Table 3 – Clearances to Horizontal Vent Terminal
Structure
Min. Clearances to Vent Terminal
(all directions unless specified)
Combustion air inlet of another appliance
6 ft. (1.8m)
Forced air inlet within 10 ft. (3.1m)
3 ft. (0.9m) above
Door, window or gravity air inlet
4ft. (1.2m) horizontally
4 ft. (1.2m) below
1ft. (0.3m) above
Gas meter and relief equipment, Electric meter
US- 4ft. (1.2m) horizontally
Canada - 6 ft. (1.8m)
Gas Regulator
3 ft. (0.9m) horizontally
Adjacent public walkways
7 ft. (2.1m) above
When venting through exterior combustible walls a minimum clearance of 1” must be maintained.
Refer to Figures 10 and 11
below for proper through the wall installations depending on the type of wall
material.
Figure 10 –Combustible Material Wall