted by rotating the control knob This can be set to give temperatures in the range 10 C to...

Страница 16: ...given under the section headed MAINTENANCE COLD HOT WARNING If the appliance is to be left unused followinginstallationandcommissioning e g unocupied properties the appliance should be drained or regu...

Страница 17: ...pecting the water heater internally Safety valve operation CAUTION Water discharged may be very hot Manually operate the Temperature Pressure Relief Valve for a few seconds Check water is discharged a...

Страница 18: ...ance interior Ensure sealing surfaces are clean and seals are undamaged if in doubt fit a new gasket Replace immersion heater ensuring correct orientation One of the bolt holes uses a larger bolt to e...

Страница 19: ...Check and adjust setting if required Replace if necessary Element Failure Replace EPA Discharge of water from Expansion pressure relief valve continuously Excessive mains water pressure Check pressure...

Страница 20: ...lect The appliance has not been subject to wilful or accidental damage caused by your negligence Regular maintenance has been carried out by a competent person or a Heatrae Sadia authorised engineer i...

Страница 21: ...y Users in Private Households in the European Union This symbol on the product indicates that this product must not be disposed of with your other household waste Instead it is your responsibility to...

Страница 22: ...22 13 Spare parts 18 9 4 15 16 5 17 3 20 21 22 1 2 19 Figure 11 Spare parts...

Страница 23: ...ion relief valve 0 6 Mpa 6 bar not shown 95607986 11 Pressure reducing valve not shown 95605082 12 Tundish not shown 95605838 13 Non return valve 22mm not shown 7037720 14 Indicator light BBSC not sho...

Страница 24: ...24...

Страница 25: ...25...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...rporate responsibility and sustainability charters and reduce our printed material we encourage you to download product brochures from our website In designing these files we have taken into account t...

Отзывы: