2-Way Motorized Valve with Feedback installation Manual

HT# 059301-00 

A

ValVE DiMEnsiOns

Motorized Valves should be sized by Cv ratings 

(the capacity factor or flow coefficient).  This is 

defined as the number of gallons of water at 60°F 

that pass through a device with a one pound per 
square inch pressure differential.

1

5

 ¼

 

B

c

a

7 ⅝ 

7 ½

2-Way single-seat Motorized Valve

Valve 

size

catalog 

number

Flow

Coefficient 

cv

Dimensions

Mount

Body

trim

Est 

shipping 

Weight

Medium

temp 

range °F

a

B

c

1 ½”

928051-50-VM

24

5 ¾

3 ¼

19”

NPT

Bronze

S. Steel

31

32 to 400

2”

928052-00-VM

40

6 ½“

3 ⅝ ”

19 ¼”

NPT

Bronze

S. Steel

35

32 to 400

2 ½”

928052-50-VM

65

9”

4 ¾”

20 ¾”

Flanged

Iron

Bronze

71

32 to 300

3”

928053-00-VM

90

10”

5 ⅜”

21 ⅝”

Flanged

Iron

Bronze

88

32 to 300

4”

928054-00-VM

170

13”

6 ⅜"

22 ⅝”

Flanged

Iron

Bronze

135

32 to 300

5”

928055-00-VM

280

15 ¾”

5 ¾"

23 ¼”

Flanged

Iron

Bronze

150

32 to 300

6”

928056-00-VM

360

17 ¾”

6 ½”

23 ⅞”

Flanged

Iron

Bronze

191

32 to 300

8”

928058-00-VM

680

16 ¼”

8 ⅞”

25 ⅛”

Flanged

Iron

Bronze

306

32 to 300

10”

928060-00-VM

960

20"

9 ⅞”

25 ⅞”

Flanged

Iron

Bronze

451

32 to 300

trOUBlEsHOOting

loud banging noise.

•   Make sure that the valve is installed on a horizontal pipe.
•   Make sure that no condensate will drain back against the valve when closed.  This will cause the steam to flash the 

condensate causing the banging when the valve opens.

actuator does not move.

•   Make sure that the control is sending a moving signal to the actuator.  The control must have a relay in each of the 

outputs.

•   Check that the transformer is operating properly and is its VA rating is equal to or higher than the actuator's VA 

rating.  See "Actuator Specifications" on page 8.

Содержание 928051-50-VM

Страница 1: ...y control All equipment must have its own certified limit and safety controls required by local codes The installer must verify proper operation and correct any safety problems prior to the installati...

Страница 2: ...ped per the following packing lists Valve package actuator package Valve Bushing Locknut Actuator Actuator Brass Bracket with two hex screws and two nuts Hex Wrench 5 24 VAC Transformer Stem Nut Stem...

Страница 3: ...the valve Remove the Actuator Brass Brackets This should release the Stem Attachment Thread the Stem Attachment to the Valve Stem Make sure that it is tightened against the Stem Nut Mount the Actuato...

Страница 4: ...oating type signal R W B The actuator must be powered using the provided 24 VAC transformer A single transformer can only power a single actuator The transformer is supplied with every complete valve...

Страница 5: ...SENSORS INPUTS ROUTE SENSOR AND AUXILIARY WIRES THROUGH THIS KNOCKOUT ONLY SYS AUX CLOCK OPTION 1 T T Cycle On 5 60m Val 45 Day OD 31 o F SYS 148 o F OUTPUT T T C O R P O R A T I O N R 2 3 4 5 9 10 12...

Страница 6: ...Bronze 88 32 to 300 4 928054 00 VM 170 13 6 22 Flanged Iron Bronze 135 32 to 300 5 928055 00 VM 280 15 5 23 Flanged Iron Bronze 150 32 to 300 6 928056 00 VM 360 17 6 23 Flanged Iron Bronze 191 32 to...

Страница 7: ...ted to the heating system boilers or electrical power system that is required for proper operation of any controls or other equipment installed by Heat timer corporation or any contractor third party...

Страница 8: ...actuator for manual operation Mounting Vertical above center line of valve Feedback Signal 1K ohm Terminals 8 9 10 2 Way Valve Specifications Body 1 2 Valves ANSI B16 15 Bronze 250lb Threaded NPT 2 1...

Отзывы: