FEATURE
Temperature Format
Switching Differential
Frost Protect
Frost Protection Temperature
Output Delay
Communications ID No.
Up/Down Temperature Limit
Sensor Selection
Floor Temperature Limit
Optimum Start
Rate of Change
Program Mode
DESCRIPTION
00 =
o
C, 01 =
o
F (°C = Default)
0.5
o
- 3.0
o
C (1
o
C = Default)
00 = Disabled, 01 = Enabled (01 = Default)
07
o
- 17
o
C (12
o
C = Default)
Enter Value: 00 - 15 Minutes (00 = Default)
Enter number 01-32
00
o
- 10
o
C (00 = Default)
00 = Built in Air Sensor
01 = Remote Air Sensor
02 = Floor Sensor
03 = Floor Sensor and Built in Air Sensor
04 = Floor Sensor and Remote Air Sensor
20-45
o
C (28
o
C = Default)
00 = Disabled (Default)
01 = 01hr, 02 = 02hr, 03 = 03hr
For Information Only
00 = Weekday/Weekend (Default)
01 = 7 Day Programming
SETTING
Optional Settings - Feature Table
Error Codes
E0 =
The internal sensor has developed a fault.
You should contact your thermostat retailer for assistance.
E1 =
The remote floor probe has not been connected, has been wired
incorrectly or the probe is faulty.
E2 =
The remote air probe has not been connected, has been wired incorrectly
or the probe is faulty.
Error Icon
Error Number