MODBUS Installation and Operation Manual

HT# 059266-00A

HWrQ PlaTInUM MODBUS VarIaBle lIST

HWrQ reg / 

VarIaBle#

DeSCrIPTIOn

MUlT

 ♦1

(if not 1)

UOM

range / STaTeS / SPeCIal 

ValUeS

reaD 

Only

1 – 3

Model

6 Character string 

♦3

X

4 – 13

Serial Number

20 Character string 

♦3

X

14

Firmware Version

100

X

15

Boost Offset

°C, °F

0 - 33°C, 0 - 60°F

16

Boost Mode

0=Off, 1=Vari Boost, 

2=Vari Boost + ESD

17,18

Bypass Time

Minutes

0 - 2,147,483,647 

♦4

X

19 through 50

Boiler Status

(BTYPE=0)®

(BTYPE=1)®

(BTYPE=2)®

(BTYPE=3)®

0=Off, 1=On

0=Off, 1=Low, 2=High

0=Off, 1=Low, 2=Med, 3=High, 

0=Off, 1=Low, 2=MLow, 3=Mhigh, 

4=High

X

51

Boiler Type . See"HWRQ Platinum 

Boiler Type Table" on page 7

0=On/Off, 1=2-Stage, 2=3-Stage, 

3=4-Stage

52

Bypass Mode

0=Auto, 1=Bypass

53 through 84

Extension Panel Stage 

Communication Error

0=“”, 1=C/E

X

85

Control Mode

0=Reset, 1=Set Point

86

Outdoor Cut-off

°C, °F

0 - 25°C, 30 - 75°F

87

DHW Call Mode

0=No Priority, 1= Priority

88

Day Light Saving

0=Enable, 1=Disable

89

Sensor Fault Mode

0=Stages On, 1=Stages Off

90

Fast Cool Down

0=Minimum Target Temp, 1=Off

91

Sensor Type

0=°F Sensor, 1=°C Sensor

92

Lead Boiler

See"HWRQ Platinum Boiler Type 

Table" on page 7

93 through 124

Lockout Input

0=(inactive), 1=L/O

X

125

Logic Mode

0=PID, 1=OSS

126

Last Stage Hold

°C, °F

0 –17°C, 0 - 30°F

127

Min Runtime

Minutes

1-60

128

Min Water Temp

°C, °F

21 - 77°C, 70 - 170°F

129 through 160 Boiler Mode

0=Auto, 1=Standby, 2=Off, 3=On

161

Total Boilers

1 – 32 / (BTYPE+1)

162

Outdoor Sensor

°C, °F

-40 – 121°C, -40 - +250°F

(32000=Open, 32001=Shorted)

♦2

X

163

Outdoor Sensor Trim

°C, °F

-3 - +3°C, -5 - +5°F

164

Offset Temp

°C, °F

-22 - +22°C, -40 - +40°F

165

Panel Date

Days since 

1/1/1981

0 – 36500

166

Pump Run-On

Minutes

0 - 60

167

Panel Time

Minutes 

since 0:00

0 – 1439, 1440=not set

168

Pump

0=Off, 1=On

X

169

Purge Delay

Minutes

0-10

170

Reset Ratio

0=1:3, 1=1:2, 2=1:1 .5, 3=1:1 .25, 

4=1:1, 5=1 .25:1, 6=1 .5:1, 7=2:1, 

8=3:1, 9=4:1

171

Reaction Time

Minutes

1 - 10

Содержание MODBUS RTU RS485

Страница 1: ...or safety control all equipment must have its own certified limit and safety controls required by local codes The installer must verify proper operation and correct any safety problems prior to the in...

Страница 2: ...Configuration 3 MODBUS Communication Options 3 MAC Address 3 Baud 3 Troubleshooting 3 HWr Platinum MODBUS Variable list 4 HWrQ Platinum MODBUS Variable list 6 Multi MOD Platinum MODBUS Variable list...

Страница 3: ...US COMMUnICaTIOn OPTIOnS SELECT MENU Maintenance Network Settings Multi MOD Platinum SELECT MENU Settings More Settings Remote Interface Network Settings All Other Platinum Controls Before connecting...

Страница 4: ...f 27 Sensor Type 0 F 1 C 28 Minimum Water Temp C F 21 71 C 70 170 F 29 Outdoor Sensor C F 40 122 C 40 250 F 32000 Open 32001 Shorted 2 X 30 Outdoor Sensor Trim C F 3 3 C 5 5 F 31 Offset Temperature C...

Страница 5: ...Single Register function code 6 and Write Multiple Registers function code 16 are supported note All variables with multiple UOM s depend upon the value of Input Mode to determine which to use note Us...

Страница 6: ...Cut off C F 0 25 C 30 75 F 87 DHW Call Mode 0 No Priority 1 Priority 88 Day Light Saving 0 Enable 1 Disable 89 Sensor Fault Mode 0 Stages On 1 Stages Off 90 Fast Cool Down 0 Minimum Target Temp 1 Off...

Страница 7: ...are packed 2 characters per register most significant byte first 4 Multi register values are stored big endian first register x 65536 second register value note All variables are stored as Holding Re...

Страница 8: ...0 60 79 Input Mode 0 F 1 C 2 15psi 3 30psi 4 100psi 5 200psi 6 300psi 7 HWR 8 Reset F 9 Reset C X 80 Lead Stage 0 19 A T 81 Pre purge Delay 10 Minutes 0 0 10 0 82 through 101 Lockout Input Stages 1 20...

Страница 9: ...ecified divide a read value by this to obtain the actual value Multiply desired value by this before writing 2 For variables that specify them if a read value is a special value 32000 32005 do not div...

Страница 10: ...ted 2 X 31 Outdoor Sensor Trim C F 3 3 C 5 5 F 32 Operation Mode 0 Burner valve 1 District Steam 33 Output Relay 0 Off 1 On X 34 Panel Date Days since 1 1 1981 0 36500 35 Panel Time Minutes since 0 00...

Страница 11: ...mation MPCQ PlaTInUM MODBUS VarIaBle lIST MPCQ reg VarIaBle DeSCrIPTIOn MUlT 1 if not 1 UOM range STaTeS SPeCIal ValUeS reaD Only 1 3 Model 6 Character string 3 X 4 13 Serial Number 20 Character strin...

Страница 12: ...tem Run on Minutes 0 60 237 System Relay 0 Off 1 On X 238 Throttle Range 2 psi 0 5 5 0 239 Heat Establish Pressure 10 psi 0 5 5 0 MPCQ Platinum Boiler Type Table Boiler Type LEAD Special value Up to T...

Страница 13: ...o 0 note Use Setback if Operation Mode is set to 1 note Use Last Stage Hold Min Runtime Purge Reaction Time Standby Delay when Logic Mode is set to 0 note Use Reaction Time when Lead Stage Rotation Mo...

Страница 14: ...6 Day Light Saving 0 Enable 1 Disable 27 Sensor Fault Mode 0 OutputOn 1 OutputOff 28 Valve at Freezing 0 100 29 Sensor Mode 0 F 1 C X 30 Motor Time Seconds 120 600 31 Manual Valve Target 0 100 32 Nigh...

Страница 15: ...gister value note All variables are stored as Holding Registers MODBUS functions Read Holding Registers function code 3 Write Single Register function code 6 and Write Multiple Registers function code...

Страница 16: ...building systems including but not limited to the heating system boilers or electrical power system that is required for proper operation of any controls or other equipment installed by Heat Timer Co...

Отзывы: