background image

17

Heatilator • MEL36, MEL42  Installation Manual • 4044-212 • Rev D • 01/06/15

ROOM ABOVE (non-insulated ceiling) 

ATTIC ABOVE (insulated ceiling)

Ceilng firestop 

attached to bottom 

of framing

Ceiling firestop 

attached to top of 

framing

Note: 

Use same dimensional lumber for framing 

ceiling firestop and joists. 

2 in. (51mm) 

clearance

2 in. (51mm) 

clearance

WARNING!  Risk of Fire! DO NOT 

seal area between 

firestop opening and chimney pipe except where they en

-

ter the attic or leave the warm air envelope of the home 

(use 600° F sealant).

Figure 5.7  Installing the Ceiling Firestop

E. Install Ceiling Firestops

 CAUTION! 

Risk of Fire! Ceiling firestops must be used 

whenever the chimney penetrates a ceiling/floor.

•  The ceiling firestop slows spread of fire and reduces 

cold air infiltration.

•  Install a ceiling firestop whenever chimney penetrates 

ceiling/floor.

•  Mark and cut an opening in ceiling as shown in Figure 5.7.

•  Frame the opening with the same size lumber used in 

the ceiling joists.

•  Nail the ceiling firestop to the bottom of the ceiling joists 

when there is a room above.

•  Use an attic insulation shield if the ceiling is insulated. 

The ceiling firestop may then be attached above or below 

the joists.

If  the  attic  space  is  ventilated  and  the  fireplace  system 

height from floor to the flue outlet of the termination is 13’6’’ 

or more, it is not necessary to use the Thimble and extend 

the radiation shield into the roof flashing.  The installation 

can be done as a normal residential installation using the 

standard firestop attic shield.

Installation of a ceiling firestop is required:
•  Refer to Figures 5.7, 5.9, 5.10.

•  Roll the shield (around the chimney if already installed). 

The three holes on each side will match up (large holes 

on top). 

•  Insert three screws into the matching holes to form a 

tube.

•  Bend the tabs on the bottom of the tube inward to 90° to 

maintain chimney air space.

•  Rest the insulation shield on the ceiling firestop below.

•  Bend the tabs at the top of the shield inward to 90° to 

maintain the 2 in. (51 mm) air space from the chimney.

F.  Attic Insulation Shield Installation

WARNING! Risk of Fire! You MUST install an attic insu

-

lation shield when there is any possibility of insulation or 

other combustible material coming into contact with the 

chimney. 

ThIMbLE AppLICATION NOT REqUIRED WhEN ATTIC 

INsULATION shIELD Is UsED.
• 

DO NOT

 pack insulation between the chimney and the 

attic insulation shield. 

•  Failure to keep insulation and other materials away from 

chimney pipe could cause fire.

• 

DO NOT

 offset chimney inside insulation shield.

Catalog #

A

B

in.

mm

in.

mm

FS338

14-1/2

368

14-1/2

368

FS339

14-1/2

368

18-3/8

467

FS340

14-1/2

368

23

584

Содержание MEL36

Страница 1: ...hildren to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or othe...

Страница 2: ...Fireplace System Requirements 6 3 Framing and Clearances A Fireplace Dimensions 7 B Clearances 8 Minimum Clearances to Combustibles 8 C Frame the Fireplace 9 D Secure and Level the Fireplace 9 E Prot...

Страница 3: ...arth Home Technologies install parts or components not Listed or approved Improper installation adjustment alteration service or maintenance can cause injury or property damage For assistance or addit...

Страница 4: ...above and around fireplace Mantel and surround Decorative facing and trim Hearth extension Factory built fireplace Protective metal hearth strip s Outside combustion air Combustible framing header on...

Страница 5: ...OTICE In addition to these framing dimensions also reference the following section Clearances Section 3 B Design and Installation Considerations Notice Check building codes prior to installation Insta...

Страница 6: ...cating saw Framing material Pliers Non combustible sealant Hammer Gloves Phillips screwdriver Framing square Flat blade screwdriver Electric drill and bits Plumb line Safety glasses Level Tape measure...

Страница 7: ...75 in 476 mm 13 45 in 476 mm 21 in 533 mm 7 50 in 191 mm 9 25 in 235 mm 7 50 in 191 mm Gas Knockout Outside Air 9 25 in 235 mm Gas Knockout 7 50 in 191 mm 39 50 in 1003 mm C D B 21 37 in 543 mm 7 37 i...

Страница 8: ...cause fire Figure 3 2 Clearances to Combustible Materials Minimum Clearances to Combustibles WITHIN ENCLOSURE AREA Fireplace to backwall 1 2 in 13 mm Fireplace to sidewall 1 2 in 13 mm Top standoffs t...

Страница 9: ...nce between the framing and chimney section Clearance of Radiation Shield thimble to chimney is set at 1 1 2 in 38 mm Caution Risk of Cuts Abrasions Wear protective gloves and safety glasses during in...

Страница 10: ...n combustible surfaces DO NOT cover metal strips with combustible materials Sparks or embers may ignite flooring Hearth extensions MUST be installed exactly as specified Figure 3 6 Outside Air Install...

Страница 11: ...ireplace 35 ft 10 67 m Maximum unsupported chimney above roof 6 ft 1 83 m Warning Risk of Fire You must maintain 2 in 51 mm air space clearance to insulation and other combustible materials around the...

Страница 12: ...fset return You determine from the table that you need 34 1 8 in 867 mm Dimension B between the offset and re turn The chimney component that best fits your application is one SL324 15 degree 30 degre...

Страница 13: ...imney must extend 2 ft 6 m above any portion of the roof or adjacent structures within 10 ft 3 m of the chimney C Termination Requirements Install a cap approved and listed for this fireplace system L...

Страница 14: ...oof Additional support for tall chimneys Install roof flashing according to minimum requirements Maintain minimum clearances to combustibles as specified Offsets returns may not exceed 30 from vertica...

Страница 15: ...to fasten chimney sections together Do NOT penetrate inner flue Warning Risk of Fire You MUST use screws to fas ten offset returns to chimney sections to keep the chim ney parts from twisting Failure...

Страница 16: ...the extension to the thimble using the screws provided with the extension Install the thimble assembly and nail screw it securely to the framing members Center the flashing over the chimney and fasten...

Страница 17: ...ilated and the fireplace system height from floor to the flue outlet of the termination is 13 6 or more it is not necessary to use the Thimble and extend the radiation shield into the roof flashing Th...

Страница 18: ...codes for further details Double check the Chimney Assembly Continue assembling the chimney sections up as need ed While doing so be aware of the height and unsup ported chimney length limitations giv...

Страница 19: ...als may be used to cover the metal fireplace front A bead of 300 deg F minimum non combustible sealant must be used to close off any gaps at the top and sides between the fireplace and facing to preve...

Страница 20: ...bustible material Manufactured hearth materials will usually have a published R value resistance to heat or k value conductivity of heat Refer to the formula in Table 6 1 to convert a k value to an R...

Страница 21: ...le material Fireplace Opening 4 in 102 mm min Continuous non combustible sealant 1 2 in Micore Hearth Extension or equivalent insulation Figure 6 4 Hearth Extension Construction warning Risk of Fire A...

Страница 22: ...here the non combustible board is placed over the metal surfaces the space between the metal face of the fireplace and framing members Combustible Wall 2 x 4 stud wall Standoffs Measured from top of f...

Страница 23: ...mm 12 in 305 mm 11 1 4 in 286 mm FLUSH FRONT 4 in 102 mm BRICK FRONT 5 0 a n g l e 39 angle Figure 6 11 Mantel Leg Surround or Wall Projection acceptable on both sides of opening E Sidewalls Surround...

Страница 24: ...rovision Warning Fire and or Asphyxiation Risk Use with solid wood fuel or decorative gas appliance only Gas fire generates fumes DO NOT install unvented gas logs Damper must be locked fully open when...

Страница 25: ...883 SL348 48 1219 46 3 4 1187 Catalog Description CAK4A Chimney Air Kit ID4 ID6 Insulated Duct Outside Air UD4 UD6 Uninsulated Duct Outside Air SL306 Chimney Section 6 in 152 mm long SL312 Chimney Se...

Страница 26: ...7 Chimney Joint Band 2 in 51 mm 10 1 2 in 267 mm RF370 Roof Flashing 24 5 8 in 625 mm 27 3 8 in 695 mm 12 in 305 mm RF371 Roof Flashing 31 in 787 mm 24 5 8 in 625 mm 12 in 305 mm Catalog A B FS338 0 d...

Страница 27: ...r com Please contact your Heatilator dealer with any questions or concerns For the location of your nearest Heatilator dealer please visit www heatilator com 27 Heatilator MEL36 MEL42 Installation Man...

Отзывы: