Heatilator • MEL36, MEL42  Installation Manual • 4044-212 • Rev D • 01/06/15

B. Offsets/Returns

•  Use an offset/return to bypass overhead obstructions.

•  An offset and return can be used as a single entity or separated by chimney section(s).

 WARNING! 

Risk of Fire! DO NOT use offset/returns greater than 30°. Chimney draft will be restricted and could cause 

overheating and fire. Secure offsets with screws ( not to exceed 1/2” / 13 mm in length) Secure returns with strapping. 

Straight chimney sections may be secured with screws. Keep chimney sections from separating or twisting.

•  Measure the shift needed to avoid the overhead obstruction. Refer to dimension A in Figure 4.2.

•  Find the appropriate A dimension listed in Table 4.3. The B dimension coinciding with the A dimension measurement in 

Table 4.3 represents the required vertical clearance needed to complete the offset/return.

•  Read across the chart to find the number of chimney sections/model numbers needed between the offset and return.

A

B

1-1/4 in. (32 mm)

OVERLAP

Figure 4.2  Chimney Offset/Return

Table 4.3 Offset Dimensions

Example:

 

Your “A” dimension from Figure 4.2 is 14-1/2 in. (368 

mm). Using Table 4.3, the dimension closest to, but not 

less than 14-1/2 in. (368 mm) is 14-1/2 in. (368 mm) us-

ing a 30° offset/return. 
You determine from the table that you need 34-1/8 in. 

(867 mm) (Dimension “B”) between the offset and re-

turn. 
The chimney component that best fits your application is 

one SL324.

15-degree

30-degree

SL306 SL312 SL318 SL324 SL336 SL348

A

B

A

B

in.

mm

in.

mm

in.

mm

in.

mm

1 5/8

41

13 3/8

340

3 5/8

92

15 1/2 394

-

-

-

-

-

-

2 7/8

73

17 3/4

451

5 1/2

140 18 5/8 473

1

-

-

-

-

-

4 1/8

102

22 3/8

568

7 1/4

184 21 3/4 552

2

-

-

-

-

-

4 1/2

114

23 5/8

600

8 1/2

216 23 3/4 603

-

1

-

-

-

-

5 3/4

146

28 1/4

718 10 1/4 260

27

686

1

1

-

-

-

-

6

152

29 3/8

746 11 1/2 292

29

737

-

-

1

-

-

-

7 1/4

184

34

864 13 1/4 337 32 1/8 816

-

2

-

-

-

-

7 3/4

197

36 1/8

918 14 1/2 368 34 1/8 867

-

-

-

1

-

-

8 3/4

222

39 3/4 1010 16 1/4 413 37 3/8 949

1

-

-

1

-

-

10 3/8 264

45 5/8 1159 19 1/4 489 42 1/2 1080

-

-

2

-

-

-

10 5/8 270

46 3/4 1187 20 1/2 521 44 5/8 1133

-

-

-

-

1

-

11 7/8 302

51 3/8 1305 22 1/4 565 47 3/4 1213

1

-

-

-

1

-

13 1/2 243

57 1/4 1454 25 1/4 641 52 7/8 1343

-

-

-

2

-

-

13 3/4 349

58 3/8 1483 26 1/2 673

55

1397

-

-

-

-

-

1

15

381

63

1600 28 1/4 718 58 1/8 1476

1

-

-

-

-

1

16 1/2 419

68 3/4 1746 31 1/4 794 63 1/4 1607

-

1

-

-

-

1

18

457

74 5/8 1895 34 1/4 870 68 1/2 1740

-

-

1

-

-

1

19 5/8 498

80 3/8 2042 37 1/4 946 73 3/4 1873

-

-

-

1

-

1

20 5/8 524

84 1/8 2137 39 1/8 994 76 7/8 1953

1

-

-

1

-

1

22 3/4 578

91 7/8 2334 43 1/4 1099 84 1/8 2137

-

-

-

-

1

1

24

610

96 1/2 2451 45 1/8 1146 87 1/4 2216

1

-

-

-

1

1

25 7/8 657 103 1/2 2629 49 1/4 1251 94 1/2 2400

-

-

-

-

-

2

Proper assembly of air-cooled chimney parts result in an overlap at chimney joints of 1-1/4 in. (32 mm). Effective 

length is built into this chart.

Содержание MEL36

Страница 1: ...hildren to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or othe...

Страница 2: ...Fireplace System Requirements 6 3 Framing and Clearances A Fireplace Dimensions 7 B Clearances 8 Minimum Clearances to Combustibles 8 C Frame the Fireplace 9 D Secure and Level the Fireplace 9 E Prot...

Страница 3: ...arth Home Technologies install parts or components not Listed or approved Improper installation adjustment alteration service or maintenance can cause injury or property damage For assistance or addit...

Страница 4: ...above and around fireplace Mantel and surround Decorative facing and trim Hearth extension Factory built fireplace Protective metal hearth strip s Outside combustion air Combustible framing header on...

Страница 5: ...OTICE In addition to these framing dimensions also reference the following section Clearances Section 3 B Design and Installation Considerations Notice Check building codes prior to installation Insta...

Страница 6: ...cating saw Framing material Pliers Non combustible sealant Hammer Gloves Phillips screwdriver Framing square Flat blade screwdriver Electric drill and bits Plumb line Safety glasses Level Tape measure...

Страница 7: ...75 in 476 mm 13 45 in 476 mm 21 in 533 mm 7 50 in 191 mm 9 25 in 235 mm 7 50 in 191 mm Gas Knockout Outside Air 9 25 in 235 mm Gas Knockout 7 50 in 191 mm 39 50 in 1003 mm C D B 21 37 in 543 mm 7 37 i...

Страница 8: ...cause fire Figure 3 2 Clearances to Combustible Materials Minimum Clearances to Combustibles WITHIN ENCLOSURE AREA Fireplace to backwall 1 2 in 13 mm Fireplace to sidewall 1 2 in 13 mm Top standoffs t...

Страница 9: ...nce between the framing and chimney section Clearance of Radiation Shield thimble to chimney is set at 1 1 2 in 38 mm Caution Risk of Cuts Abrasions Wear protective gloves and safety glasses during in...

Страница 10: ...n combustible surfaces DO NOT cover metal strips with combustible materials Sparks or embers may ignite flooring Hearth extensions MUST be installed exactly as specified Figure 3 6 Outside Air Install...

Страница 11: ...ireplace 35 ft 10 67 m Maximum unsupported chimney above roof 6 ft 1 83 m Warning Risk of Fire You must maintain 2 in 51 mm air space clearance to insulation and other combustible materials around the...

Страница 12: ...fset return You determine from the table that you need 34 1 8 in 867 mm Dimension B between the offset and re turn The chimney component that best fits your application is one SL324 15 degree 30 degre...

Страница 13: ...imney must extend 2 ft 6 m above any portion of the roof or adjacent structures within 10 ft 3 m of the chimney C Termination Requirements Install a cap approved and listed for this fireplace system L...

Страница 14: ...oof Additional support for tall chimneys Install roof flashing according to minimum requirements Maintain minimum clearances to combustibles as specified Offsets returns may not exceed 30 from vertica...

Страница 15: ...to fasten chimney sections together Do NOT penetrate inner flue Warning Risk of Fire You MUST use screws to fas ten offset returns to chimney sections to keep the chim ney parts from twisting Failure...

Страница 16: ...the extension to the thimble using the screws provided with the extension Install the thimble assembly and nail screw it securely to the framing members Center the flashing over the chimney and fasten...

Страница 17: ...ilated and the fireplace system height from floor to the flue outlet of the termination is 13 6 or more it is not necessary to use the Thimble and extend the radiation shield into the roof flashing Th...

Страница 18: ...codes for further details Double check the Chimney Assembly Continue assembling the chimney sections up as need ed While doing so be aware of the height and unsup ported chimney length limitations giv...

Страница 19: ...als may be used to cover the metal fireplace front A bead of 300 deg F minimum non combustible sealant must be used to close off any gaps at the top and sides between the fireplace and facing to preve...

Страница 20: ...bustible material Manufactured hearth materials will usually have a published R value resistance to heat or k value conductivity of heat Refer to the formula in Table 6 1 to convert a k value to an R...

Страница 21: ...le material Fireplace Opening 4 in 102 mm min Continuous non combustible sealant 1 2 in Micore Hearth Extension or equivalent insulation Figure 6 4 Hearth Extension Construction warning Risk of Fire A...

Страница 22: ...here the non combustible board is placed over the metal surfaces the space between the metal face of the fireplace and framing members Combustible Wall 2 x 4 stud wall Standoffs Measured from top of f...

Страница 23: ...mm 12 in 305 mm 11 1 4 in 286 mm FLUSH FRONT 4 in 102 mm BRICK FRONT 5 0 a n g l e 39 angle Figure 6 11 Mantel Leg Surround or Wall Projection acceptable on both sides of opening E Sidewalls Surround...

Страница 24: ...rovision Warning Fire and or Asphyxiation Risk Use with solid wood fuel or decorative gas appliance only Gas fire generates fumes DO NOT install unvented gas logs Damper must be locked fully open when...

Страница 25: ...883 SL348 48 1219 46 3 4 1187 Catalog Description CAK4A Chimney Air Kit ID4 ID6 Insulated Duct Outside Air UD4 UD6 Uninsulated Duct Outside Air SL306 Chimney Section 6 in 152 mm long SL312 Chimney Se...

Страница 26: ...7 Chimney Joint Band 2 in 51 mm 10 1 2 in 267 mm RF370 Roof Flashing 24 5 8 in 625 mm 27 3 8 in 695 mm 12 in 305 mm RF371 Roof Flashing 31 in 787 mm 24 5 8 in 625 mm 12 in 305 mm Catalog A B FS338 0 d...

Страница 27: ...r com Please contact your Heatilator dealer with any questions or concerns For the location of your nearest Heatilator dealer please visit www heatilator com 27 Heatilator MEL36 MEL42 Installation Man...

Отзывы: