Heat-N-Glo Pier-PV-IPI Скачать руководство пользователя страница 15

20

V

= VENT  TERMINAL

X

= AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

     Figure 19.   Vent Termination Minimum Clearances

A

= 12" .......................... clearances above grade, ve ran-

da, porch, deck or balcony

B

= 12" .......................... clearances to window or door

that may be opened, or to per-
manently closed window.

D*

= 18" .......................... vertical clearance to unventilat-

ed soffit or to ventilated soffit lo-
cated above the terminal

E

    *18” min. ................ for vinyl clad soffits and below

electrical service

F

=  9" ........................... clearance to outside corner

G

= 12" .......................... clearance to inside corner

H

= 3 ft. (Canada) ....... not to be installed above a gas

meter/regulator assembly within 3
feet (90cm) horizontally from the
center-line of the regulator

I

= 3 ft. (U.S.A.)

6 ft. (Canada) ........ clearance to gas service regula-

tor vent outlet

J

= 9" (U.S.A.)

12" (Canada) .......... clearance to non-mechanical air

supply inlet to building or the
combustion air inlet to any other
appliance

K

= 3 ft. (U.S.A.)

6 ft. (Canada) .......... clearance to a mechanical

air supply inlet

L** = 7 ft. ........................... clearance above paved side-

walk or a paved driveway lo-
cated on 

public

 property

M*** = 18" ............................ clearance under veranda,

porch, deck or balcony

N

= 12” ............................ non-vinyl sidewalls

12” ............................ vinyl sidewalls

O

= 18” ............................ non-vinyl soffit and overhang

18” ............................ vinyl soffit and overhang

P

= 8 ft.

  ** a vent shall not terminate directly above a sidewalk or paved

driveway which is located between two single family dwellings and
serves both dwellings.

 *** only permitted if veranda, porch, deck or balcony is fully open on a

minimum of 2 sides beneath the floor.

NOTE 1

: On private property where termination is less than 7 feet above

a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed
cap shield is suggested.

NOTE 2

: Termination in an alcove space (spaces open only on one side

and with an overhang) are permitted with the dimensions specified for
vinyl or non-vinyl siding and soffits. 

1

. There must be 3 feet minimum

between termination caps. 

2. 

 All mechanical air intakes within 10 feet

of a termination cap must be a minimum of 3 feet below the termination
cap. 

3.

 All gravity air intakes within 3 feet of a termination cap must be

a minimum of 1 foot below the termination cap.

(See Note 1)

(See Note 1)

S =  6" MIN. ................... clearance from sides of elec-

trical service

T = 36" MIN. .................. clearance above electrical

service

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

    

Q

MIN

     R

MAX

  1 cap

  3 feet

   2 x Q 

ACTUAL

  2 caps

  6 feet

   1 x Q 

ACTUAL

  3 caps

  9 feet

2/3 x Q 

ACTUAL

  4 caps

12 feet

1/2 x Q 

ACTUAL

Q

MIN

 = # termination caps x 3        R

MAX

 = (2 / # termination caps) x Q

ACTUAL

(See Note 5)

(See Note 5)

NOTE 3

: Local codes or regulations may require different

clearances.

NOTE 4: 

Termination caps may be hot. Consider their proximity

to doors or other traffic areas.

NOTE 5: 

Location of the vent termination must not interfere with

access to the electrical service.

WARNING: In the U.S:

 Vent system termination is 

NOT

 permit-

ted in screened porches. You must follow side wall, overhang
and ground clearances as stated in the instructions.

In Canada:

 Vent system termination is 

NOT

 permitted in screened

porches. Vent system termination is permitted in porch areas with
two or more sides open. You must follow all side walls, overhang
and ground clearances as stated in the instructions.

Heat-N-Glo assumes no responsibility for the improper perfor-
mance of the fireplace when the venting system does not meet
these requirements.

D

E

B

L

v

v

v

v

v

v

v

v

B

B

A

H

M

X

J or K

I

A

G

F

U.S.

(3 FT)

B

O

N

P

R

Q

(See Note 2)

Electrical

Service

V

S

V

S

V

T

D*

V

Содержание Pier-PV-IPI

Страница 1: ...E REFERENCE 1 This appliance may be installed in an af termarket permanently located manu factured mobile home where not pro hibited by local codes 2 This appliance is only for use with the type of ga...

Страница 2: ...ERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first...

Страница 3: ...19 Step 4 Positioning Leveling and Securing the Fireplace 22 Step 5 The Gas Control System 22 Step 6 The Gas Supply Line 23 Step 7 Gas Pressure Requirements 23 Step 8 Wiring the Fireplace 24 Step 9 F...

Страница 4: ...riate to the particular installation Refer to the National Fuel Gas Code ANSI Z223 1 NFPA54 current edition The Uniform Mechanical Code current edition and local Building Officials for the options all...

Страница 5: ...ructions will void the own er s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the following actions Installation of a...

Страница 6: ...DOOR TOP STANDOFFS 1 2 13mm 2 43 5 8 1107mm 42 5 8 1081mm 42 1067mm 32 3 4 829mm 21 533mm 32 5 16 820mm 8 1 2 216mm 37 7 16 950mm 17 15 16 455mm 24 610mm 21 533mm 12 304mm 2 ELECTRICAL ACCESS 4 100mm...

Страница 7: ...mm 8 1 2 216mm 24 610mm 2 9 16 64mm 4 1 2 114mm 47 5 8 1208mm 32 3 4 829mm 12 304mm 2 4 100mm 2 ELECTRICAL ACCESS GAS LINE ACCESS 26 5 8 676mm 10 1 2 266mm 4 1 16 102mm 2 4 1 2 114mm 2 4 3 4 121mm 2 5...

Страница 8: ...or after the fireplace is set in place Framing should be positioned to accommo date wall coverings and fireplace facing material The dia gram below shows framing reference dimensions CAUTION MEASURE F...

Страница 9: ...er or heavier Model A B C D PIER PV IPI 42 1 8 42 1 2 23 25 5 8 ST PV IPI 47 5 8 42 1 2 23 26 5 8 Figure 4 Framing Dimensions NOTE DIMENSIONS SHOWN IN INCHES Showscenterof 12 x 12 vent framing holes f...

Страница 10: ...r horizontal vent runs NO OTHER VENTING SYS TEMS OR COMPONENTS MAY BE USED Detailed installation instructions are included with each vent termination kit and should be used in conjunction with this In...

Страница 11: ...IGHT OUT HORIZONTAL VENTING H FT 36 MIN 914 mm 40 MAX 12 2 M 8 900 Bends MAX Figure 7 STRAIGHT UP VERTICAL VENTING V FT 40 MAX 12 2 M 8 900 Bends MAX Figure 8 V H VERTICAL DROP V MAX Run 48 1219 mm 8...

Страница 12: ...as fireplaces to draft properly If the home experiences negative pressure or is likely to experience negative pressure connection to an outside air source is mandatory A 4 inch side collar see Figure...

Страница 13: ...ing 9 9 INTERIOR WALL SHIELD FLEX PIPE For Vertical Runs One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes To install firestops for vertical runs that pass thr...

Страница 14: ...4 REQUIRED NOTE There must be NO INSULATION or other combustibles inside the framed firestop opening WARNING VENTING TERMINALS SHALL NOT BE RECESSED INTO A WALL OR SIDING VENT TERMINATION CLEARANCES...

Страница 15: ...ensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes within 10 feet of a termination cap must be a minimum o...

Страница 16: ...AGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMINA TION CAP IS AT LEAST 20 INCHES FROM A VER TICAL WALL AND 2 FEET BELOW A HORIZONTAL OVERHANG NOTE This also pertains to vertical vent systems in stalled o...

Страница 17: ...t to the floor The diagram below shows how to properly position level and secure the fireplace Figure 22 Proper Positioning Leveling and Securing of a Fireplace Step 5 The Gas Control System WARNING T...

Страница 18: ...t does not penetrate the actual firebox Open the fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe support the co...

Страница 19: ...WHT ORG GRN WHT ON OFF WALLSWITCH BRN BRN BLK WHT BLK WHT BLK WHT BLK TERMINAL BLOCK BULB SOCKET ASSEMBLY 3 ROCKER SWITCH BLK OPTIONAL ELECTRIC EMBER KIT EMBERKIT MS RED BRN BLK BL K WHT RED BRN BLK W...

Страница 20: ...Figures 27 Figure 26 Fan Wiring Diagram Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the factory installed junction box before the fireplace is perman...

Страница 21: ...stible material such as wood can be placed on the top edge and sides of the fireplace Hearth Extensions A hearth extension may be desirable for aesthetic reasons However ANSI or CAN CGA testing standa...

Страница 22: ...el Type PIER PV IPI TEMPERED ST PV IPI TEMPERED Heat N Glo fireplaces manufactured with tempered glass may be installed in hazardous locations such as bathtub enclosures as defined by the CPSC The tem...

Страница 23: ...rts at the rear of the burner Save the remaining ember materials for use during fire place servicing The bag of embers provided is suffi cient for 3 to 5 applications Replace the glass door and a fron...

Страница 24: ...ghting the fireplace double check the unit for possible obstructions that could be blocking the vent terminations or the front grilles Double check for faulty components Any component that is found to...

Страница 25: ...eriodically By Qualified service technician Task Make a visual check of the straight flame sensor rod Use emery cloth to carefully remove any existing film or white deposits Checking Flame Patterns Fl...

Отзывы: