spEciFicatiOns

Actuator Specifications

Actuator Input Signal: 

  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 

24VAC Floating

Power Consumption: .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .10VA
Operating temperature .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  

Ambient 15°F to 120°F

Manual Override:    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Manual Crank
Construction:    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

Aluminum Bracket and Housing

Locations: 

  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 

NEMA Type 2 / IP54 Indoor Only

Clearance:  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

Minimum of 4- 6” above the actuator for manual operation

Mounting:.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .Vertical above center line of valve
Feedback Signal:.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

1K ohm Terminals (8, 9, 10)

2-Way Valve Specifications

Body: 

  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

(1 ½” -2” Valves) ANSI B16.15 Bronze 250lb. Threaded (NPT)

 

  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

(2 ½” - 10” Valves) ANSI B16.1 Iron 125lb. Flange

Trim:  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

(1 ½” -2” Valves) 316 Stainless Steel

   

(2 ½” - 10” Valves) Bronze

Packing:  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 

 Long-Life Multi-Stack, EPDM Lip Packing for temperatures up to 350°F

Seat Closure:.  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .

 (1 ½” - 2” Valves) Single-Seat ANSI Class IV and Class VI shut-off

   

 (2 ½” - 6” Valves) Single-Seat ANSI Class IV shut-off

   

 (8” - 10” Valves) Double-Seat ANSI Class IV shut-off

Temperature:    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 

(1 ½” -2” Valves) +32ºF to 400ºF

   

(2 ½” - 10” Valves) +32ºF to 350ºF

Содержание 928051-50-VM

Страница 1: ...y control All equipment must have its own certified limit and safety controls required by local codes The installer must verify proper operation and correct any safety problems prior to the installati...

Страница 2: ...ped per the following packing lists Valve package actuator package Valve Bushing Locknut Actuator Actuator Brass Bracket with two hex screws and two nuts Hex Wrench 5 24 VAC Transformer Stem Nut Stem...

Страница 3: ...the valve Remove the Actuator Brass Brackets This should release the Stem Attachment Thread the Stem Attachment to the Valve Stem Make sure that it is tightened against the Stem Nut Mount the Actuato...

Страница 4: ...oating type signal R W B The actuator must be powered using the provided 24 VAC transformer A single transformer can only power a single actuator The transformer is supplied with every complete valve...

Страница 5: ...SENSORS INPUTS ROUTE SENSOR AND AUXILIARY WIRES THROUGH THIS KNOCKOUT ONLY SYS AUX CLOCK OPTION 1 T T Cycle On 5 60m Val 45 Day OD 31 o F SYS 148 o F OUTPUT T T C O R P O R A T I O N R 2 3 4 5 9 10 12...

Страница 6: ...Bronze 88 32 to 300 4 928054 00 VM 170 13 6 22 Flanged Iron Bronze 135 32 to 300 5 928055 00 VM 280 15 5 23 Flanged Iron Bronze 150 32 to 300 6 928056 00 VM 360 17 6 23 Flanged Iron Bronze 191 32 to...

Страница 7: ...ted to the heating system boilers or electrical power system that is required for proper operation of any controls or other equipment installed by Heat timer corporation or any contractor third party...

Страница 8: ...actuator for manual operation Mounting Vertical above center line of valve Feedback Signal 1K ohm Terminals 8 9 10 2 Way Valve Specifications Body 1 2 Valves ANSI B16 15 Bronze 250lb Threaded NPT 2 1...

Отзывы: