Engineering Design Guide 

HBH SERIES 

Heat Controller, Inc.

23

HBH Series 60Hz

Engineering Specifi cations – Page 2

Fan and Motor Assembly:

All units shall have belt-driven single centrifugal fan. Fan motor shall be permanently lubricated with thermal overload protection. Units 
supplied without permanently lubricated motors must provide external oilers for easy service. The fan and motor assembly must be 
capable of overcoming the external static pressures as shown on the schedule. Airfl ow/Static pressure rating of the unit shall be based 
on a wet coil and a clean fi lter in place. Ratings based on a dry coil and/or no fi lter, or on an ESP less than 0.25” (6.35 mm w.g.) shall 
NOT be acceptable.

Option: Various blower drive packages for selectable static pressure/airfl ow.

Refrigerant Circuit:

All units shall contain R-410A sealed refrigerant circuit including a high effi ciency scroll compressor designed for heat pump operation, 
a thermostatic expansion valve for refrigerant metering, an enhanced corrugated aluminum lanced fi n and rifl ed copper tube refrigerant 
to air heat exchanger, reversing valve, coaxial (tube in tube) refrigerant to water heat exchanger, and safety controls including a high 
pressure switch, low pressure switch (loss of charge), water coil low temperature sensor, and air coil low temperature sensor. Access 
fi ttings shall be factory installed on high and low pressure refrigerant lines to facilitate fi eld service. Activation of any safety device
shall prevent compressor operation via a microprocessor lockout circuit. The lockout circuit shall be reset at the thermostat or at the 
contractor supplied disconnect switch. Units that cannot be reset at the thermostat shall not be acceptable.

Hermetic compressors shall be internally sprung. The scroll compressors shall have a dual level vibration isolation system. The com-
pressor(s) will be mounted on specially engineered sound-tested EPDM vibration isolation grommets to a large heavy gauge compres-
sor mounting plate, which is then isolated from the cabinet base with rubber grommets for maximized vibration attenuation. Compressor 
shall have thermal overload protection. Compressor shall be located in an insulated compartment isolated from air stream to minimize 
sound transmission.

Refrigerant to air heat exchangers shall utilize enhanced corrugated lanced aluminum fi ns and rifl ed copper tube construction rated to 
withstand 625 PSIG (4309 kPa) refrigerant working pressure. Refrigerant to water heat exchangers shall be of copper inner water tube 
and steel refrigerant outer tube design, rated to withstand 625 PSIG (4309 kPa) working refrigerant pressure and 500 PSIG (3445 kPa) 
working water pressure. The refrigerant to water heat exchanger shall be “electro-coated” with a low cure cathodic epoxy material a 
minimum of 0.4 mils thick (0.4 – 1.5 mils range) on all surfaces. The black colored coating shall provide a minimum of 1000 hours salt 
spray protection per ASTM B117-97 on all external steel and copper tubing. The material shall be formulated without the inclusion of 
any heavy metals and shall exhibit a pencil hardness of 2H (ASTM D3363-92A), crosshatch adhesion of 4B-5B (ASTM D3359-95), and 
impact resistance of 160 in-lbs (184 kg-cm) direct (ASTM D2794-93).

Refrigerant metering shall be accomplished by thermostatic expansion valve only. Expansion valves shall be dual port balanced type 
with external equalizer for optimum refrigerant metering. Units shall be designed and tested for operating ranges of entering water tem-
peratures from 20° to 120°F (-6.7° to 48.9°C). Reversing valve shall be four-way solenoid activated refrigerant valve, which shall default 
to heating mode should the solenoid fail to function. If the reversing valve solenoid defaults to cooling mode, an additional low tempera-
ture thermostat must be provided to prevent over-cooling an already cold room.

Option: The unit shall be supplied with cupro-nickel coaxial water to refrigerant heat exchanger. 

Option: The unit shall be supplied with extended range Insulation option, which adds closed cell insulation to internal water lines, and 
provides insulation on suction side refrigeration tubing including refrigerant to water heat exchanger.

Option:

 The refrigerant to air heat exchanger shall be “electro-coated” with a low cure cathodic epoxy material a minimum of 0.4 

mils thick (0.4 – 1.5 mils range) on all surfaces. The black colored coating shall provide a minimum of 1000 hours salt spray  protection 
per ASTM B117-97 on all galvanized end plates and copper tubing, and a minimum of 2000 hours of salt spray on all aluminum fi ns. 
The material shall be formulated without the inclusion of any heavy metals and shall exhibit a pencil hardness
of 2H (ASTM D3363-92A), crosshatch adhesion of 4B-5B (ASTM D3359-95), and impact resistance of 160 in-lbs (184 kg-cm) 
direct (ASTM D2794-93). 

Drain Pan:

The drain pan shall be constructed of galvanized steel and have a powder coat paint application to further inhibit corrosion. This cor-
rosion protection system shall meet the stringent 1000 hour salt spray test per ASTM B117. If plastic type material is used, it must be 
HDPE (High Density Polyethylene) to avoid thermal cycling shock stress failure over the lifetime of the unit. Drain pan shall be fully
insulated. Drain outlet shall be located at pan as to allow complete and unobstructed drainage of condensate. Drain pan hose assem-
bly can be connected to either side, drain outlet to be 1”FPT fi tting. Choice of drain connection to only one side will not be accepted. 

Содержание HBH Series

Страница 1: ...Heat Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com ENGINEERING DESIGN GUIDE Commercial Horizontal Packaged Water Source Heat Pump HBH Series 6 10 Tons...

Страница 2: ...Data HBH120 10 Performance Data Correction Tables 11 Antifreeze Correction Table 12 Blower Performance Data HBH072 Standard Unit 13 Blower Performance Data HBH096 Standard Unit 14 15 Blower Performanc...

Страница 3: ...or desuperheater capacity Mbtuh FPT female pipe thread KW total power unit input kilowatts LAT leaving air temperature F LC latent cooling capacity BTUH LWT leaving water temperature F MBTUH 1000 BTU...

Страница 4: ...d assess the selection If the units selected are not within 10 of the load calculations then review what effect changing the GPM water temperature and or air flow and air temperature would have on the...

Страница 5: ...n horizontal units Cabinetry Compact design galvanized steel construction FPT water connections high and low voltage knockouts filter and filter brackets All horizontal units have field convertible di...

Страница 6: ...for AHRI is 3 0 turns open Note 3 All HBH120 ratings 4000CFM 1888 l s w 30GPM 1 89 l s Sheave setting for AHRI is 3 0 turns open Note 4 Cooling capacities based upon 80 6 F DB 66 2 F WB entering air t...

Страница 7: ...cutout due to the activation of the Low Temperature Protection JW3 should never be clipped for standard range equipment or systems without antifreeze Example At 50 F EWT Entering Water Temperature an...

Страница 8: ...0 3 9 9 1 73 5 54 7 5 2 91 2 14 1 106 7 5 9 86 5 109 1 5 3 85 10 0 0 4 0 8 67 1 52 1 6 0 87 7 11 2 103 7 5 8 83 8 107 9 5 2 15 0 1 9 4 4 69 8 53 3 5 7 89 2 12 4 108 0 5 9 87 8 109 6 5 3 20 0 3 9 8 9 7...

Страница 9: ...108 4 5 1 24 0 6 3 14 5 99 7 73 1 6 9 123 2 14 5 143 5 8 09 115 9 109 4 5 2 85 12 0 1 1 2 7 92 3 70 0 8 0 119 6 11 6 138 3 7 98 111 1 107 9 5 1 18 0 3 4 7 7 95 7 71 4 7 5 121 3 12 8 145 3 8 13 117 5 1...

Страница 10: ...4 8 30 0 9 4 21 7 126 9 91 0 8 8 157 1 14 4 186 9 11 2 148 6 111 2 4 9 85 15 0 2 0 4 6 116 4 86 5 10 2 151 2 11 5 179 5 11 0 141 9 109 5 4 8 22 5 5 1 11 9 121 1 88 5 9 6 153 8 12 7 189 4 11 3 151 0 1...

Страница 11: ...ier Entering DB F Power Heat of Rejection 60 65 70 75 80 80 6 85 90 95 50 0 7335 0 8825 0 9782 0 7834 55 0 8063 0 6757 0 8842 1 1119 0 9836 0 8424 60 0 8830 0 6734 0 8817 1 0918 0 9900 0 9301 65 0 977...

Страница 12: ...989 0 997 1 070 15 0 986 0 986 1 009 0 968 0 990 1 210 25 0 978 0 978 1 014 0 947 0 983 1 360 Methanol 5 0 995 0 995 1 002 0 989 0 997 1 070 15 0 990 0 990 1 007 0 968 0 990 1 160 25 0 982 0 982 1 012...

Страница 13: ...5 4 3 5 3 2 5 2 1 5 2500 BHP 0 52 0 57 0 61 0 66 0 72 0 78 0 83 0 89 0 94 1 00 1 03 1 08 1 14 1 20 1 25 1 31 Sheave Mtr B B A A A A A A C E E E E E E E RPM 620 660 700 740 780 815 850 885 920 950 985...

Страница 14: ...920 950 985 1015 1045 1075 1100 1130 Turns Open 4 3 2 5 1 5 5 5 5 4 5 3 5 3 2 5 2 1 5 1 4 3 5 3 2700 BHP 0 60 0 65 0 70 0 75 0 80 0 86 0 91 0 97 1 02 1 08 1 14 1 20 1 26 1 32 1 38 1 44 Sheave Mtr B B...

Страница 15: ...1 1 47 1 53 1 59 1 68 1 75 1 83 1 90 1 96 2 02 2 08 Sheave Mtr A A A A A A A A A A C C C C E E RPM 765 800 835 870 900 930 960 990 1015 1045 1070 1100 1125 1150 1175 1200 Turns Open 6 5 4 5 4 3 5 3 2...

Страница 16: ...31 1 37 1 43 1 49 1 55 1 62 1 68 1 75 1 81 1 88 1 95 Sheave Mtr B B B B A A A A A A A A A A A C RPM 740 770 805 840 875 905 935 965 995 1020 1050 1075 1105 1130 1155 1180 Turns Open 4 3 2 5 2 6 5 5 5...

Страница 17: ...ve Mtr A A A A A A A A D E E E RPM 970 995 1020 1045 1070 1100 1125 1145 1170 1195 1215 1240 Turns Open 4 5 4 3 5 3 2 5 2 1 5 1 5 1 3 5 3 2 5 4600 BHP 2 39 2 45 2 54 2 63 2 72 2 83 2 92 3 00 3 10 3 18...

Страница 18: ...Motor Quantity 1 Standard Motor hp kW 1 0 75 2 1 49 3 2 24 Large Motor hp kW 2 1 49 3 2 24 5 3 73 Blower No of Blowers 1 Blower Wheel Size D x W in cm 12 x 12 30 48 x 30 48 Water Connection Size FPT...

Страница 19: ...LEFT VIEW AIR COIL SIDE LEFT RETURN END DISCHARGE CBP EAP BSP CAP CAP FRONT E D F G CAP CBP CAP EAP BSP FRONT FRONT CONTROL BOX PLAN VIEW TOP V S U RIGHT RETURN RIGHT VIEW AIR COIL SIDE RIGHT RETURN E...

Страница 20: ...8 18 3 N A N A 20 HBH160 H 208 3 60 197 254 A B C 2 23 2 164 0 8 5 54 9 60 7 5 600 80 H 208 3 60 197 254 D E 2 23 2 164 0 13 8 60 2 66 0 5 600 80 F 460 3 60 414 506 A B C 2 11 2 75 0 4 1 26 5 29 3 N...

Страница 21: ...EQFGU QT 8 QRGTCVKQP FKUEQPPGEV 4 NGCF CV QT 8 QRGTCVKQP FKUEQPPGEV 8 1 NGCF CV CPF CVVCEJ 40 NGCF VQ PUWNCVG QRGP GPF QH 8 1 NGCF 5WHHKZ FGUKIPCVGU CUUQEKCVKQP YKVJ GCF EQORTGUUQT 5WHHKZ YKVJ CI EQOR...

Страница 22: ...g m3 foil backed fiber insulation for ease of cleaning Insulation placement shall be designed in a manner that will eliminate any exposed edges to prevent the introduction of glass fibers into the air...

Страница 23: ...Pa working water pressure The refrigerant to water heat exchanger shall be electro coated with a low cure cathodic epoxy material a minimum of 0 4 mils thick 0 4 1 5 mils range on all surfaces The bla...

Страница 24: ...t 5 minutes after trip if the fault has cleared If a fault occurs 3 times sequentially without thermostat meeting temperature then lockout requiring manual reset will occur j Ability to defeat time de...

Страница 25: ...h memory stop and PT port c Y strainer with blowdown valve bronze material FPT connections d Motorized water valve slow acting 24v FPT connections Hose Kit Assemblies The following assemblies ship wit...

Страница 26: ...OOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQF...

Отзывы: