10
Heat & Glo • 6000TRSI-AUC • 2078-900 Rev. Q • 6/10
Figure 1.8 Straight Out Horizontal Flueing
H
H
MIN. RUN
MAX. RUN
13.1" (331 mm)
24" (610 mm)
H
Figure 1.9 Flueing with One 90° Elbow
V
H
1´ MIN. (0.30 M)
2´ MAX. (0.61 M)
2´ MIN. (0.61 M)
4´ MAX. (1.22 M)
3´ MIN. (0.91 M)
6´ MAX. (1.83 M)
4´ MIN. (1.22 M)
8´ MAX. (2.44 M)
24´ MAX. (7.32 M)
8´ MAX. (2.44 M)
V
H
ONE (1) 90-DEGREE ELBOW
Figures 1.9 and 1.10 show an installation using one (1)
90-degree elbow. Dimension V is listed as
MINIMUM
vertical dimensions and dimension H is listed as cor-
responding
MAXIMUM
horizontal dimensions.
TWO (2) 90-DEGREE ELBOWS
Figures 1.11 and 1.12 show examples of possible in-
stallations using two (2) 90-degree elbows. Dimension
V is listed as
MINIMUM
vertical dimensions, dimension
H is listed as
MAXIMUM
beginning horizontal dimen-
sions, and dimension H + H
1
is listed as corresponding
TOTAL MAXIMUM
horizontal dimensions.
THREE (3) 90-DEGREE ELBOWS
Figures 1.13 through 1.15 show examples of possible
installations using three (3) 90-degree elbows. Dimen-
sions V are listed
MINIMUM
fi rst vertical dimensions
and dimensions H are listed as beginning
MAXIMUM
horizontal dimensions. Dimensions H + H
1
and H +
H
1
+ H
2
are listed as
TOTAL MAXIMUM
horizontal
dimensions. Dimensions V + V
1
are listed as
TOTAL
MAXIMUM
vertical dimensions.
ELBOWS
The fl ue systems installed on this gas heater may also
include one (1), two (2), or three (3) 90 - degree elbow
assemblies.
Figures 1.9 through 1.15 and their corresponding
tables show examples of fl ue confi gurations using
elbows. The relationships of vertical rise to horizontal
run in fl ue confi gurations using elbows
MUS
T be strictly
adhered to.
STRAIGHT OUT HORIZONTAL FLUE SYSTEM
Figure 1.8 shows straight out horizontal fl ue systems
approved for use on this model.