![Heat Transfer Phoenix Evolution Скачать руководство пользователя страница 14](http://html.mh-extra.com/html/heat-transfer/phoenix-evolution/phoenix-evolution_installation-and-operation-manual_2115981014.webp)
ing valve certified to ASSE 1017. You must completely follow the instructions included with the mix-
ing valve for proper installation. This mixing valve must be installed on the domestic outlet to assure
that the hot water temperature does not vary as the unit adjusts its stored water automatic set point
to meet the requirements of the hydronic heating module.
D. PHOENIX EVOLUTION PIPING
The domestic inlet and outlet ports on all the Phoenix Evolution are 1” NPT connections. We rec-
ommend the installation of shut-off valves and unions on both the inlet and outlet ports to isolate
the Phoenix Evolution for future service. It is important the connections on the inlet and outlet are
brass or copper. Never use dielectric unions or galvanized steel fittings. Teflon thread sealant must
be used to seal tank all connections. An approved ASSE 1017 mixing valve is provided with every
Phoenix Evolution and must be installed on the outlet to protect the user from scalding tempera-
tures. This valve will reduce the point of discharge temperature by mixing the hot and cold water
from the discharge outlet or mixed outlet port. This device alone will not protect the user from scald-
ing temperature. Point of use devices must be installed to protect user from scalding temperatures.
Use only point of use mixing valves that are rated under the approved ASSE 1016 standard. To install
and set up the mixing valve, follow the pre-installation steps in this manual and also follow the
enclosed instructions included with the mixing valve.
E. MIXING VALVE INSTALLATION
DOMESTIC WATER PIPING
n
WARNING
The mixing valve provided with this appliance must be installed on the hot water outlet
connection to reduce the risk of scalding. This mixing valve only reduces the risk of a
scalding injury. The installation of additional mixing valves at the point of use is
required.
13
n
DANGER
Water temperature over 125 degrees F. can cause severe burns
instantly, or death from scalds. Children, disabled, and elderly are
at highest risk of being scalded. See instruction manual before
setting temperature at water heater. Feel water before bathing or
showering! Temperature limiting valves are available. See chart
below showing temperature burn rate.
PART 4: DOMESTIC WATER PIPING
(CONTINUED)
Содержание Phoenix Evolution
Страница 71: ...70 ...
Страница 72: ...71 ...
Страница 73: ...72 MAINTENANCE NOTES ...
Страница 74: ...73 MAINTENANCE NOTES ...
Страница 75: ...74 MAINTENANCE NOTES ...
Страница 76: ... 2009 Heat Transfer Products Inc www htproducts com LP 314 REV 12 21 09 ...