to normal operation. If the code is entered cor-
rectly, the control will switch off the gas valve and
purge fan while showing a solid
|
---
|
in the dis-
play. The display will then show a
|1|
alternating to
|dd|
. This first function verifies that the control is
configured as a VWH boiler.
C. PROGRAM NAVIGATION
Next you will have to press the
{S/3}
key to move
through each function. To increase or decrease
a value, you will need to press either the
{S/1-}
key or
{S/2+}
key to change the default values. If
there is no key action for 1 minute, the display
returns to normal operation. Changes are effec-
tive immediately but not directly stored until the
{S/4}
key is pressed down for 3 seconds then the
new values are stored. Listed below are the vari-
ety of functions the installer can program into
the 926 Control.
Function Default Function
Number
Value
Description
1
dd
N o change allowed
2
149ºF N o change allowed
3
180˚ Maximum Domestic water heater
delivery temperature allowed in
user menu. Installer can set the
maximum temperature. Range
95-185
4
20ºF
Offset temperature / number of
degrees above the tank set point
that will control the boiler output.
Ex. Storage tank set at 120º with
20º offset boiler supply will be
140º. Range 1-39
5
7ºF
Allows the installer to change the
differential temperature (dh)
Range 1-18
6
5 Min. Circulator Post Purge Time after
tank sensor is satisfied that the
pump will run (Note: it is recom-
mend that Circulator Post Purge
Time be set no greater than 5 min-
utes). Range: 0 to 10 minutes
Function Default Function
Number
Value
Description
7
68
N /A (No change required)
8
5
N /A (No change required)
9
180
N /A (No change required)
10
68
N /A (No change required)
11
95
N /A (No change required)
12
68
N /A (No change required)
13
0
N /A (No change required)
14
30
N /A (No change required)
15
0
Bus Addressing Boilers (Cascade
8 Boiler Max.)
Master = Address 0 / Followers =
Address 1 thru 7.
Note: Never address boiler with
number 8 which is not to be used.
Range: 0-8
16
0
Allows the installer to connect up
a 0-10 Volt signal directly from
Building Management System. To
activate, change value to 2.
Warning: Values 1 and 3 are not to
be programmed into board
Range: 0-3
17
0
N /A (No change required)
18
1
N /A (No change required)
19
180
N /A (No change required)
20
2
Flow switch. Do not change
0= none
1=water pressure switch
2=flow switch
3=low water cut-off
21
0
N /A (No change required)
22
100% Maximum boiler output percent-
age. Default = 100%. This param-
eter can be adjusted to lower the
maximum boiler output if neces-
sary. Example MOD CON 500
boiler setting at 80% boiler will go
to 400000 BTU/hr max rather than
500000 BTU/hr. Range 50–100%
PART 11: START-UP PROCEDURES FOR THE INSTALLER
(CONTINUED)
CAUTION
The Boiler cannot be programmed while
there is a call for heat.
GAS-FIRED HOT WATER SUPPLY BOILER
Boiler Manual
58
Содержание MODCON VWH 300 HL
Страница 23: ...PART 5 BOILER PIPING CONTINUED GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 22 ...
Страница 24: ...PART 5 BOILER PIPING CONTINUED GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 23 ...
Страница 25: ...PART 5 BOILER PIPING CONTINUED GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 24 ...
Страница 26: ...PART 5 BOILER PIPING CONTINUED GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 25 ...
Страница 28: ...27 GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual PART 5 BOILER PIPING CONTINUED ...
Страница 52: ...PART 8 FIELD WIRING CONTINUED Fig 8 5 LP 255 Rev 11 09 09 GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 51 ...
Страница 75: ...LP 172 REV 2 16 06 74 ...
Страница 76: ...LP 172 REV 2 16 06 75 ...
Страница 77: ...MAINTENANCE NOTES 76 ...
Страница 78: ...MAINTENANCE NOTES 77 ...
Страница 79: ...MAINTENANCE NOTES 78 ...
Страница 80: ... 2003 2009 Heat Transfer Products Inc www HTproducts com LP 276 REV 11 25 09 ...