PART 12: TROUBLESHOOTING
(CONTINUED)
NOTE: If receiving
an F09 fault code,
c h e c k t h e g a p
spacing between
points on the elec-
trode by holding
t w o q u a r t e r s
together and slid-
ing them through
t h e g a p . T h e r e
should be a slight
resistance.
Resistance Table
Fig. 12-3
Fig. 12-4
GAS-FIRED HOT WATER SUPPLY BOILER
Boiler Manual
63
PART 13: MAINTENANCE
A. MAINTENANCE PROCEDURES
Periodic maintenance should be performed
once a year by a qualified service technician to
assure that all the equipment is operating safely
and efficiently. The owner should make neces-
sary arrangements with a qualified heating con-
tractor for periodic maintenance of the heater.
Installer must also inform the owner that the lack
of proper care and maintenance of the heater
may result in a hazardous condition.
n
WARNING
BEFORE EACH HEATING SEASON
A trained
and qualified service technician should perform
the inspections as per the boiler inspection and
maintenance schedule in the back of manual.
Failure to do so could result in death or serious
injury.
Water Temperature (°F)
Resistance (ohms)
32
32550
41
25340
50
19870
59
15700
68
12490
77
10000
86
8059
95
6535
104
5330
113
4372
122
3605
131
2989
140
2490
149
2084
158
1753
167
1481
176
1256
185
1070
194
915
203
786
212
667
System/Pipe Sensor Temperature Sensor 7250P-324
Boiler Sensor (7250P-667) Indirect/Tank Sensor (72 50P-325)
Содержание MODCON VWH 300 HL
Страница 23: ...PART 5 BOILER PIPING CONTINUED GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 22 ...
Страница 24: ...PART 5 BOILER PIPING CONTINUED GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 23 ...
Страница 25: ...PART 5 BOILER PIPING CONTINUED GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 24 ...
Страница 26: ...PART 5 BOILER PIPING CONTINUED GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 25 ...
Страница 28: ...27 GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual PART 5 BOILER PIPING CONTINUED ...
Страница 52: ...PART 8 FIELD WIRING CONTINUED Fig 8 5 LP 255 Rev 11 09 09 GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 51 ...
Страница 75: ...LP 172 REV 2 16 06 74 ...
Страница 76: ...LP 172 REV 2 16 06 75 ...
Страница 77: ...MAINTENANCE NOTES 76 ...
Страница 78: ...MAINTENANCE NOTES 77 ...
Страница 79: ...MAINTENANCE NOTES 78 ...
Страница 80: ... 2003 2009 Heat Transfer Products Inc www HTproducts com LP 276 REV 11 25 09 ...