Service Manual
VMH 30, 36 SerieS
Heat Controller
20
℃
20
22
28
30
40
38
45
43
Fmax=F4
Fmax=F7
Fmax=F8
Fmax=F6
Fmax=F3
T4
℃
-1.0
-0.5
0.5
1.0
1.5
2.0
2.5
3.0
3.5
A
B
C
D
E
F
G
H
T1-TS
8.4.2 Cooling Mode
8.4.2.1 Compressor running rules:
The operation frequency of compressor after starting submits to the following rule.
If users switch on AC by remote controller, the compressor will run at the Fmax frequency for 7
minutes according to outdoor ambient temp. During the 7 minutes, frequency limitation is active.
7 minutes later, the compressor running frequency will be controlled as below:
While
Temp. zone
A
B
C
D
E
F
G
Frequency
F8
F8
F7
F6
F5
F3
F1
T1-TS
(3.5)
(3.0)
(2.5)
(2.0)
(1.5)
(1.0)
(0.5)
(-0.5)
(-1.0)
T4 °F
113°
109°
104°
100°
86°
82°
72°
68°
T4 °C
(45)
(43)
(40)
(38)
(30)
(28)
(22)
(20)
T1-TS °F
38°
37.5°
36.5°
35.5°
34.5°
3
4
°
33°
31°
30°