Step 1
Identify the piping connections on the panel. You will need 2x 30mm, or large adjustable or
smooth jaw pipe wrenches to tighten the fittings.
Step 2
Ensure that the panel is mounted in the correct position
Step 3
Connect the 2 adapters to the supply and return piping on the panel, using the supplied
washers. Do not overtighten the panel connections, as this will damage the rubber washers.
Step 4
Attach the PEX tubing to the manifold connection using #77000 series connectors (not
included).
Brass Insert with
O-ring
Split Ring Ferrule
Cone Ring
Plastic Nut
Step 5
Remove the plastic manifold nut.
Step 6
Lubricate the inside of the manifold port with silicone o-ring lubricant (#79952).
Step 7
Cut the PEX tubing at a 90º angle.
Step 8
Place the plastic manifold nut, cone ring, and split ring ferrule onto the PEX tubing (the
bevelled edge of the cone ring must be facing the split ring ferrule).
Step 9
Method A
a)
Push the brass insert onto the PEX tubing as far as it will go.
b)
Push the PEX tubing with the brass insert as far as it will go into the manifold. Ensure that
the o-ring is clean and take care not to pinch it.
Step 10
Method B
a)
Push brass insert as far as it will go into the manifold. Ensure the o-ring is clean and take
care not pinch it.
b)
Push PEX tubing onto the brass insert as far as it will go.
Step 11
Use the multi-pupose wrench to tighten the nut.
90°
Cut PEX tubing at a 90º angle to
ensure proper connection
Piping Hookup