Heatilator • Novus NBV • 4055-188 Rev C • 04/08
19
A. Fuel Conversion
Before making gas connections ensure appliance being in-
stalled is compatible with the available gas type.
Any natural or propane gas conversions necessary to meet
the appliance and locality needs must be made by a quali-
fi
ed technician using Hearth & Home Technologies speci
fi
ed
and approved parts.
B. Gas Pressure
Proper input pressures are required for optimum appliance
performance. Gas line sizing requirements need to be made
following
NFPA51
.
C. Gas Connection
Refer to Reference Section 16 for location of gas line access
in appliance.
Note:
Have the gas supply line installed in accordance
with local building codes, if any. If not, follow
ANSI
223.1
. Installation should be done by a quali
fi
ed installer
approved and/or licensed as required by the locality. (In
the Commonwealth of Massachusetts installation must be
performed by a licensed plumber or gas
fi
tter.)
Note:
A listed (and Commonwealth of Massachusetts
approved) 1/2 in. (13 mm) T-handle manual shut-off valve
and
fl
exible gas connector are connected to the 1/2 in.
(13 mm) control valve inlet.
• If substituting for these components, please consult
local codes for compliance.
Pressure requirements for appliance are shown in table be-
low. Minimum pressures must be met when other household
gas appliances are operating.
Pressure
Natural Gas
Propane
Minimum Inlet Pressure
5.0 in. w.c.
11.0 in. w.c.
Maximum Inlet Pressure
7.0 in. w.c.
14.0 in. w.c.
Manifold Pressure
3.5 in. w.c.
10.0 in. w.c.
WARNING
Gas Leak Risk
• Support control when attaching pipe to
prevent bending gas line.
Fire Risk
Explosion Risk
Verify inlet pressures.
• High pressure may cause overfire
condition.
• Low pressure may cause explosion.
• Verify minimum pressures when other
household gas appliances are operating.
Install regulator upstream of valve if line
pressure is greater than 1/2 psig.
WARNING
9
9
Gas Information
Fire Risk
Explosion Risk
High pressure will damage valve.
• Disconnect gas supply piping BEFORE
pressure testing gas line at test pressures
above 1/2 psig.
• Close the manual shutoff valve BEFORE
pressure testing gas line at test pressures
equal to or less than 1/2 psig.
WARNING
Note:
Gas line may be run from either side of appliance
using one of the knockouts provided. Hole in outer shell
NOT to exceed 2-1/2 in. and should never penetrate the
fi
rebox.
Note:
The gap between supply piping and gas access hole
may be caulked with high temperature caulk or stuffed
with non-combustible, unfaced insulation to prevent cold
air in
fi
ltration.