Vitae 5Kw & 8Kw Landscape V1 

– 7-6-17 

 

 

Ventilation

    

Any Room or space containing an appliance should have permanent ventilation opening of free area of 
550mm Sq per kw of rated output but in no case less than 6500mm sq where air permeability is greater than 
5.0m3, or 65550mmsq per kw of rated output above 5 Kw where the air permeability is less than 
5.0m3.

 

"Note:  If there is another appliance using air fitted in the same or adjacent room, it will be necessary 

to provide an additional air supply."  

Ref Building Reg’s Document J 

 
There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit 
fumes into the room. 

 

4.0

 

Installation Information 

 
Chimney 

The chimney height and the position of the chimney terminal should conform to 

Building Regulations

. Flue 

heights should be high enough to ensure sufficient draught to clear the products of combustion. Check that 
the chimney is in good condition, dry, free from cracks and obstructions. The diameter of the flue should not 
be less than 125mm and not more than 200mm. If any of these requirements are not met, the chimney should 
be lined by a suitable method. The chimney must be swept before connection to the stove. 
 
Where the chimney is believed to have previously served an open fire installation, it is possible that the 
higher flue gas temperature from the stove may loosen deposits that were previously firmly adhered, with 
the consequent risk of flue blockage. It is therefore recommended that the chimney be swept a second time 
within a month of regular use after installation. 
If you have any doubts about the suitability of your chimney, consult your local dealer/stockist or chimney 
specialist. If there is no existing chimney then either a solid fuel compatible prefabricated block chimney or 
a twin-walled insulated stainless steel flue to BS 1856-1 can be used. These chimneys must be fitted in 
accordance with the manufacturer’s instructions and also please refer to the current issues of British 
Standards BS EN 15287-1:2007 for design, installation and commissioning of chimneys. 
 

Flue Draught  

A flue draught of minimum 1.2mm to a maximum 2.5mm water gauge (12 to 25 Pascals) is required for 
satisfactory appliance performance. The flue draught should be checked under fire at high output and, if it 
exceeds the recommended maximum, a draught stabiliser must be fitted so that the rate of burning can be 
controlled to prevent over-firing. 
 

Connection to the Chimney 

This appliance is 

not

 suitable for use in a shared flue. This appliance requires a direct flue connection to the 

spigot. If practical, an existing fireplace opening can be bricked up or sealed with a register plate and a short 
length  of  flue  pipe  of  a  minimum  125mm  internal  diameter  may  then  be  used  to  connect  the  stove  to  the 
register  plate  in  the  chimney.  This  flue  pipe  should  conform  to  Building  Regulations.  The  stove  must  be 
insulated and properly fitted into the fireplace opening by back filling with 6:1 ratio vermiculite & cement 
mixture using minimal water through the top of the fireplace or flue spigot opening. The surface should be 
finished using 1:1:8 mix of cement, lime and sand. The connecting pipe is fitted with the spigot pushed up 
from 

inside

 the stove and rotated onto its keyhole slots to join to the pipe. Ensure that the pipe end is no closer 

than 76mm to the side or rear chimney walls. 
 
If necessary a hole must be opened up into the flue way above the fireplace in order to fit the appliance to 
the flue correctly. Please consult HETAS recommended fitting methods if in doubt. It is 

essential

 that all 

connections between the stove and chimney-flue are sealed and made airtight with sealing rope, clamping 
rings and/or fire cement or heat resisting cement where required. 
 

Содержание Vitae 5Kw

Страница 1: ...he user in the correct use of the appliance and operation of controls Important This product must be installed by a suitably qualified installer Heat Design 30 60 Hawthorn Road Western Industrial Esta...

Страница 2: ...nt Safety Information 4 4 2 Health Safety Precautions 4 4 3 Site Requirements 6 4 4 Fitting the Stove 6 5 Technical Data 10 6 Operating Instructions 11 6 1 Air controls 11 6 2 Cleaning 11 6 3 Fuels 12...

Страница 3: ...through the front door Then remove the two side firebricks and the two rear firebricks Handle store very carefully to one side where they will not get broken 2 2 Now lift and remove the riddle grate...

Страница 4: ...on Date of Installation Model Number Vitae 5Kw 8Kw Landscape Serial Number Fitter Plumber Name Address Telephone Number Commissioning Checklist Installer to complete and sign off Stove correctly flued...

Страница 5: ...specialist guidance and use appropriate protective equipment Metal Parts When installing or servicing this stove proper care should be taken to avoid the possibility of personal injury Important Chimn...

Страница 6: ...ck chimney or a twin walled insulated stainless steel flue to BS 1856 1 can be used These chimneys must be fitted in accordance with the manufacturer s instructions and also please refer to the curren...

Страница 7: ...n or partially over it The appliance must be installed on a floor with adequate load bearing capacity If the existing construction does not meet this requirement suitable measures e g load distributin...

Страница 8: ...iii in reverse B Installing a stove into a chimney that is already lined see Fig 4 or Fig 5 i The integrity of the chimney must be thoroughly inspected and verified by a suitably qualified professiona...

Страница 9: ...m the stove up the chimney and emitted safely to atmosphere Notice plate should be filled out with indelible ink and located either A next to the electricity consumer unit B next to a gas consumer uni...

Страница 10: ...9 Vitae 5Kw 8Kw Landscape V1 7 6 17...

Страница 11: ...Wood Nominal Heat Output kW 4 7 8 1 Efficiency 81 2 82 9 CO 13 O2 0 06 0 09 DUST 13 O2 mg Nm 15 10 Flue Temp C 256 287 Flue Outlet Size Inch 5 5 Fuel Consumption kg hr 1 33 2 0 Max Log Length 380mm 58...

Страница 12: ...ustion thereby improving efficiency increasing heat output and decreasing unwanted atmospheric emissions At certain stages of burning you will notice jets of flame emerging near the air holes to the r...

Страница 13: ...f burning problems with wood stoves is due to excessively damp wood Wood can appear perfectly dry on the outside but still contain 40 50 water on the inside A moisture meter can be purchased from some...

Страница 14: ...nufacturers recommended replacement parts on the appliance 6 10 Seasonal Use Remove the baffle and inspect the inside of the stove and the flue ways and ensure they are 100 clear after a period of dis...

Страница 15: ...oes persist then the following immediate action should be taken 1 Open doors and windows to ventilate room and all people then to leave the premises 2 Let the fire out 3 Check for flue or chimney bloc...

Страница 16: ...engineer attends any stove problem that is not related to product failure 6 Where can I get spare parts Your local Vitae Stove retailer will be pleased to supply spare parts and to provide any other i...

Страница 17: ...A 44 Door Hinge Pin Y1HDCD51C 06 Side Plate Left fireboard Y1HDLD06A 45 Rope Flat 30mm Y1VTL05D53A 07 Side Plate Right fireboard Y1HDLD07A 46 Rope 14mm for Door Length 1 85 meter Y1VTL05D54A 16 Baffle...

Страница 18: ...eboard Y1HDLD06A 45 Rope Flat 30mm Y1VTL08D53A 07 Side Plate Right fireboard Y1HDLD07A 46 Rope 14mm for Door Length 2 26 meter Y1VTL08D54A 16 Baffle Plate Y1VTL08D19A 48 Rope Flat 2mm x 8mm Y1HD56A 17...

Отзывы: