Heatilator  •  NBV30-IFT, NBV33-IFT, NBV36-IFT, NBV42-IFT Owner’s Manual  •  2624-981 Rev. C 

 

•  8/20      

IntelliFire Touch - (continued)

Symptom

Possible Cause

Corrective Action

Pilot sparks but does not light, 

after 90 sec, 3 Red/1 Green 

Lockout

No gas supply.

Verify incoming gas line ball valve is ‘Open’.  Verify inlet pres-

sure is within requirement for gas type used.  Contact gas sup-

plier.

ECM has poor ground.

Verify wiring, check valve harness black wire is securely 

grounded to metal chassis.

Gas valve defective.

Check pilot valve solenoid kick and hold voltages during igni-

tion cycle.  Kick V should be >1 V, hold V minimum 0.26 V.  If 

voltages are OK, replace gas valve.

Pilot lights but main burner 

does not light.   Pilot continues 

to spark for 90 sec then goes 

into 3 Red/1 Green Lockout.

No flame detected. Flame 

rectification issue.

Check if white sense lead is securely connected to ‘S’ terminal 

of IFT-ECM.  Check resistance of sense lead between sense 

rod tip and connector to IFT-ECM, should be less than 1 ohm 

- if not, replace pilot assembly.  Check system ground, ensure 

black valve harness wire is securely attached to metal chassis.  

Check wiring for damage.  With system OFF, check resistance 

between tip of sense rod and pilot hood, should be resistance 

(>1 M-ohm). 

No flame detected or sense rod 

contamination. 

With  glass  assembly  installed,  verify  pilot  flame  is  engulfing 

flame sense rod on pilot assembly.  Verify inlet gas pressure 

is correct for gas type.  Polish flame sense rod with fine steel 

wool to remove any contaminants that may have accumulated.

Pilot lights and rectifies, but 

main burner does not light.

Main valve solenoid.

Check if green wire in valve harness is connected to green 

main valve solenoid.  Check main valve solenoid resistance, 

nominal is 60 ohms.  If open or shorted, replace valve.  Verify 

valve inlet pressure is correct for gas type.

Pilot and main do not light, 

ECM goes into 5 Red/1 Green 

Lockout.

Power Vent (PV) Failure.

Power Vent blower defective - check wiring to IFT-ACM, check 

if blower is working.  Check if PV pressure switch is connected 

to brown and black wire in 6-pin valve wire harness.  Check if 

pressure switch is closed (shorted) when PV blower is running.  

Refer to PV troubleshooting instructions. 

Appliance lights and runs for a 

few minutes then shuts down 

and/or appliance cycle ON 

and OFF with less than 90 sec 

of ON time. 

Shorted or loose connection in 

flame detection circuit.

Check if white sense lead is securely connected to ‘S’ terminal 

of IFT-ECM.  Check resistance of sense lead between sense 

rod tip and connector to IFT-ECM, should be less than 1 ohm 

- if not, replace pilot assembly.  Check system ground, ensure 

black valve harness wire is securely attached to metal chassis.  

Check wiring for damage.  With system OFF, check resistance 

between tip of sense rod and pilot hood, should be resistance 

(>1 M-ohm). 

Poor flame rectification or 

contaminated sense rod. 

With  glass  assembly  installed,  verify  pilot  flame  is  engulfing 

flame sense rod on pilot assembly.  Verify inlet gas pressure 

is correct for gas type.  Polish flame sense rod with fine steel 

wool to remove any contaminants that may have accumulated.  

Verify no soot deposits are in sense rod to pilot hood gap.

Logs are set up wrong. 

Remove and re-install logs per the log placement instructions.

Damaged pilot assembly.

Verify  the  pilot  assembly  ceramic  insulator  around  the  flame 

sensing rod is not cracked, damaged or loose.  Check resis-

tance between tip of sense rod and IFT-ECM connector, should 

be less than 1 ohm.  Replace pilot assembly if damage is de-

tected.

High temp limit swtich interrupts 

power to appliance.

This appliance is equipped with a temperature limit switch 

which is located above the appliance firebox.  This switch is 

used to protect against reverse draft or flue blockage on b-vent 

appliances.  Verify appliance is drafting properly and termina-

tion cap is clear.  

No power to appliance. 

High temp limit switch not wired 

correctly.  6V transformer not 

plugged into junction box.  6V 

power supply jumper wire is not 

plugged into IFT-ECM.

Verify 6V transformer is plugged into junction box. Verify high 

temp limit switch wires and 6V transformer are connected to 

2179-300 jumper wire.  Verify 2179-300 jumper wire is plugged 

into IFT-ECM.  Reference installation manual for wiring dia-

gram. 

Содержание NBV30-IFT

Страница 1: ...call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a q...

Страница 2: ...Pression xx x in w c Po Col D eau Maximum Manifold Pressure Pression x x in w c Po Col d eau Minimum Manifold Pressure Pression x x in w c Po Col d eau Minimum rate with variable regulator on control...

Страница 3: ...pecific Information A Appliance Certification 6 B Glass Specifications 6 C BTU Specifications 6 3 Important Safety and Operating Information A Appliance Safety 7 B General Operating Parts 8 C Fuel Spe...

Страница 4: ...ler distributor whichever occurs earlier However the warranty shall commence no later than 24 months following the date of product shipment from HHT regardless of the installation or occupancy date Th...

Страница 5: ...or improper handling 4 improper operation abuse misuse continued operation with damaged corroded or failed components accident or improperly incorrectly performed repairs 5 environmental conditions i...

Страница 6: ...eat in residential heating calculations 2 2 Product Specific Information This product is listed to ANSI standards for Vented Gas Fireplaces May be installed in a sleeping room when the provisions for...

Страница 7: ...l gas and the products of combustion of such fuels can expose you to chemicals including benzene which is known to the State of California to cause cancer and reproductive harm For more information go...

Страница 8: ...emperatures above the center of the appliance at various heights above the appliance opening NOTICE Surface temperatures listed above are taken with a temperature measuring probe as prescribed by the...

Страница 9: ...turer and from model to model actual TV temperatures should be validated at the me of each installa on TVs should not be used in situa ons where the actual TV temperature exceeds the manufacturers max...

Страница 10: ...ol handle is HOT when fireplace is in operation Adjust BEFORE lighting fire F Before Lighting Appliance Before operating this fireplace for the first time it is rec ommended that a qualified service t...

Страница 11: ...e gas sup plier s instructions C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand DO NOT D DO NOT use this appliance if any part...

Страница 12: ...t away Optional Heat Out Gas Kit The Heat Out Gas heat management option is available for use with the NBV IFT appliances and must be used in conjunction with the IFT RC400 control The Heat Out Gas ki...

Страница 13: ...N Position The appliance will ignite and run continuously at the HI flame setting No adjustment in flame height is possible Remote Position The remote position allows operation of the appliance from a...

Страница 14: ...ch to start the appliance appliance will ignite normally if the error condition was corrected If the IFT ECM re enters the lock out condition after these steps call your dealer for service Appliance O...

Страница 15: ...l be turned off and cooled before servicing When properly maintained your fireplace will give you many years of trouble free service Contact your dealer to answer questions regarding proper operation...

Страница 16: ...event unin tended operation Remove batteries from remote controls Unplug the 6 volt adapter plug Clean glass with a non abrasive non ammonia based commercially available gas fireplace glass cleaner Li...

Страница 17: ...ve penetrated the sheet metal are sharp and should be avoided Remove all foreign objects Verify unobstructed air circulation Figure 4 2 IPI Pilot Flame Pattern Pilot and Burner Ignition and Operation...

Страница 18: ...g from manufacturing Odor may also be released from finishing materials and adhesives used around the fireplace These circumstances may require additional curing related to the installation environmen...

Страница 19: ...e intensity based on the difference between the desired room temperature and actual temperature In thermostat mode the hearth appliance will start in HI flame but as the actual temperature approaches...

Страница 20: ...OFF position Verify IFT ECM slider switch is in ON or REM position Verify AC power available to junction box Verify AC DC adaptor is plugged into junction box and ECM Verify AC DC adaptor out put volt...

Страница 21: ...s connected to brown and black wire in 6 pin valve wire harness Check if pressure switch is closed shorted when PV blower is running Refer to PV troubleshooting instructions Appliance lights and runs...

Страница 22: ...3 J After a qualified service technician has installed the heat management system follow the instruction supplied with the kit for operation Contact your dealer if you have questions Optional Refracto...

Страница 23: ...8 20 B Service Parts Service Parts Beginning Manufacturing Date Sept 2020 Ending Manufacturing Date Active 1 2 3 4 5 Part number list on following page Log Set Assembly Novus Gas Fireplace BV 08 20 N...

Страница 24: ...4031 217 10 Glass Latch Assembly Qty 4 req 2382 400 Y 11 Hearth Pan 2380 111 12 Burner Assembly 2380 007 Y 13 Valve Assembly Refer to valve page 14 Gasket Valve Plate Qty 2 req 4055 135 15 Glass Frame...

Страница 25: ...4031 218 10 Glass Latch Assembly Qty 4 req 2382 400 Y 11 Hearth Pan 2381 111 12 Burner Assembly 2381 007 Y 13 Valve Assembly Refer to valve page 14 Gasket Valve Plate Qty 2 req 4055 135 15 Glass Frame...

Страница 26: ...4031 219 10 Glass Latch Assembly Qty 4 req 2382 400 Y 11 Hearth Pan 2382 111 12 Burner Assembly 2382 007 Y 13 Valve Assembly Refer to valve page 14 Gasket Valve Plate Qty 2 req 4055 135 15 Glass Frame...

Страница 27: ...4031 220 10 Glass Latch Assembly Qty 4 req 2382 400 Y 11 Hearth Pan 2383 111 12 Burner Assembly 2383 007 Y 13 Valve Assembly Refer to valve page 14 Gasket Valve Plate Qty 2 req 4055 135 15 Glass Fram...

Страница 28: ...Y 13 7 Valve NG SRV2166 302 Y Valve Propane 2166 303 Y 13 8 Brass Fitting Pkg of 5 303 315 5 Y 13 9 Wire Harness IFT 6 Pin SRV2326 132 Y 13 10 Jumper Wire 2155 003 Y 13 11 Module IFT Control SRV2326 1...

Страница 29: ...___________________________________________________ ________________________________________________________________________________ ___________________________________________________________________...

Отзывы: