![heatco EMA Series Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/heatco/ema-series/ema-series_installation-operation-and-maintenance-instructions_2116238026.webp)
26
IX.
Gas Supply, Piping and Connections
1. Installation of piping must conform with local building codes and ordinances, or in the absence of local codes with
ANSI Z223.1 the National Fuel Gas Code. In Canada, installation must be in accordance with CAN/CGA –B149.1 for
Natural Gas and B149.2 for Propane units. Use a pipe sealant
resistant to LP gases
on Gas supply connections to
heater.
2. When several units are served by the same main gas supply, the total capacity (cubic feet per hour), and length of the
gas supply must be considered in sizing the supply piping to the furnace. See Table 5 below.
3. Be sure that gas regulators servicing more than one heater have the proper pipe and internal orifice size for the total
input of all heating units serviced by the regulator.
4. The Minimum gas supply pressure to each furnace for use with Natural Gas is 5.0” w.c. and for Propane Gas is 11.0”
w.c.. Maximum gas pressure must not exceed 14.0” w.c. for either gas.
5. A drip leg (sediment trap) and a manual shut off valve must be provided immediately upstream of the gas control on
the heating unit (See Figure 21). To facilitate servicing of unit, installation of a union is recommended.
Figure 21 – Drip Leg and Supply Connection
6.
Use a back up wrench
on the gas valve when connecting field supply gas piping to avoid loosening pre-piped furnace
gas connections during installation.
7.
The individual duct furnace inlet gas supply pipe connection size is ¾” NPT. Do not use pipe smaller than ¾”
NPT to the furnace.