Minimum Opening (Square Inches)

Minimum Permanent Free Opening, Square Inches

for Masonry Built Fireplaces

Chimney Height (Feet)

6

8

10

15

20

30

18” Log Set

49.2

45.5

41.7

37.7

34.3

31.2

24” Log Set

56.6

52.4

48.2

43.2

39.8

35.9

Table 1

Minimum Opening (Square Inches)

Minimum Permanent Free Opening, Square Inches

for Factory Built Fireplaces

Chimney Height (Feet)

10

15

20

25

30

35

40

18” Log Set

35.3

26.4

22.1

18.1

17.3

15.9

15.2

24” Log Set

44.2

32.2

26.4

22.9

20.4

18.9

18.1

Table 2

3

Содержание Gas Burner

Страница 1: ...dequate do not operate logs until draft is adequate If you smell fumes from the burner in the room when the damper is fully open it indicates that the fireplace draft is insufficient If the draft is i...

Страница 2: ...Fuel Gas Code ANSI Z223 1 The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess o...

Страница 3: ...0 18 Log Set 49 2 45 5 41 7 37 7 34 3 31 2 24 Log Set 56 6 52 4 48 2 43 2 39 8 35 9 Table 1 Minimum Opening Square Inches Minimum Permanent Free Opening Square Inches for Factory Built Fireplaces Chim...

Страница 4: ...k of the fireplace as possible The fireplace will draft better with the burner unit toward the back of the fireplace Never place the burner assembly more toward the front in larger fireplaces 5 Remove...

Страница 5: ...charred face of the log facing the room Line up the two holes in the bottom of this log with the two 3 8 pegs and gently slide the log over the pegs until it rests on the grate Do not force 2 Remove t...

Страница 6: ...low Middle Log CHML 18 Glow Middle Log CHML 24 Back Log RAD 18 Back Log RAD 24 Back Log CHML 18 Back Log CHML 24 Left Middle Log RAD 18 Left Middle Log RAD 24 Left Middle Log CHML 18 Left Middle Log C...

Страница 7: ...ty information previously listed above 2 Turn gas control handle clockwise to the OFF position 3 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas S...

Страница 8: ...any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIG...

Страница 9: ...position 3 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above on this label If you don t smell gas go...

Страница 10: ...and logs 2 It is recommended that a qualified electrician do the installation 3 The wall switch kit has a wall switch and cover and is designed to be installed in a standard wall switch box NOTE The w...

Страница 11: ...rol Valve Rotary 3 8 Black Street Elbow Screw 10 32 X 2 1 2 Square Nut 1 4 X 20 Valve Mounting Bracket Insulating Washer Burner Stainless Glow Burner Stainless Glow Valve Handle Bracket Insulating Mou...

Отзывы: