Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. T • 3/14
30
Top Vent - Vertical Termination
This model is approved to use DVP or SLP Series fl ue
pipe components. A
DVP-TVHW
or
SLP-TVHW
vertical
Termination Cap must be used to terminate fl ue systems
in a vertical position.
Approved fl ue system components are labeled for identifi -
cation.
NO OTHER FLUE SYSTEMS OR COMPONENTS
MAY BE USED.
Detailed installation instructions are in-
cluded with each fl ue termination kit and should be used
in conjunction with this manual.
WARNING! Risk of Fire! This gas appliance and fl ue
assembly must be fl ued directly to the outside and must
never be attached to a chimney serving a separate solid
fuel burning appliance. Each gas appliance must use a
separate fl ue system-common fl ue systems are prohibited.
WARNING! Risk of Fire! DO NOT apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specifi ed in
this manual. Overlapping material could ignite and will in-
terfere with proper operation of doors and louvers.
• Horizontal sections 3 in. (76 mm) from the top of the
pipe.
• Horizontal sections 2-1/2 in. (64 mm) at wall shield
fi restops.
• Horizontal sections 1 in. (25 mm) from sides and bottom
of the pipe.
• Vertical sections 1 in. (25 mm) on all sides of pipe.
Failure to keep insulation or other material away from vent
pipe may cause over heating and fi re.
For alternative installations, other than depicted, contact
your dealer for further information.
MODEL
FLUE TERMINATION APPROVALS
350TRSI-AUF
350TRSILP-AUF
SLP-TVHW, DVP-TVHW
Figure 7.8
Figure 7.7
V
MAX. RUN
36 ft.
(10.97 m)
Straight Up Vertical Flue System
Figure 7.7 shows straight up vertical fl ue system approved
for use on this model.
If the heater installation requires a vertical fl ue
exceeding 14-3/4 in. (4.5 m) above the unit
with no horizontal fl ue or elbows a vertical fl ue
restrictor must be installed (see Figure 7.7).
CAP
V
1
RESTRICTOR
PLATE