background image

 

Heatilator • Novus NBV • 4055-188 Rev C • 04/08 

35

With proper installation, operation and maintenance your gas appliance will provide years of trouble-free service. If you do 
experience a problem, this troubleshooting guide will assist a quali

fi

 ed service person in the diagnosis of a problem and the 

corrective action to be taken. This troubleshooting guide can only be used by a quali

fi

 ed service technician.

A. Standing Pilot Ignition System

Symptom

Possible Causes

Corrective Actions

1.

After repeated triggering 
of the red or black piezo 
ignitor button, the spark 
ignitor will not light the 
pilot.

A.

Defective ignitor.

Check the spark at the electrode and pilot. If there is no spark and the 
electrode wire is properly connected, replace the ignitor.

B.

Defective pilot or 
misaligned electrode 
(spark at electrode).

Using a match, light the pilot. If the pilot lights, turn off the pilot and trigger 
the red or black piezo ignitor button again. If the pilot lights, an improper 
gas/air mixture caused the bad lighting and a longer purge period is 
recommended. If the pilot will not light, ensure the gap at the electrode and 
pilot is 1/8  in. to have a strong spark. If the gap is OK, replace the pilot.

C.

No gas or low gas 
pressure.

Check the remote shut-off valves from the appliance. There is usually a 
valve near the gas main. There can be more than one valve between the 
appliance and the main.

D.

No LP in tank.

Check the LP (propane) tank. You may be out of fuel.

2.

The pilot will not stay lit 
after carefully following 
the lighting instructions

A.

Defective thermocouple.

Check that the pilot 

fl

 ame impinges on the thermocouple. Clean and/or 

adjust the pilot for maximum 

fl

 ame impingement.

Ensure that the thermocouple connection at the gas valve is fully inserted 
and tight (hand tighten plus 1/4  turn).
Disconnect the thermocouple from the valve, place one millivolt meter lead 
wire on the tip of the thermocouple and the other meter lead wire on the 
thermocouple copper lead. Start the pilot and hold the valve knob in. If the 
millivolt reading is less than 15mV, replace the thermocouple.

B.

Defective valve.

If the thermocouple is producing more than 15 millivolts, replace faulty valve.

3.

The pilot is burning, there 
is no gas burning, the 
valve knob is in the ON 
position, and the ON/
OFF switch is in the ON 
position.

A.

ON/OFF switch or wires 
are defective.

Check the ON/OFF switch and wires for proper connections. Place the 
jumper wires across the terminals at the switch. If the burner comes on, 
replace the defective switch. If the switch is OK, place the jumper wires 
across the switch wires at the gas valve. If the burner comes on, the wires 
are faulty or connections are bad.

B.

Thermopile may not be 
generating suf

fi

 cient 

millivoltage.

If the pilot 

fl

 ame is not close enough physically to the thermopile, adjust the 

pilot 

fl

 ame.

Be sure the wire connections from the thermopile at the gas valve terminals 
are tight and that the thermopile is fully inserted into the pilot bracket.
Check the thermopile with a millivolt meter. Take the reading at TH-TP&TP 
terminals of the gas valve. The meter should read 325 millivolts minimum 
while holding the valve knob depressed in the pilot position, with the pilot lit, 
and the ON/OFF switch in the OFF position. Replace the faulty thermopile of 
the reading is below the speci

fi

 ed minimum.

With the pilot in the ON position, disconnect the thermopile leads from 
the valve. Take a reading at the thermopile leads. The reading should be 
325 millivolts minimum. Replace the thermopile if the reading is below the 
minimum.

C.

Defective valve.

Turn the valve knob to the ON position. Place the ON/OFF switch in the ON 
position. Check the millivolt meter at the thermopile terminals. The millivolt 
meter should read greater than 125mV. If the reading is acceptable, and if 
the burner does not come on, replace the gas valve.

D.

Plugged burner ori

fi

 ce.

Check the burner ori

fi

 ce for stoppage. Remove stoppage.

E.

Wall switch or wires are 
defective.

Follow the corrective action in Symptom and Possible Cause 1.A. above. 
Check the switch and wiring. Replace where defective.

14 

14 

Troubleshooting 

Содержание NBV3630

Страница 1: ...eration D O N O T D I S C A R D If the information in these instruc tions is not followed exactly a fire may result causing property damage personal injury or death Do not store or use gasoline or oth...

Страница 2: ...tion on appliance Dealership purchased from Dealer phone Notes We recommend that you record the following pertinent information about your appliance Listing Label Information Location The model inform...

Страница 3: ...C Securing and Leveling Appliance 17 8 Installing Vent Pipe 18 A Assemble Vent Sections 18 B Attach Vent to Firebox Assembly 18 C Securing Vent Sections 18 9 Gas Information 19 A Fuel Conversion 19 B...

Страница 4: ...tement is in compliance with CPSC 16 CFR Section 1201 5 Certification and labeling requirements which refers to 15 U S Code USC 2063 stating Such certificate shall accompany the product or shall other...

Страница 5: ...jurisdiction about restrictions installation inspection and permits CAUTION When planning an appliance installation it s necessary to determine the following information before installing Where the ap...

Страница 6: ...ney should Be installed through the warm airspace enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Penetrate the highest part of t...

Страница 7: ...king material Hammer Gloves Phillips screwdriver Framing square Flat blade screwdriver Electric drill and bits 1 4 in Plumb line Safety glasses Level Manometer Voltmeter Tape measure Non corrosive lea...

Страница 8: ...to walls See Figure 3 1 Note For actual appliance dimensions refer to Section 16 In addition to these framing dimensions also reference the following sections Clearances and Mantel Projections Section...

Страница 9: ...ilding envelope in any manner Walls ceiling base plate and cantilever floor of the chase should be insulated Vapor and air infiltration barriers should be installed in the chase as per regional codes...

Страница 10: ...I in 39 34 7 8 19 5 8 mm 991 886 498 NBV4236 NBV4236I in 42 34 7 8 19 5 8 mm 1067 886 498 NBV4842 NBV4842I in 48 34 7 8 19 5 8 mm 1219 886 498 Fire Risk Odor Risk Install appliance on hard metal or wo...

Страница 11: ...in from fireplace opening to perpendicular wall B Mantel Leg or Perpendicular Wall Top of Appliance Drywall A B Figure 3 4 Clearances to Combustible Mantel Legs or Wall Projec tions acceptable on both...

Страница 12: ...s Staggered Height If using decorative cap cover s this distance may need to be increased Refer to the installation instruc tions supplied with the decorative cap cover Figure 4 2 Multiple Vertical Te...

Страница 13: ...66 m min 60 ft 18 29 m max Figure 5 1 Vertical Termination Clearances Maximum horizontal run is 50 of vertical Horizontal run cannot be more than 30 ft 9 14 m Vent supports are per vent manufacturer s...

Страница 14: ...zontal distance is 50 of vertical vent height Fire Risk Explosion Risk Insulation and other combustibles must not infringe on clearances ALWAYS maintain specified clearances around venting and firesto...

Страница 15: ...g dimensions Figure 6 1 Exterior Wall Hole 6 6 Vent Clearances and Framing B Wall Penetration Framing Follow vent pipe manufacturer s instructions for all clear ances around pipe For a wall penetratio...

Страница 16: ...t blocked by snow leaves etc Clear area outside house or in ventilated crawl space YES NO NO NO NO Use only duct materials specified by manufacturer preferably with short run or mainly straight duct e...

Страница 17: ...ion level and se cure the appliance see Figure 7 3 Nailing tabs are pro vided to secure the appliance to the framing members Place the appliance into position Level the appliance from side to side and...

Страница 18: ...nner lining Pipe may separate if not properly joined WARNING Figure 8 1 Attaching Vent to Firebox B Attach Vent to Firebox Assembly Three tabs extend from appliance collar shield Attach tabs to first...

Страница 19: ...t local codes for compliance Pressure requirements for appliance are shown in table be low Minimum pressures must be met when other household gas appliances are operating Pressure Natural Gas Propane...

Страница 20: ...00 ft it may be necessary to decrease the input rating by chang ing the existing burner orifice to a smaller size Input rate should be reduced by 4 for each 1000 ft above a 2000 ft elevation in the U...

Страница 21: ...ighly recommended that the junction box be installed at this time to avoid reconstruction The battery pack requires two D cell batteries not included Batteries cannot be placed in the battery pack whi...

Страница 22: ...al wall switch WSK MLT HTL Figure 10 1 Intellifire Pilot Ignition IPI Wiring Diagram Pilot Ignitor GAS VALVE To Burner Gas Inlet Inlet Tap ORG SILVER Thermopile WHT RED Flame Sensor Copper Tubing Push...

Страница 23: ...W H T W HT B L K BLK GRN wire inside box Copper ground attached to GRN screw with GRN wire 14 2WG Cover Plate outside firebox Romex Connector Figure 10 3 Junction Box Detail Note Do NOT wire 110 VAC t...

Страница 24: ...o ceiling Figure 11 1 Clearances to Mantels or other Combustibles above Appliance 1 in 25 mm min to perpendicular wall A 3 1 2 in 89 mm min from fireplace opening to perpendicular wall B Mantel Leg or...

Страница 25: ...rom the shoulder screws in the fireplace columns See Figure 12 3 Rotate the screen open as shown in Figure 12 4 C Remove the Shipping Materials Remove the shipping materials from inside or underneath...

Страница 26: ...lava rock J Remove Screen Protector Tear the corrugated as shown in Figure 12 6 The corrugated must be separatewd along the entire top edge of the protector Slide the screen protector off the screen...

Страница 27: ...of the appliance Slide the hood into position uncer the screw heads Tighten the four screws See Figure 12 9 K Unpackage the Hood Floor Cover Remove the hood floor cover and protective cardboard from t...

Страница 28: ...fixed glass assembly as a complete assembly Remove screen Pull the four 30 33 36 in appliances or seven 42 in appliance glass assembly latches out of the groove on the glass frame Refer to Figure 12...

Страница 29: ...should be adjusted by a qualified installer at the time of installation The air shutter is set at the factory for minimum vertical vent run Adjust air shutter for longer vertical runs See Figure 12 1...

Страница 30: ...ice agency or the gas supplier WARNING Do NOT use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of th...

Страница 31: ...rmal operating condition Turn on appliance and allow to operate for at least 10 minutes Check draft as shown in Figure 13 1 This can be done using a smoke or flame producing match Hold lit match at bo...

Страница 32: ...appliance WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life FOR YOUR SAFETY READ BEFORE LIGHTING 33631D C U...

Страница 33: ...xactly a fire or explosion may result causing property damage personal injury or loss of life FOR YOUR SAFETY READ BEFORE LIGHTING 29097D This appliance needs fresh air for safe operation and must be...

Страница 34: ...dor is excessive it may require the initial three to four hour continuous burn on high followed by a second burn up to 12 hours to fully drive off any odor from paint and lubricants used in the manufa...

Страница 35: ...le copper lead Start the pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple B Defective valve If the thermocouple is producing more than 15 millivolts...

Страница 36: ...ly D Bad thermopile or thermocouple Replace if necessary E Improper vent cap installation Check for proper installation and freedom from debris or blockage 6 Glass soots A Flame impingement Adjust the...

Страница 37: ...e If there is no spark at I terminal module must be replaced If there is a spark at I terminal module is fine Inspect pilot assembly for shorted sparker wire or cracked insulator around electrode 3 Pi...

Страница 38: ...es control compartment Burner burner ports Risk of Fire Delayed ignition or explosion Exposure to combustion fumes Odors WARNING Handle glass assembly with care Note Clean glass after initial 3 4 hour...

Страница 39: ...repaint as necessary 2 Replace appliance if firebox has been perforated Burner ignition and operation 1 Verify burner is properly secured and aligned with pilot or ignitor 2 Clean off burner top inspe...

Страница 40: ...Model A B C NBV3630 NBV3630I inches 35 30 8 5 8 mm 889 762 219 NBV3933 NBV3933I inches 38 33 11 5 8 mm 965 838 295 NBV4236 NBV4236I inches 41 36 14 5 8 mm 1041 914 371 NBV4842 NBV4842I inches 47 42 2...

Страница 41: ...9 Dry Wall Lip 4031 205 N 10 Hood 4055 213 N 11 Glass Shield 4031 217 N 12 Glass Latch Assembly Qty 4 33858 Y 13 Hearth Pan 4055 109 N 14 Burner Assembly 4055 046 Y 15 Valve Assembly Standing Pilot 4...

Страница 42: ...Assembly Wall Switch 28602 Y Orifi ce NG 083 4021 435 Y Orifi ce LP 52C 4021 426 Y 1 2 3 4 5 6 7 8 9 10 11 12 IMPORTANT THIS IS DATED INFORMATION When requesting service or replacement parts for your...

Страница 43: ...Shield 4031 218 N 12 Glass Latch Assembly Qty 4 33858 Y 13 Hearth Pan 4055 110 N 14 Burner Assembly 4055 047 Y 15 Valve Assembly Standing Pilot 4055 025 N IPI 4055 027 N 16 Gasket Valve Plate 4055 13...

Страница 44: ...ire Assembly Wall Switch 28602 Y Orifi ce NG 43C 582 843 Y Orifi ce LP 54C 582 854 Y 1 2 3 4 6 7 8 9 10 11 12 IMPORTANT THIS IS DATED INFORMATION When requesting service or replacement parts for your...

Страница 45: ...Shield 4031 219 N 12 Glass Latch Assembly Qty 4 33858 Y 13 Hearth Pan 4055 111 N 14 Burner Assembly 4055 047 Y 15 Valve Assembly Standing Pilot 4055 025 N IPI 4055 027 N 16 Gasket Valve Plate 4055 13...

Страница 46: ...Bulkhead 4021 429 N 10 Bulkhead Flexible 4021 512 N Wire Assembly Wall Switch 28602 y Orifi ce NG 42C 582 842 Y Orifi ce LP 0 058 4021 602 Y IMPORTANT THIS IS DATED INFORMATION When requesting servic...

Страница 47: ...N 9 Glass Shield 4031 220 N 10 Glass Latch Assembly Qty 4 33858 Y 11 Hearth Pan 4055 112 N 12 Burner Assembly 4055 049 Y 13 Valve Assembly Standing Pilot 4055 025 N IPI 4055 027 N 16 Gasket Valve Pla...

Страница 48: ...ket Bulkhead 4021 429 N 10 Bulkhead Flexible 4021 512 N Wire Assembly Wall Switch 28602 y Orifi ce NG 37C 582 837 Y Orifi ce LP 52C 582 852 Y IMPORTANT THIS IS DATED INFORMATION When requesting servic...

Страница 49: ...version Kit DF DEMI30 Operable Square Decorative Front DF TRES30 Operable Arch Decorative Front FFDEMI30 Non operable Decorative Front Model Description NBV3933 B vent standing pilot natural gas 39 fr...

Страница 50: ...DF DEMI36 Operable Square Decorative Front DF TRES36 Operable Arch Decorative Front FFDEMI36 Non operable Decorative Front Model Description NBV4842 B vent standing pilot natural gas 48 framing width...

Страница 51: ...Heatilator Novus NBV 4055 188 Rev C 04 08 51 WTB36 Traditional Brick Refractory WHB36 Herringbone Brick Refractory...

Страница 52: ...52 Heatilator Novus NBV 4055 188 Rev C 04 08 This page intentionally left blank...

Страница 53: ...Heatilator Novus NBV 4055 188 Rev C 04 08 53 This page intentionally left blank...

Страница 54: ...54 Heatilator Novus NBV 4055 188 Rev C 04 08 This page intentionally left blank...

Страница 55: ...nadequate ventilation or drafting caused by tight sealing construction of the structure air handling devices such as exhaust fans or forced air furnaces or other causes 5 use of fuels other than those...

Страница 56: ...4 5000162 5016609 5076254 5113843 5191877 5218953 5263471 5328356 5341794 5347983 5429495 5452708 5542407 5601073 5613487 5647340 5688568 5762062 5775408 5890485 5931661 5941237 5947112 5996575 600674...

Отзывы: