Engineering Design Guide 

HBH SERIES 

Heat Controller, Inc.

11

HBH Performance Data – Correction Tables

Air Flow Correction Table

Entering Air Correction Table

Percent 

of Rated 

Airfl ow

Total 

Capacity

Sensible

Power

Heat of 

Rejection

Heating 

Capacity

Power

Heat of 

Extraction

75%

0.962

0.869

0.947

0.959

0.959

1.039

0.962

81%

0.975

0.902

0.960

0.972

0.970

1.024

0.973

88%

0.988

0.934

0.972

0.984

0.981

1.009

0.985

94%

0.994

0.967

0.986

0.992

0.990

1.004

0.992

100%

1.000

1.000

1.000

1.000

1.000

1.000

1.000

106%

1.007

1.028

1.014

1.009

1.010

1.000

1.005

113%

1.014

1.056

1.028

1.017

1.020

1.001

1.010

119%

1.019

1.083

1.046

1.024

1.036

1.008

1.013

125%

1.023

1.109

1.063

1.031

1.051

1.015

1.016

Entering

Air WB°F

Total

Capacity

Sensible Cooling Capacity Multiplier - Entering DB °F

Power

Heat of

Rejection

60

65

70

75

80

80.6

85

90

95

50

0.7335

0.8825

*

*

*

*

*

*

*

*

0.9782

0.7834

55

0.8063

0.6757

0.8842

1.1119

*

*

*

*

*

*

0.9836

0.8424

60

0.8830

0.6734

0.8817

1.0918

*

*

*

*

*

0.9900

0.9301

65

0.9774

0.6682

0.8764

1.0885

1.1136

1.2949

*

*

0.9973

0.9981

66.2

0.9851

0.6177

0.8243

1.0357

1.0612

1.2452

*

*

0.9987

0.9879

67

1.0000

0.5842

0.7897

1.0000

1.0262

1.2119

*

*

1.0000

1.0000

70

1.0426

0.6609

0.8688

0.8941

1.0811

1.2916

*

1.0043

1.0420

75

1.1386

0.6517

0.6517

0.8594

1.0695

1.2838

1.0118

1.1128

* = Sensible capacity equals total capacity
AHRI/ISO/ASHRAE 13256-1 uses entering air conditions of Cooling - 80.6°F DB/66.2°F WB, 1
and Heating - 68°F DB/59°F WB entering air temperature

Entering 

Air 

DB ºF

Heating 

Capacity

Power

Heat of 

Extraction

50

1.040

0.839

1.101

55

1.030

0.883

1.075

60

1.018

0.920

1.053

65

1.008

0.960

1.026

68

1.001

0.984

1.011

70

1.000

1.000

1.000

75

0.978

1.038

0.979

80

0.968

1.091

0.943

HBH072-120 Entering Air Correction Table Cooling

Содержание HBH Series

Страница 1: ...Heat Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com ENGINEERING DESIGN GUIDE Commercial Horizontal Packaged Water Source Heat Pump HBH Series 6 10 Tons...

Страница 2: ...Data HBH120 10 Performance Data Correction Tables 11 Antifreeze Correction Table 12 Blower Performance Data HBH072 Standard Unit 13 Blower Performance Data HBH096 Standard Unit 14 15 Blower Performanc...

Страница 3: ...or desuperheater capacity Mbtuh FPT female pipe thread KW total power unit input kilowatts LAT leaving air temperature F LC latent cooling capacity BTUH LWT leaving water temperature F MBTUH 1000 BTU...

Страница 4: ...d assess the selection If the units selected are not within 10 of the load calculations then review what effect changing the GPM water temperature and or air flow and air temperature would have on the...

Страница 5: ...n horizontal units Cabinetry Compact design galvanized steel construction FPT water connections high and low voltage knockouts filter and filter brackets All horizontal units have field convertible di...

Страница 6: ...for AHRI is 3 0 turns open Note 3 All HBH120 ratings 4000CFM 1888 l s w 30GPM 1 89 l s Sheave setting for AHRI is 3 0 turns open Note 4 Cooling capacities based upon 80 6 F DB 66 2 F WB entering air t...

Страница 7: ...cutout due to the activation of the Low Temperature Protection JW3 should never be clipped for standard range equipment or systems without antifreeze Example At 50 F EWT Entering Water Temperature an...

Страница 8: ...0 3 9 9 1 73 5 54 7 5 2 91 2 14 1 106 7 5 9 86 5 109 1 5 3 85 10 0 0 4 0 8 67 1 52 1 6 0 87 7 11 2 103 7 5 8 83 8 107 9 5 2 15 0 1 9 4 4 69 8 53 3 5 7 89 2 12 4 108 0 5 9 87 8 109 6 5 3 20 0 3 9 8 9 7...

Страница 9: ...108 4 5 1 24 0 6 3 14 5 99 7 73 1 6 9 123 2 14 5 143 5 8 09 115 9 109 4 5 2 85 12 0 1 1 2 7 92 3 70 0 8 0 119 6 11 6 138 3 7 98 111 1 107 9 5 1 18 0 3 4 7 7 95 7 71 4 7 5 121 3 12 8 145 3 8 13 117 5 1...

Страница 10: ...4 8 30 0 9 4 21 7 126 9 91 0 8 8 157 1 14 4 186 9 11 2 148 6 111 2 4 9 85 15 0 2 0 4 6 116 4 86 5 10 2 151 2 11 5 179 5 11 0 141 9 109 5 4 8 22 5 5 1 11 9 121 1 88 5 9 6 153 8 12 7 189 4 11 3 151 0 1...

Страница 11: ...ier Entering DB F Power Heat of Rejection 60 65 70 75 80 80 6 85 90 95 50 0 7335 0 8825 0 9782 0 7834 55 0 8063 0 6757 0 8842 1 1119 0 9836 0 8424 60 0 8830 0 6734 0 8817 1 0918 0 9900 0 9301 65 0 977...

Страница 12: ...989 0 997 1 070 15 0 986 0 986 1 009 0 968 0 990 1 210 25 0 978 0 978 1 014 0 947 0 983 1 360 Methanol 5 0 995 0 995 1 002 0 989 0 997 1 070 15 0 990 0 990 1 007 0 968 0 990 1 160 25 0 982 0 982 1 012...

Страница 13: ...5 4 3 5 3 2 5 2 1 5 2500 BHP 0 52 0 57 0 61 0 66 0 72 0 78 0 83 0 89 0 94 1 00 1 03 1 08 1 14 1 20 1 25 1 31 Sheave Mtr B B A A A A A A C E E E E E E E RPM 620 660 700 740 780 815 850 885 920 950 985...

Страница 14: ...920 950 985 1015 1045 1075 1100 1130 Turns Open 4 3 2 5 1 5 5 5 5 4 5 3 5 3 2 5 2 1 5 1 4 3 5 3 2700 BHP 0 60 0 65 0 70 0 75 0 80 0 86 0 91 0 97 1 02 1 08 1 14 1 20 1 26 1 32 1 38 1 44 Sheave Mtr B B...

Страница 15: ...1 1 47 1 53 1 59 1 68 1 75 1 83 1 90 1 96 2 02 2 08 Sheave Mtr A A A A A A A A A A C C C C E E RPM 765 800 835 870 900 930 960 990 1015 1045 1070 1100 1125 1150 1175 1200 Turns Open 6 5 4 5 4 3 5 3 2...

Страница 16: ...31 1 37 1 43 1 49 1 55 1 62 1 68 1 75 1 81 1 88 1 95 Sheave Mtr B B B B A A A A A A A A A A A C RPM 740 770 805 840 875 905 935 965 995 1020 1050 1075 1105 1130 1155 1180 Turns Open 4 3 2 5 2 6 5 5 5...

Страница 17: ...ve Mtr A A A A A A A A D E E E RPM 970 995 1020 1045 1070 1100 1125 1145 1170 1195 1215 1240 Turns Open 4 5 4 3 5 3 2 5 2 1 5 1 5 1 3 5 3 2 5 4600 BHP 2 39 2 45 2 54 2 63 2 72 2 83 2 92 3 00 3 10 3 18...

Страница 18: ...Motor Quantity 1 Standard Motor hp kW 1 0 75 2 1 49 3 2 24 Large Motor hp kW 2 1 49 3 2 24 5 3 73 Blower No of Blowers 1 Blower Wheel Size D x W in cm 12 x 12 30 48 x 30 48 Water Connection Size FPT...

Страница 19: ...LEFT VIEW AIR COIL SIDE LEFT RETURN END DISCHARGE CBP EAP BSP CAP CAP FRONT E D F G CAP CBP CAP EAP BSP FRONT FRONT CONTROL BOX PLAN VIEW TOP V S U RIGHT RETURN RIGHT VIEW AIR COIL SIDE RIGHT RETURN E...

Страница 20: ...8 18 3 N A N A 20 HBH160 H 208 3 60 197 254 A B C 2 23 2 164 0 8 5 54 9 60 7 5 600 80 H 208 3 60 197 254 D E 2 23 2 164 0 13 8 60 2 66 0 5 600 80 F 460 3 60 414 506 A B C 2 11 2 75 0 4 1 26 5 29 3 N...

Страница 21: ...EQFGU QT 8 QRGTCVKQP FKUEQPPGEV 4 NGCF CV QT 8 QRGTCVKQP FKUEQPPGEV 8 1 NGCF CV CPF CVVCEJ 40 NGCF VQ PUWNCVG QRGP GPF QH 8 1 NGCF 5WHHKZ FGUKIPCVGU CUUQEKCVKQP YKVJ GCF EQORTGUUQT 5WHHKZ YKVJ CI EQOR...

Страница 22: ...g m3 foil backed fiber insulation for ease of cleaning Insulation placement shall be designed in a manner that will eliminate any exposed edges to prevent the introduction of glass fibers into the air...

Страница 23: ...Pa working water pressure The refrigerant to water heat exchanger shall be electro coated with a low cure cathodic epoxy material a minimum of 0 4 mils thick 0 4 1 5 mils range on all surfaces The bla...

Страница 24: ...t 5 minutes after trip if the fault has cleared If a fault occurs 3 times sequentially without thermostat meeting temperature then lockout requiring manual reset will occur j Ability to defeat time de...

Страница 25: ...h memory stop and PT port c Y strainer with blowdown valve bronze material FPT connections d Motorized water valve slow acting 24v FPT connections Hose Kit Assemblies The following assemblies ship wit...

Страница 26: ...OOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQF...

Отзывы: