6.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional tightening
mm
inch
N.cm
N.cm
Ф6.35
1/4
1500
1600
Ф9.52
3/8
2500
2600
Ф12.7
1/2
3500
3700
Ф16
5/8
4500
4700
Ф19
3/4
6500
6700
6.2 Power wiring & connecting cables
Power Wiring
Consult local building codes, NEC (National Electric Code) or CEC (Canadian Electric Code)
for special requirements.
Connecting Cables: Voltage drop on the connecting cable should be kept to a minimum. The
operating voltage will vary between -24V to 24V DC.
Use cable:
Model Size
Power Source
Min. Ckt Amp
Max. Fuse/CB Amp
AWG (min.)
Connecting Cable
(outdoor to indoor)
30K
208/230V-60-1
16.0/25.0
14/4 Copper
Stranded
36K
20.0/30.0