Heat & Glo • RED60 • 2159-900 Rev. B • 12/09
26
Figures 7.7, 7.8, 7.9 and 7.10 show possible framing
techniques.
WARNING! Risk of fi re and burns! DO NOT install PVI-
DVP with the access panel facing upward. Overheating
may occur.
ACCESS PANEL
Figure 7.7 PVI-SLPMounted to Horizontal Surface
ACCESS PANEL
Note: AN 8 X 16 inch framed
hole is required in front of the
access panel.
This hole may be covered with
an open air louvered cover.
Figure 7.8 PVI-SLP Mounted to Vertical Surface
CHASE
APPLIANCE
SCREWS
Note: AN 8 X 16 inch
framed hole is required in
front of the access panel.
This hole may be covered
with an open air louvered
cover.
Figure 7.9 Mount PVI-SLP to Chase
Figure 7.10 PVI-SLP Mounted with Fresh Air Access
1/2 IN. MAX. FROM
BACK OF OPEN
AIR COVER
SHEETROCK
ADJUST BRACKET
TO SPECIFIED DEPTH
LOUVERED OR
OPEN AIR WALL
COVER
Figure 7.10 and Figure 7.11 show the proper installation
of the PVI-DVP if a louvered register is being used to
provide free air.
WARNING! Risk of fire and burns! DO NOT install
PVI-DVP with the access panel facing upward.
Overheating may occur.
Note: An 8 X 16 inch framed hole is required in front of the
access panel. This hole may be covered with an open air lou
vered cover.
Note:
If the access
cover is not louvered,
the 1/2 in. clearance
should change to a
minimum of 2 in.
Î