33
9.2.2 Indoor / outdoor unit’s communication error
No
Reconnect and retest
No
Yes
Yes
E1 after 8 m
inutes
Check the wiring between indoor and outdoor
unit. Are the wires connected correctly?
No
Is all the wiring between terminal and
Indoor PCB connected properly?
Is all the wiring to the Outdoor PCB
connected correctly?
Possible
electromagnetic
interference.
Reconnect and retest
Reconnect and retest
Yes
-24V<Vs<+24V
DC
? (Vs is the
voltage between S and N).
Yes
No
Change the Indoor PCB. If the AC still
displays E1, Change the outdoor PCB.
Change the outdoor PCB. If the AC still
displays E1, Change the indoor PCB.
Return to normal
Turn off the power supply, after 1 minute,
connect the power supply and turn on
the unit.