Heat-N-Glo 6000TRS-AU Скачать руководство пользователя страница 25

25

FIGURE 31.

2.4  FAN OPERATION

The accessory fan is wired in series with a speed con-
trol switch and a temperature sensor switch. Set the
speed control to an "ON" position and light the heater.
The temperature sensor switch will automatically start
the fan when the switch warms up—and stop the fan
when it cools down. You can manually stop the fan by
turning the speed control switch to "OFF". See Figure
19 for fan wiring diagram.

3.0  SERVICING AND MAINTENANCE

A

. HEATER SERVICING:

  Frequency of heater  servic-

ing will depend upon use and type of installation.

B.

IMPORTANT:

  TURN OFF GAS BEFORE SERVIC-

ING APPLIANCE.  IT IS RECOMMENDED THAT A
COMPETENT SERVICE TECHNICIAN PERFORM
SERVICE CHECK-UPS AT THE BEGINNING OF
EACH HEATING SEASON.

C. The appliance and flue system should be inspected

before initial use and at least annually by a qualified
field service person.

D. Inspect the external flue cap on a regular basis to

make sure that no debris is interfering with the air
flow.

E. Keep the control compartment, logs, and burner area

surrounding the logs clean by vacuuming or brush-
ing at least twice a year.

CAUTION:

  THE LOGS GET VERY HOT - HANDLE

ONLY WHEN COOL.

WARNING:  DO NOT USE ABRASIVE CLEANERS ON
THE GLASS DOOR ASSEMBLY. DO NOT ATTEMPT
TO CLEAN THE GLASS DOOR WHEN IT IS HOT.

F. The glass door should be cleaned using a house-

hold glass cleaner.

DO NOT

 handle or attempt to

clean the glass when it is 

HOT.

G. In order to properly clean the burner and pilot as-

sembly, turn off the gas to the unit and remove the
logs exposing the burner and pilot assembly.  Clean
all foreign materials from top of burner. Check to
make sure that the burner orifice is clean.

Visually inspect the pilot periodically. Brush or blow
away any dust or linen accumulations. If the pilot ori-
fice is plugged, disassembly may be required to re-
move any foreign materials from the orifice or tubing.
When the appliance is put back in service check burner
flame patterns with Figure 30.

Standing Pilot

3/8"

(9.5mm)

FIGURE 30.

To obtain proper operation, it is imperative that the pi-
lot and main burner flame characteristics are steady,
not lifting or floating.  Typically, the top 3/8-inch at the
pilot generator should be engulfed in the pilot flame
(Figure 31).

Содержание 6000TRS-AU

Страница 1: ...4 USA 1 888 427 3973 392 900D 10 02 INSTALLATION AND OPERATION INSTRUCTIONS This product is covered by one or more of the following patents United States 4 112 913 4 408 594 4 422 426 4 424 792 4 520...

Страница 2: ...nual Report to your dealer any parts dam aged in shipment specifically check glass condition The gas logs and flue system components are in sepa rate packages Read all instructions before starting ins...

Страница 3: ...Installer Testing 21 2 0 OPERATING INSTRUCTIONS 21 2 1 Safety and Lighting Information 23 2 2 Safety Information 23 2 3 Lighting Instructions 24 2 4 Fan Operation 25 3 0 SERVICING AND MAINTENANCE 25 3...

Страница 4: ...r remote control are desired If the heater is to be installed on carpeting or tile or on any combustible material other than wood flooring the heater should be installed on a metal or wood panel that...

Страница 5: ...FIGURE 2 Heater Dimensions Locations and Space Requirements 1 1 Locating the Heater The diagram See figure 2 shows space and clearance requirements for locating a heater within a room Minimum Clearan...

Страница 6: ...2 1066mm 978mm 559mm 6837mm 1054mm FIGURE3 Framing Dimensions For minimum clearances see the direct vent termination clearance diagrams on page 7 1 2 Framing the Heater Framing can be built before or...

Страница 7: ...ut 300 Appliances over 50 MJ h input 500 b From the ground or above a balcony 300 c From a return wall or external corner 500 d From a gas meter M 1000 e From an electricity meter or fuse box P 500 f...

Страница 8: ...UE SYSTEM Figure 5 shows straight up vertical flue system approved for use on this model STRAIGHT OUT HORIZONTAL FLUE SYSTEM Figure 6 shows straight out horizontal flue systems ap proved for use on th...

Страница 9: ...M V H V FT H FT 1 MIN 305mm 4 MAX 1 22m 2 MIN 610mm 8 MAX 2 4m 3 MIN 914mm 12 MAX 3 7m 4 MIN 1 22m 16 MAX 4 9m V H 24 MAX 7 3m H 8 MAX 2 4m FIGURE8 Flueing with One 90 Elbow NOTE If a 90o elbow is fi...

Страница 10: ...2 48m 3 MIN 914mm 4 MAX 1 22m 12 MAX 3 72m 4 MIN 1 22m 6 MAX 1 8m 16 MAX 4 9m 20 MAX 6 1m 6 MAX 1 8m 16 MAX 4 9m H1 V H FIGURE 10 Flueing with Two 90 Elbows V FT H H1 FT 1 MIN 305mm 4 MAX 1 22m 2 MIN...

Страница 11: ...86 m 12 MAX 3 6 m 4 MIN 1 22 m 8 MAX 2 48 m 16 MAX 4 9 m 8 MAX 2 48 m 16 MAX 4 9 m NOTE V V MAX 36 10 9 m FLUEING WITH THREE 3 90 ELBOWS FIGURE11 Flueing with three 90 elbows V H H H1 H2 1 MIN 305 mm...

Страница 12: ...3 MIN 914mm 12 MAX 3 7m 4 MIN 1 22m 16 MAX 4 9m NOTE H H1 16 MAX 4 9m V V1 H H1 36 MAX 10 9m V FT H H1 FT 1 MIN 305mm 4 MAX 1 22m 2 MIN 610mm 8 MAX 2 4m 3 MIN 914mm 12 MAX 3 7m 4 MIN 1 22m 16 MAX 4 9m...

Страница 13: ...TOVECEMENTMUSTBEPLACED AROUNDTHEINNERPIPEHEATERSTARTING COLLARBEFOREATTACHINGTHEFIRSTFLUE COMPONENT FAILURE TO SEAL THIS JOINT MAY CAUSE THE HEATER TO OPERATE IM PROPERLY SEEFIGURE14 WARNING ENSURETHA...

Страница 14: ...er of the hole is one 1 inch 25mm above the center of the horizontal flue pipe Position the firestops on both sides of the hole pre viously cut and secure the firestops with nails or screws The heat s...

Страница 15: ...hole FIGURE 20 Attic Firestop C Flue Termination For Horizontal Terminations To attach and secure the termination to the last section of horizontal flue Rotate and interlock the ends as described at t...

Страница 16: ...accordingly Cover the opening of the installed flue pipes Cut and frame the roof hole Use framing lumber the same size as the roof rafters and install the frame securely Flashing anchored to the frame...

Страница 17: ...BRN BRN BLUE GRD BLUE JUNCTION BOX DETAIL FAN TEMPERATURE SENSOR SWITCH FAN SPEED CONTROL JUNCTION BOX 1 5 FAN These heaters have a factory installed Fan Electrical Junction Boxes variable speed Rheo...

Страница 18: ...EALED A 150 C MINIMUM SEALANT MATERIAL MUST BE USED THESE JOINTS ARE NOT REQUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 150 C MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO THE FIRE...

Страница 19: ...V382 701 Locate log 1 on grate with knotches and push log towards rear of firebox LOG 2 SRV382 702 Locate log 2 on grate with knotches Slide left end of log forward and right side back against tab Log...

Страница 20: ...t the right end on top of log 2 LOG 5 SRV382 705 Place bottom of log 5 between the 4th and 5th grate bars rest the top onto log 1 LOG 6 SRV438 724 Place the Y shaped part of log 6 over the 3rd grate b...

Страница 21: ...building WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL The control system for this model is a millivolt type It consists of a gas control valve variable regulator a stand ing pilot assembly a ther...

Страница 22: ...FORE THE UNIT CAN BE PLACED INTO SAFE OP ERATION DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDER WATER IMMEDIATELY CALL AQUALIFIEDSERVICETECHNICIANTOINSPECT THE UNIT AND TO REPLACEANY PART OF TH...

Страница 23: ...has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the gas control system which has been under water 2 1 SAFETY LIGHTING INFORMATI...

Страница 24: ...houldnotrequireaccessingforlighting purposes The pilot is located inside the combustionchamber THERMOPILE PILOTBURNER 6 To put the control in the pilot position turn the control knob counter clockwise...

Страница 25: ...and burner area surrounding the logs clean by vacuuming or brush ing at least twice a year CAUTION THE LOGS GET VERY HOT HANDLE ONLY WHEN COOL WARNING DO NOT USEABRASIVE CLEANERS ON THE GLASS DOOR AS...

Страница 26: ...m the underside of the thermopile The thermopile can then be sepa rated from the pilot bracket Unscrew the pilot assembly bracket and remove NOTE When removing the pilot assembly carefully pull the el...

Страница 27: ...gnitor 1 Using a match light pilot If pi lot lights turn off pilot and trig ger the red or black button again If pilot lights an improper gas air mixture caused the bad light ing and a longer purge pe...

Страница 28: ...he micro switch and connect to terminal TP on the gas valve Turn green knob to pilot position depress and light pilot light If meter reading is greater than 325 m v after 30 seconds the pilot generato...

Страница 29: ...llow for igni tion or the heater continues to shut off disconnect the limit switch wire from the gas valve and repeat the lighting instruc tions If the pilot and burner re main lit after the heater wa...

Страница 30: ...debris or blockage 1 Adjust the log set so that the flame does not impinge on it 1 Adjust the air shutter at the base of the burner 1 Inspect the opening at the base of the burner It is imperative th...

Страница 31: ...nt wholesale price defective electrical or manual components optional components or accessories and glass panels not including glass panels broken during misuse or careless handling HEAT N GLO shall n...

Отзывы: