Heat Controller HBH Series Скачать руководство пользователя страница 4

Engineering Design Guide 

HBH SERIES 

Heat Controller, Inc.

4

Step 1  Determine the actual heating and cooling loads at the 

desired dry bulb and wet bulb conditions.

Step 2  Obtain the following de sign parameters: Entering water 

temperature, water fl ow rate in GPM, air fl ow in CFM, 
water fl ow pressure drop and design wet and dry bulb 
temperatures. Air fl ow CFM should be between 300 and 
450 CFM per ton. Unit water pressure drop should be 
kept as close as possible to each other to make water 
balancing easier. Go to the ap pro pri ate tables and fi nd 
the proper indicated water fl ow and water tem per a ture. 

 Step 3  Select a unit based on total and sensible cooling 

conditions. Select a unit which is closest to the actual 
cooling load.

Step 4  Use data from performance tables at the design water 

fl ow and water temperature. Read the total and sensible 
cooling capacities (Note: interpolation is per mis si ble, 
ex trap o la tion is not). 

Step 5  Read the heating capacity. If it exceeds the design criteria 

it is acceptable. It is quite normal for Water-Source Heat 
Pumps to be selected on cooling capacity only since the 
heating output is usually greater than the cooling capacity.

Step 6  Determine the correction factors associated with the 

variable factors of dry bulb and wet bulb (page 14).

 

Corrected Total Cooling = 

 

tabulated total cooling x wet bulb correction.

 

Corrected Sensible Cooling = 

 

tabulated sensible cooling x wet/dry bulb correction.

Step 7  Determine the correction factor associated with antifreeze 

in system loop. If heating EWT is 50°F or below you 
may have to use antifreeze. Calculate leaving water 
temperature per performance data selection notes (page 
18). If antifreeze is required, use correction table for 
correcting total and sensible capacities.

Step 8  Compare the corrected capacities to the load 

re quire ments. Normally if the capacities are within 10% 
of the loads, the equipment is ac cept able. It is better to 
undersize than oversize, as undersizing improves humidity 
control, reduces sound levels and extends the life of the 
equip ment.

Step 9  When completed, calculate water temperature rise and 

assess the selection. If the units selected are not within 
10% of the load cal cu la tions, then review what effect 
chang ing the GPM, water temperature and/or air fl ow and 
air tem per a ture would have on the corrected capacities. 
If the desired capacity cannot be achieved, select the 
next larger or smaller unit and repeat the procedure. 
Remember, when in doubt, undersize slightly for best 
performance. 

Example Equipment Selection For Cool ing

Step 1 Load Determination:

Assume you have determined that the appropriate cooling load 
at the desired dry bulb 80°F and wet bulb 65°F con di tions is as 
follows:

  Total Cooling.................................................90,500 BTUH
  Sensible Cooling...........................................73,300 BTUH
  Entering Air Temp...........80°F Dry Bulb / 65°F Wet Bulb

Step 2 Design Conditions:

Similarly, you have also obtained the following design 
pa ram e ters:

  Entering Water Temp (Cooling).................................90°F
  Entering Water Temp (Heating).................................60°F
  Water Flow (Based upon 12°F rise in temp.)......18 GPM
  Air Flow..............................................................2,800 CFM

Step 3, 4 & 5 HP Selection:

After making your preliminary selection (TCH096), we enter the 
data from tables at design water fl ow and water tem per a ture and 
read Total Cooling, Sens. Cooling and Heat of Rej. ca pac i ties:

  Total Cooling....................................................93,200 BTUH
  Sensible Cooling..............................................70,390 BTUH
  Heat of Rejection...........................................120,100 BTUH
 Airfl ow...................................................................3,200 CFM

Step 6, 7 & 8 Entering Air, Airfl ow and Antifreeze Corrections:

Next, we determine our correction factors.

Airfl ow 2800 ÷ 3200 = 88%   

Antifreeze - None

 

 

Table 

Ent Air   Air Flow      Cor rect ed

  Corrected Total Cooling = 93,200 x .977 x .976 x 1 = 88,871
  Corrected Sens Cooling = 70,390 x 1.088 x .933 x 1=71,453
  Corrected Heat of Rej. = 120,100 x .998 x .976 =116,983

Step 9 Water Temperature Rise Calculation & As sess ment:

  Rise = Heat of Reject ÷ (GPM x 500)

  Actual Temperature Rise 116,983 ÷ 9,000 = 13.0°F       

When we compare the Corrected Total Cooling and Corrected 
Sensible Cooling fi gures with our load re quire ments stated in Step 
1, we discover that our selection is /- 10% of our sensible 
load requirement. Fur ther more, we see that our Cor rect ed Total 
Cooling fi gure is slightly undersized as recommended, when 
compared to the actual in di cat ed load.

Alternate Step 7: If your EWT for heating is 40°F then system 
requires antifreeze. If a solution of 15% Propylene Glycol is 
required, then:

  Corrected Total Cooling = 88,871 x .986 = 87,626
  Corrected Sens Cooling =  71,453 x .986 = 70,452

Selection Procedure

Содержание HBH Series

Страница 1: ...Heat Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com ENGINEERING DESIGN GUIDE Commercial Horizontal Packaged Water Source Heat Pump HBH Series 6 10 Tons...

Страница 2: ...Data HBH120 10 Performance Data Correction Tables 11 Antifreeze Correction Table 12 Blower Performance Data HBH072 Standard Unit 13 Blower Performance Data HBH096 Standard Unit 14 15 Blower Performanc...

Страница 3: ...or desuperheater capacity Mbtuh FPT female pipe thread KW total power unit input kilowatts LAT leaving air temperature F LC latent cooling capacity BTUH LWT leaving water temperature F MBTUH 1000 BTU...

Страница 4: ...d assess the selection If the units selected are not within 10 of the load calculations then review what effect changing the GPM water temperature and or air flow and air temperature would have on the...

Страница 5: ...n horizontal units Cabinetry Compact design galvanized steel construction FPT water connections high and low voltage knockouts filter and filter brackets All horizontal units have field convertible di...

Страница 6: ...for AHRI is 3 0 turns open Note 3 All HBH120 ratings 4000CFM 1888 l s w 30GPM 1 89 l s Sheave setting for AHRI is 3 0 turns open Note 4 Cooling capacities based upon 80 6 F DB 66 2 F WB entering air t...

Страница 7: ...cutout due to the activation of the Low Temperature Protection JW3 should never be clipped for standard range equipment or systems without antifreeze Example At 50 F EWT Entering Water Temperature an...

Страница 8: ...0 3 9 9 1 73 5 54 7 5 2 91 2 14 1 106 7 5 9 86 5 109 1 5 3 85 10 0 0 4 0 8 67 1 52 1 6 0 87 7 11 2 103 7 5 8 83 8 107 9 5 2 15 0 1 9 4 4 69 8 53 3 5 7 89 2 12 4 108 0 5 9 87 8 109 6 5 3 20 0 3 9 8 9 7...

Страница 9: ...108 4 5 1 24 0 6 3 14 5 99 7 73 1 6 9 123 2 14 5 143 5 8 09 115 9 109 4 5 2 85 12 0 1 1 2 7 92 3 70 0 8 0 119 6 11 6 138 3 7 98 111 1 107 9 5 1 18 0 3 4 7 7 95 7 71 4 7 5 121 3 12 8 145 3 8 13 117 5 1...

Страница 10: ...4 8 30 0 9 4 21 7 126 9 91 0 8 8 157 1 14 4 186 9 11 2 148 6 111 2 4 9 85 15 0 2 0 4 6 116 4 86 5 10 2 151 2 11 5 179 5 11 0 141 9 109 5 4 8 22 5 5 1 11 9 121 1 88 5 9 6 153 8 12 7 189 4 11 3 151 0 1...

Страница 11: ...ier Entering DB F Power Heat of Rejection 60 65 70 75 80 80 6 85 90 95 50 0 7335 0 8825 0 9782 0 7834 55 0 8063 0 6757 0 8842 1 1119 0 9836 0 8424 60 0 8830 0 6734 0 8817 1 0918 0 9900 0 9301 65 0 977...

Страница 12: ...989 0 997 1 070 15 0 986 0 986 1 009 0 968 0 990 1 210 25 0 978 0 978 1 014 0 947 0 983 1 360 Methanol 5 0 995 0 995 1 002 0 989 0 997 1 070 15 0 990 0 990 1 007 0 968 0 990 1 160 25 0 982 0 982 1 012...

Страница 13: ...5 4 3 5 3 2 5 2 1 5 2500 BHP 0 52 0 57 0 61 0 66 0 72 0 78 0 83 0 89 0 94 1 00 1 03 1 08 1 14 1 20 1 25 1 31 Sheave Mtr B B A A A A A A C E E E E E E E RPM 620 660 700 740 780 815 850 885 920 950 985...

Страница 14: ...920 950 985 1015 1045 1075 1100 1130 Turns Open 4 3 2 5 1 5 5 5 5 4 5 3 5 3 2 5 2 1 5 1 4 3 5 3 2700 BHP 0 60 0 65 0 70 0 75 0 80 0 86 0 91 0 97 1 02 1 08 1 14 1 20 1 26 1 32 1 38 1 44 Sheave Mtr B B...

Страница 15: ...1 1 47 1 53 1 59 1 68 1 75 1 83 1 90 1 96 2 02 2 08 Sheave Mtr A A A A A A A A A A C C C C E E RPM 765 800 835 870 900 930 960 990 1015 1045 1070 1100 1125 1150 1175 1200 Turns Open 6 5 4 5 4 3 5 3 2...

Страница 16: ...31 1 37 1 43 1 49 1 55 1 62 1 68 1 75 1 81 1 88 1 95 Sheave Mtr B B B B A A A A A A A A A A A C RPM 740 770 805 840 875 905 935 965 995 1020 1050 1075 1105 1130 1155 1180 Turns Open 4 3 2 5 2 6 5 5 5...

Страница 17: ...ve Mtr A A A A A A A A D E E E RPM 970 995 1020 1045 1070 1100 1125 1145 1170 1195 1215 1240 Turns Open 4 5 4 3 5 3 2 5 2 1 5 1 5 1 3 5 3 2 5 4600 BHP 2 39 2 45 2 54 2 63 2 72 2 83 2 92 3 00 3 10 3 18...

Страница 18: ...Motor Quantity 1 Standard Motor hp kW 1 0 75 2 1 49 3 2 24 Large Motor hp kW 2 1 49 3 2 24 5 3 73 Blower No of Blowers 1 Blower Wheel Size D x W in cm 12 x 12 30 48 x 30 48 Water Connection Size FPT...

Страница 19: ...LEFT VIEW AIR COIL SIDE LEFT RETURN END DISCHARGE CBP EAP BSP CAP CAP FRONT E D F G CAP CBP CAP EAP BSP FRONT FRONT CONTROL BOX PLAN VIEW TOP V S U RIGHT RETURN RIGHT VIEW AIR COIL SIDE RIGHT RETURN E...

Страница 20: ...8 18 3 N A N A 20 HBH160 H 208 3 60 197 254 A B C 2 23 2 164 0 8 5 54 9 60 7 5 600 80 H 208 3 60 197 254 D E 2 23 2 164 0 13 8 60 2 66 0 5 600 80 F 460 3 60 414 506 A B C 2 11 2 75 0 4 1 26 5 29 3 N...

Страница 21: ...EQFGU QT 8 QRGTCVKQP FKUEQPPGEV 4 NGCF CV QT 8 QRGTCVKQP FKUEQPPGEV 8 1 NGCF CV CPF CVVCEJ 40 NGCF VQ PUWNCVG QRGP GPF QH 8 1 NGCF 5WHHKZ FGUKIPCVGU CUUQEKCVKQP YKVJ GCF EQORTGUUQT 5WHHKZ YKVJ CI EQOR...

Страница 22: ...g m3 foil backed fiber insulation for ease of cleaning Insulation placement shall be designed in a manner that will eliminate any exposed edges to prevent the introduction of glass fibers into the air...

Страница 23: ...Pa working water pressure The refrigerant to water heat exchanger shall be electro coated with a low cure cathodic epoxy material a minimum of 0 4 mils thick 0 4 1 5 mils range on all surfaces The bla...

Страница 24: ...t 5 minutes after trip if the fault has cleared If a fault occurs 3 times sequentially without thermostat meeting temperature then lockout requiring manual reset will occur j Ability to defeat time de...

Страница 25: ...h memory stop and PT port c Y strainer with blowdown valve bronze material FPT connections d Motorized water valve slow acting 24v FPT connections Hose Kit Assemblies The following assemblies ship wit...

Страница 26: ...OOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQF...

Отзывы: