MODBUS Installation and Operation Manual
11
HT# 059266-00A
note:
All variables are stored as ‘Holding Registers’ . MODBUS functions :
• ‘Read Holding Registers’ (function code 3),
• ‘Write Single Register' (function code 6),
• and ‘Write Multiple Registers’ (function code 16) are supported .
note:
All variables with multiple UOM’s depend upon the value of ‘Input Mode’ to determine which to use .
note:
Use 'District Steam Delay' when 'Operating Mode' is set to District Steam . Use 'System Setpoint',
'System Differential' and 'Thermal Lockout Enable' when 'Operation Mode' is set to Burner/valve .
note:
Use 'Vari-Boost Adjustment' when 'Boost Mode' is set to Vari-Day or Vari+ESD . Use
'Manual Boost Time' when 'Vari-Boost Adjustment' is set to Manual Boost .
note:
The MPC Platinum has a schedule, which is 7-days, 4 day/night pairs per day . For example: Register
38 is the first DAY schedule of Monday; Register 39 is the first NIGHT schedule of Monday; Register 46
is the first DAY schedule of Tuesday; Register 47 is the first NIGHT schedule of Tuesday and so on .
note:
Use MPC Platinum Installation and Operation manual for supplementary information .
MPCQ PlaTInUM MODBUS VarIaBle lIST
MPCQ reg /
VarIaBle#
DeSCrIPTIOn
MUlT
(if not 1)
UOM
range / STaTeS / SPeCIal
ValUeS
reaD
Only
1 – 3
Model
X
4 – 13
Serial Number
20 Character string
X
14
Firmware Version
100
X
15
Vari-Boost Adjustment
10
0 .1 – 6 .4
16
Boost Mode
0=Disabled, 1=Manual,
2=Vari, 3=Vari+ESD
17
Manual Boost Time
Minutes
0 – 120
18,19
Bypass Time
Minutes
0 – 2,147,483,647
X
20 through 51
Boiler Status
(BTYPE=0)®
(BTYPE=1)®
(BTYPE=2)®
(BTYPE=3)®
0=Off, 1=On0=Off, 1=Low,
2=High, 0=Off, 1=Low, 2=Med,
3=High, 0=Off, 1=Low,
2=MLow, 3=Mhigh, 4=High
X
52
Boiler Type See "MPCQ Platinum
0=On/Off, 1=2-Stage2=3-
Stage, 3=4-Stage
53
Bypass Mode
0=AUTO, 1=ON
54
Cycle Length
Minutes
10 – 240
55 through 86
Extension Panel Stage
Communication Error
0=“”, 1=C/E
X
87
Day Heat Adjustment
0 – 15 = A – P
88
Outdoor Day Cutoff
°C, °F
-6 - 38°C, 20 - 100°F
89
Day Light Saving
0=Enable, 1=Disable
90
Sensor Fault Mode
0=OutputOn,1=OutputOff
91
Sensor Mode
0=°F, 1=°C
92
Lead Boiler
93 through 124
Lockout Input
0=(inactive), 1=L/O
X
125
Logic Mode
0-PID, 1-OSS
126
Last Stage Hold
10
psi
0 .0 – 5 .0
127
Min Runtime
Minutes
1 – 60
128 through 159 Boiler Mode
0=Auto, 1=Standby, 2=Off, 3=On
160
Total Boilers
1 – 32/(BTYPE+1)
161
Night Heat Adjustment
0 – 15 = A – P