10. Troubleshooting

10.1 Fault finding

Important

 

`

Servicing should only be carried out by competent 

persons in the installation and maintenance of 

unvented water heating systems.

 

`

Any spare parts used MUST be authorised parts.

 

`

Disconnect the electrical supply before removing 

any electrical equipment covers.

 

`

NEVER bypass any thermal controls or operate 

system without the necessary safety valves.The 

Fault Finding Chart (table 8, below) will enable 

operational faults to be identified and their possible 

causes  rectified.  Any  work  carried  out  on  the 

unvented appliance and its associated controls 

MUST be carried out by a competent installer for 

unvented water heating systems. In case of doubt 

contact

 

service support (see contact details on 

page 28).

WARNING

DO NOT tamper with any of the safety 

valves or controls supplied with the water 

heater as this will invalidate any warranty. 

Water contained in the water heater may 

be very hot, especially following a thermal 

control failure. Caution must be taken when 

drawing water from the water heater.

Table 8: Fault finding chart

Fault

Possible cause

Remedy

Water not heating

Electrical supply fault.

Check electrical supply. 

Thermal cut out tripped.

Check cut out. If operated then reset. Check 

thermostat & replace if necessary.

Thermostat setting too low or 

faulty.

Check and adjust setting if required. Replace if 

necessary.

Element Failure.

Replace EPA.

Discharge of water from 

Expansion (pressure) relief 

valve

(continuously).

Excessive  mains water 

pressure.

Check pressure from Pressure reducing valve. 

Replace if greater than 0.35MPa (3.5bar / 51psi)

Expansion (pressure) relief 

valve fault.

Replace Expansion (pressure) relief valve.

Discharge of water from 

Expansion (pressure) relief 

valve

(intermittently).

Loss of pressure from expansion 

vessel.

Check and if necessary recharge expansion 

vessel precharge pressure.

Discharge of water from 

temperature/pressure relief 

valve and/or water/steam from 

pressure relief valve

Thermostat and thermal cut out 

fault.

Replace combined thermostat & thermal cut out.

No water flow

Product incorrectly installed.

Check inlet & outlet connections are correct. 

Check valves are installed in accordance with 

flow direction marks.

Mains water supply not turned 

on.

Check mains water supply is turned on.

Blockage in mains water supply.

Check mains water supply for obstructions. 

Check strainer in pressure reducing valve.

“Milky water”

Oxygenated water

Water from a pressurised system releases 

oxygen bubbles when flowing. The milkiness will 

disappear after a short while.

Spare Parts

A full range of spare parts are available for the

appliance range (table 9, page 23). Refer to the 

technical data label on the appliance to identify the 

model installed and ensure the correct part is ordered. 

You will need to quote the serial number, which is 

printed on the data label. 

Содержание 7037042

Страница 1: ...Multipoint Vertical 30 100 Litres Installation operation and maintenance manual...

Страница 2: ...manufacturers and installers The purpose is to ensure that customers are provided with the correct equipment for their needs that it is installed commissioned and serviced in accordance with the manuf...

Страница 3: ...ficient maintenance of the appliance Failure to abide by the instructions for installing the product Installer s liability The installer is responsible for the installation and the commissioning of th...

Страница 4: ...ended minimum water pressure 0 08 MPa 0 8 bar Max water pressure1 6 MPa 16 bar see table 1 page 5 If the supply cord is damaged it must be replaced by the manufacturer its service agent or simularly q...

Страница 5: ...duct Name Multipoint 30L V 3kW Multipoint 50L V 3kW Multipoint 80L V 3kW Multipoint 100L V 3kW Suppliers name or trade mark Multipoint Supplier s model identifier 30L V 3kW 50L V 3kW 80L V 3kW 100L V...

Страница 6: ...43 1028 1084 1253 D 626 903 956 1134 E 100 100 100 100 F 371 371 451 451 G 95 95 105 105 H OUTLET 22mm 3 4 BSP M I INLET 22mm 3 4 BSP M J TEMPERATURE PRESSURE RELIEF VALVE DISCHARGE PIPE CONNECTION 15...

Страница 7: ...TY BLACK WIRE A TERMINAL BLOCK ELEMENT EARTH IMMERSION STUD L N E OUTER CLADDING L N THERMOSTAT ADJUSTMENT SPINDLE FACTORY SET AT 54 C 2 1 B A RESET CUT OUT TO ELEMENT CUT OUT SENSOR THERMOSTAT SENSOR...

Страница 8: ...pressure to the tap or shower an unvented water heater uses the incoming mains water pressure To do this the water heater is sealed and not vented However when the volume of water is heated it expands...

Страница 9: ...r consistently contains a high proportion of solids e g suspended matter that could block the strainer unless adequate filtration can be ensured In areas where the water supply contains chloride level...

Страница 10: ...fitted Temperature Pressure Relief valve be removed other than by a competent person To do so would invalidate any warranty claim The cold water controls supplied MUST be fitted on the mains water sup...

Страница 11: ...ical installation table supplied and should be fitted A suitable draining tap should be installed in the cold water supply to the appliance between the Expansion Valve and the appliance at as low a le...

Страница 12: ...ve with no more than 600mm of pipe between the valve outlet and the tundish see Fig 7 Note To comply with the Water Supply Water Fittings Regulations the tundish should incorporate a suitable air gap...

Страница 13: ...able providing that a wire cage or similar guard is positioned to prevent contact whilst maintaining visibility and c discharges at high level e g into a metal hopper and metal downpipe with the end o...

Страница 14: ...p to 27m 1 4m 1 7m 2 3m Table 6 Sizing of copper discharge pipe D2 for common temperature relief valve outlet sizes Safety device e g Temperature relief valve Metal discharge pipe D1 from Temperature...

Страница 15: ...g heating When the set temperature is reached the indicator light will go out The set temperature can be adjusted by rotating the control knob This can be set to give temperatures in the range 10 C to...

Страница 16: ...given under the section headed MAINTENANCE COLD HOT WARNING If the appliance is to be left unused followinginstallationandcommissioning e g unocupied properties the appliance should be drained or regu...

Страница 17: ...pecting the water heater internally Safety valve operation CAUTION Water discharged may be very hot Manually operate the Temperature Pressure Relief Valve for a few seconds Check water is discharged a...

Страница 18: ...ance interior Ensure sealing surfaces are clean and seals are undamaged if in doubt fit a new gasket Replace immersion heater ensuring correct orientation One of the bolt holes uses a larger bolt to e...

Страница 19: ...Check and adjust setting if required Replace if necessary Element Failure Replace EPA Discharge of water from Expansion pressure relief valve continuously Excessive mains water pressure Check pressure...

Страница 20: ...lect The appliance has not been subject to wilful or accidental damage caused by your negligence Regular maintenance has been carried out by a competent person or a Heatrae Sadia authorised engineer i...

Страница 21: ...y Users in Private Households in the European Union This symbol on the product indicates that this product must not be disposed of with your other household waste Instead it is your responsibility to...

Страница 22: ...22 13 Spare parts 18 9 4 15 16 5 17 3 20 21 22 1 2 19 Figure 11 Spare parts...

Страница 23: ...ion relief valve 0 6 Mpa 6 bar not shown 95607986 11 Pressure reducing valve not shown 95605082 12 Tundish not shown 95605838 13 Non return valve 22mm not shown 7037720 14 Indicator light BBSC not sho...

Страница 24: ...24...

Страница 25: ...25...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...rporate responsibility and sustainability charters and reduce our printed material we encourage you to download product brochures from our website In designing these files we have taken into account t...

Отзывы: