Optional Features - Table
Thermostat
DESCRIPTION
SETTING
FEATURE
01
02
03
04
05
06
07
08
09
10
11
Temperature Format
Switching Differential
Frost Mode
Output Delay
Up/Down Temperature Limit
Sensor Selection
Floor Temperature Limit
Optimum Start
Rate of Change
Program Mode
Thermostat Mode
00 = °C, 01 = oF (°C = Default)
01° - 03°C (01°C = Default)
00 = Enabled, 01 = Disabled (00 = Default)
00 - 15 Minutes (00 = Default)
00° 10°C (00 = Default)
00 = Built in Air Sensor
01 = Remote Air Sensor
02 = Floor Sensor Only
03 = Built In & Floor Sensor
04 = Remote Air & Floor Sensor
20° - 45°C (27°C = Default)
00 - 03 Hours (00 = Default)
Minutes to raise by 1°C
00 = 5/2 Day Programming (Default)
01 = 7 Day Programming
02 = 24h Programming
00 = Manual, 01 = Programmable (01 = Default)
Model: Slimline-E V3