MODBUS Installation and Operation Manual

 

 

3

HT# 059266-00A

MODBUS TyPe

•   Heat-Timer Platinum controls can be ordered with or upgraded to MODBUS communication.

•   The Platinum MODBUS communication uses RTU protocol and RS485 wiring.

•   When upgrading a standard Platinum control to MODBUS communication, the CPU 

Board on the back of the Platinum control must be replaced.  In addition, the MODBUS 

Communication Board must be installed.  See "Platinum Control Rear View" on page 1.

Motherboard

CPU Board

A(+)

G

B(-)

PlaTInUM Panel COnneCTeD 

TO MODBUS neTWOrK

Connect to MODBUS

RS485 Network

MODBUS

Communication

Board

MODBUS rS485 WIrIng

•   Heat-Timer Platinum control MODBUS communication uses a RS485 connection.

•   Connect the RS485 to the back of the Platinum control's MODBUS Communication Board.

•   Use 18 AWG Twisted-Pair cable.  The cable length must not exceed 3500 feet.

•   The Ground RS485 terminal (G) MUST be connected to the BMS RS485 Ground.

 alerT

DO NOT USE the RS485 Connector on the Motherboard for MODBUS communication .

Use the RS485 Connector on the MODBUS Communication Board instead .

MODBUS rTU COMMUnICaTIOn COnfIgUraTIOn

•   If the Platinum control was purchased with or upgraded to a MODBUS communication, some 

of the following settings must be configured to guarantee proper communication.

--NETWORK SETTINGS--

 MAC Address 

1

 Baud 

9600

MODBUS COMMUnICaTIOn OPTIOnS

SELECT: 

MENU/<Maintenance>/Network Settings

 

Multi-MOD Platinum

SELECT: 

MENU/<Settings>/<More Settings>/<Remote Interface>/Network Settings

 

All Other Platinum Controls

•   Before connecting the Platinum control to the MODBUS network, the user must set the following parameters according to the 

MODBUS Network Administrator's instructions.

MaC aDDreSS

Options: 

From 1 to 247

 

Default: 1

•   This is a unique ID within the MODBUS network.  It must be provided by the MODBUS 

Network Administrator.

---- MAC ADDRESS ---

      1

[            ]

BaUD

Options: 

9600, 19200, 38400

 

Default: 9600

•   The Baud determines the speed of communication.

•   Both the Platinum control and BMS must use the same Baud rate.

•   The communication is fixed to 8 Data Bits, No Parity, and 2 Stop Bits.

------ BAUD RATE -----

 9600

 19200

 38400

 alerT

MODBUS capable Platinum controls will display  

--NETWORK PANEL--

 

on the 2nd row of the display when in screen saver mode .

TrOUBleSHOOTIng

If no communication is the symptom, check the following:

•   Make sure that RS485 A(+) and B(-) terminals polarity is correct.  Otherwise, there will be no communication.

•   Both devices must have the same Baud rate.  Successful communication depends on matching the Baud rate of both devices.

•   Check that the RS485 G terminal is connected properly.

If intermittent communication is the symptom, check the following:

•   Make sure that the communication cable is of the twisted-pair type.

•   Reliable communication depends on the cable length and Baud rate used.  Long cable length may require a lower Baud rate.

Содержание MODBUS RTU RS485

Страница 1: ...or safety control all equipment must have its own certified limit and safety controls required by local codes The installer must verify proper operation and correct any safety problems prior to the in...

Страница 2: ...Configuration 3 MODBUS Communication Options 3 MAC Address 3 Baud 3 Troubleshooting 3 HWr Platinum MODBUS Variable list 4 HWrQ Platinum MODBUS Variable list 6 Multi MOD Platinum MODBUS Variable list...

Страница 3: ...US COMMUnICaTIOn OPTIOnS SELECT MENU Maintenance Network Settings Multi MOD Platinum SELECT MENU Settings More Settings Remote Interface Network Settings All Other Platinum Controls Before connecting...

Страница 4: ...f 27 Sensor Type 0 F 1 C 28 Minimum Water Temp C F 21 71 C 70 170 F 29 Outdoor Sensor C F 40 122 C 40 250 F 32000 Open 32001 Shorted 2 X 30 Outdoor Sensor Trim C F 3 3 C 5 5 F 31 Offset Temperature C...

Страница 5: ...Single Register function code 6 and Write Multiple Registers function code 16 are supported note All variables with multiple UOM s depend upon the value of Input Mode to determine which to use note Us...

Страница 6: ...Cut off C F 0 25 C 30 75 F 87 DHW Call Mode 0 No Priority 1 Priority 88 Day Light Saving 0 Enable 1 Disable 89 Sensor Fault Mode 0 Stages On 1 Stages Off 90 Fast Cool Down 0 Minimum Target Temp 1 Off...

Страница 7: ...are packed 2 characters per register most significant byte first 4 Multi register values are stored big endian first register x 65536 second register value note All variables are stored as Holding Re...

Страница 8: ...0 60 79 Input Mode 0 F 1 C 2 15psi 3 30psi 4 100psi 5 200psi 6 300psi 7 HWR 8 Reset F 9 Reset C X 80 Lead Stage 0 19 A T 81 Pre purge Delay 10 Minutes 0 0 10 0 82 through 101 Lockout Input Stages 1 20...

Страница 9: ...ecified divide a read value by this to obtain the actual value Multiply desired value by this before writing 2 For variables that specify them if a read value is a special value 32000 32005 do not div...

Страница 10: ...ted 2 X 31 Outdoor Sensor Trim C F 3 3 C 5 5 F 32 Operation Mode 0 Burner valve 1 District Steam 33 Output Relay 0 Off 1 On X 34 Panel Date Days since 1 1 1981 0 36500 35 Panel Time Minutes since 0 00...

Страница 11: ...mation MPCQ PlaTInUM MODBUS VarIaBle lIST MPCQ reg VarIaBle DeSCrIPTIOn MUlT 1 if not 1 UOM range STaTeS SPeCIal ValUeS reaD Only 1 3 Model 6 Character string 3 X 4 13 Serial Number 20 Character strin...

Страница 12: ...tem Run on Minutes 0 60 237 System Relay 0 Off 1 On X 238 Throttle Range 2 psi 0 5 5 0 239 Heat Establish Pressure 10 psi 0 5 5 0 MPCQ Platinum Boiler Type Table Boiler Type LEAD Special value Up to T...

Страница 13: ...o 0 note Use Setback if Operation Mode is set to 1 note Use Last Stage Hold Min Runtime Purge Reaction Time Standby Delay when Logic Mode is set to 0 note Use Reaction Time when Lead Stage Rotation Mo...

Страница 14: ...6 Day Light Saving 0 Enable 1 Disable 27 Sensor Fault Mode 0 OutputOn 1 OutputOff 28 Valve at Freezing 0 100 29 Sensor Mode 0 F 1 C X 30 Motor Time Seconds 120 600 31 Manual Valve Target 0 100 32 Nigh...

Страница 15: ...gister value note All variables are stored as Holding Registers MODBUS functions Read Holding Registers function code 3 Write Single Register function code 6 and Write Multiple Registers function code...

Страница 16: ...building systems including but not limited to the heating system boilers or electrical power system that is required for proper operation of any controls or other equipment installed by Heat Timer Co...

Отзывы: